Consolidated Solicitation Questions for UPS.pdf
PDF 91 KB Posted
- Attached to
- Uninterruptable Power Supply (UPS) Federal contract opportunity
- Solicitation number
- FA570225R0002
About this file
This document is a Consolidated Solicitation Questions file for an Uninterruptible Power Supply (UPS) Installation project at Al Udeid Air Base, Qatar. The solicitation seeks qualified contractors to design, procure, install, test, and commission UPS systems for Buildings B5506 and B5507, with a project magnitude between $250,000 and $500,000. Key technical requirements include installing specific power modifications such as multiple 1-phase and 3-phase circuit breakers with various voltage and amperage specifications, installing NEMA receptacles, and configuring UPS systems with a 60-minute backup time.
Administrative and process details include site visit permissions (coordinated through the Facility Manager), a preferred SECRET security clearance for vendors, and electronic communication channels. Vendors must provide detailed UPS specifications, including ratings, configuration, and input/output voltage. The project requires compliance with technical standards, and while factory certification for installation electricians is not mandatory, a certified UPS manufacturer representative must be present for system start-up. Potential vendors should note that existing CRAC units are already in the facility, and no additional CRAC unit proposals are needed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA5702-19-C-0022 Construct 763 ERS IC As Build - Attach.pdf | ||
| B5507. 58 -FA5702-19-C-0022 Construct 763 ERS IC - As Build - Attach (1).pdf | ||
| Solicitation - FA570225R0002.pdf | ||
| Attachment 1 B5507 Electrical Requirements.pdf | ||
| Attachment 2 Functional Performance Test Example.pdf | ||
| Attachment 3- Floor Plans.pptx | PPTX presentation | |
| STATEMENT OF WORK.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Consolidated Solicitation Questions – UPS Installation
1. Technical Requirements & Scope of Work:
• UPS System Specifications:
o Question: Please specify single-phase or three-phase UPS, capacity (full load), and provide SLD. We need UPS ratings, load details, and confirmation if this includes a full data center turnkey solution (including scope). (Multiple vendors) o Action: Provide detailed UPS specifications, including phase, capacity, SLD, and load details. Clarify if the project scope encompasses a full data center turnkey solution. If applicable, provide the complete scope of work.
o Answers: New Power Modifications Required for OL15 Specifically: Install qty two
(2) new 1-phase 120 V 50/60 Hz, 20 A circuit breakers for the 91000 BAY 1 PDU Black and Grey circuit feeds. Acquire and install NEMA L5-20R receptacles and wiring for each circuit feed.
o Install qty two (2) new 1-phase 120 V 50/60 Hz, 20 A circuit breakers for the 91000 BAY 2 PDU Black and Grey circuit feeds. Acquire and install NEMA L5-20R receptacles and wiring for each circuit feed.
o Install qty one (1) new 1-phase 120 V 50/60 Hz, 15 A circuit breaker for the 91000 BAY 2 Toggle Power Strip. Acquire and install a NEMA 5-15R receptacle and wiring for each circuit feed.
o Install qty one (1) new 208-240 V 50/60 Hz, 30 A circuit breaker for the 95100 PDU3 circuit feed. Acquire and install NEMA L6-30R receptacle and wiring for each circuit feed.
o Install qty one (1) new 208-240 V 50/60 Hz, 30 A circuit breaker for the 95100 PDU4 circuit feed. Acquire and install NEMA L6-30R receptacle and wiring for each circuit feed.
o Install qty one (1) new 208-240 V 50/60 Hz, 30 A circuit breaker for the 95200 PDU5 circuit feed. Acquire and install a NEMA L6-30R receptacle and wiring for each circuit feed.
o These are the new power modifications required please match our above requirements with the appropriate one-phase or three-phase UPS
• Site Survey:
o Question: Request permission for a site visit to Buildings B5506 & B5507 (Rooms 101 & 103 in B5507) to assess existing infrastructure, measure spaces, and identify logistical needs. (One vendor) o Action: Confirm whether site visits are permissible and, if so, outline the process for scheduling and any access requirements.
o Answers: site visits are permissible. Work with Facility Manager to schedule and access the building. DSN: 455-1152, 455-4039 currently SMSgt James Coles, but will change beginning of June
• Electrical Drawings and Load Details:
o Question: Request detailed electrical drawings and load schedules for accurate quoting, as current attachments only include telecommunication drawings.
