Date: 10 February 2016 1 Technical Specifications-Revision 2
TECHNICAL SPECIFICATIONS FOR
ASHE 16-1037
RENOVATE FAC. 1381 FOR 606 ACS BED DOWN,
AREA F, AVIANO AB, ITALY-REVISION 2
ADDENDUM #1_____________________________________________________________________
Paragraph 2.WORKS LOCATION:
-After Fac.#13809 add the following: “and at Fac#1380”.
-Communication Requirements-Floor Plan: be advised that the
- ” Number of NIPR CPU Drops has to be read E.a. 37”
- Given list shall mention 7 additional drops as follows (blue colour)
COMMUNICATION REQUIREMENTS-FLOOR PLAN-REPLACING FLOOR PLAN
PAGE 5 OF TECHNICAL SPECIFICATIONS –REVISION 2
Date: 10 February 2016 2 Technical Specifications-Revision 2
Paragraph 4. WORK DESCRIPTION:
Item 4m., changes as following:
Furnishing and installation anodized aluminum double door of main entrance, size 180x240 cm., the opening will be controlled by keyboard numeric code. The article includes top thermopane glass 6 + 12 + 6 mm., blind transom, door closers, panic hardware, adjustable hinges min. 3 ea., electrical power supply line, removal/reinstallation part of false ceiling which interferes with door installation and any other required for installation in a workmanlike manner.
Ea. 1
Item 4o., add the following:
“Number of NIPR CPU drops is Ea. 34 more Ea. 3 in room n.4 for a total Ea.37, not to consider different notes. All SIPR CPU drops will be in view, cable Cat IV and quad-ports for wall jacks”.
Item 4p., after DISANO “Lord” add the following:
“or equal”.
Item 4u., add the following:
The Fire Alarm System will be connected to central of fac. 1380, all new components will remain in the same position.
Item 4x., add the following:
The power of the new MDP is approx. 1950 A. The power of the three (3) transformers is 150/200/700 A. The size of the manual switch has to be the same of new MDP. The outlets 3P+N+G 100A that have to be installed in the 12 panels must be heavy duty standard Europeo (CEE).