(Multiple vendors) o Action: Provide complete electrical drawings, including load schedules, for both buildings.
o Answers: Need electrical drawings. Provided documentation for GSS system being installed.
• UPS Output and Input Confirmation:
o Question: Confirm UPS output (208V, 3 Phase (120V, 1 Phase), 50 Hz, 4 wire) and input (415V, 3 Phase, 50 Hz). (One vendor) o Action: Confirm the requested UPS output and input specifications.
o Answers: Please reference answers to question one to determine output and input requirements
• Additional Equipment and Installation Requirements:
o Question: Confirm if the offer should include: incoming power cable (with panel location), distribution boards (with schedule), conduit/wiring for PDU circuits, receptacles (L5-15R, L5-20R, L6-30R), and separate grounding for UPS. (One vendor) o Action: Clarify the inclusion or exclusion of each listed item in the vendor's scope of responsibility. Provide specific details where necessary (e.g., panel location, distribution board schedule).
o Answers: The conduit and wiring for PDU circuits is required. Please reference the L3Harris requirements document. Greg o Question: The technical requirements state that “All technicians and electricians must be factory-certified by the proposed UPS system manufacturer.” No UPS manufacturer certifies electricians from installation firms.
o Action: Would it be permissible to ensure that a certified UPS manufacturer representative is present for and performs the UPS start-up, but that the installation electricians do not need to be certified by the factory?
o Answers: Yes
2. Project Details & Documentation:
• UPS Rating and Configuration:
o Question: Please provide the required UPS rating (kVA/kW), quantities, configuration (single or parallel), input/output voltage, type (modular or standalone), battery type (VRLA or NiCad), and confirm backup time (stated as 7 minutes in the Function Performance Test document, 60 minutes elsewhere). (Multiple vendors) o Action: Provide comprehensive details on UPS rating, configuration, and specifications. Clarify any discrepancies in backup time requirements.
o Answers: The UPS rating for power should be answered in the facility document I provided. It should answer what will be needed. Back-up time should be 60 minutes.
o
• Bill of Quantities (BOQ):
o Question: Request the BOQ, if available. (Multiple vendors) o Action: Provide the BOQ or confirm if it will be made available.
• CRAC Units:
o Question: Can the vendor also design and propose CRAC units based on the provided layout? (One vendor) o Action: Clarify if proposals for CRAC units fall within the project scope.
o Answers: There are CRACs already in the facility. There is not a need for a bid on a
CRAC
3. Administrative and Process Questions:
• Vendor Requirements:
o Question: Are there mandatory vendor registration, prequalification, or security clearance requirements? (One vendor) o Action: Clarify any vendor-specific requirements or qualifications.
o Answers: Security clearance requirement preferred is SECRET
• Site Visits:
o Question: Are site visits necessary or permitted? (Multiple vendors) o Action: Provide a definitive answer regarding site visits and, if allowed, outline the process.
o Answers: Site visits allowed schedule with Facility manager see above answer for contact information
• Past Performance:
o Question: Are there specific past performance records or supporting documentation preferred for submission? (One vendor) o Action: Clarify requirements for demonstrating past performance, including specific documentation preferences.
o Answers: There is no past performance data to provide.
• Submission Format and Communication:
o Question: What is the preferred submission format and channel for ongoing communication? (One vendor) o Action: Specify the preferred submission format (e.g., electronic, hard copy) and communication channels for the project.
o Answers: Electronic email, reference above DSN phone numbers.
4. Security Clearance:
• Question: Is prior work experience at AUAB sufficient to comply with the clause requiring personnel with access to sensitive information to possess an active US Secret Clearance?
(One vendor)
• Action: Reiterate the security clearance requirements and clarify if prior work experience at AUAB supersedes the need for individual clearances.
• Answers: SECRET clearance preferred if not escort is required, and proper vetting of vendors is required.