Question Response Form 11 Jun 24.pdf
PDF 81 KB Posted
- Attached to
- Access Control System
- Solicitation number
- FA527024QB007
About this file
This document is a Memorandum for RFQ Interested Parties that provides responses to vendor questions regarding Solicitation FA527024QB007 for an Access Control System.
The key details are:
- The solicitation is for the installation of a new access control system (ACS) and upgrade of the current ACS software, database conversion, site control units, and infrastructure.
- The government confirmed that the existing communications wiring is expected to be reused unless deficiencies or compatibility issues are found.
- The server for the new ACS will be located in Building 180, Room 115, and the workstation in Building 103, Room 104.
- There are 39 existing Entrostar panels that will connect to the new server, along with 12 cameras and 66 card readers.
- The new ACS will support only the buildings within the 1 SFG compound, not the entire base.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ 0005.pdf | ||
| RFQ 0004.pdf | ||
| Question Response Form 3 Jun 24.pdf | ||
| Question Response Form 4 Jun 24.pdf | ||
| RFQ 0003.pdf | ||
| Question Response Form (2).pdf | ||
| Question Reponse Form.pdf | ||
| RFQ 0002.pdf | ||
| RFQ.pdf | ||
| Question Submission Form.docx | DOCX document | |
| SOW (17 May 24).pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
18 Jun 24
MEMORANDUM FOR RFQ INTERESTED PARTIES
FROM 18 CONS/PKB
SUBJECT: Receipt of Question(s) from Vendor Regarding RFQ FA527024QB007, Access Control System
The following are inquiries were submitted by a vendor on 11 Jun 24, for the subject requirement. The Government’s responses are recorded in blue:
1. Please confirm if the comms wiring to be replaced is:
i. OSP connection between each building?
ii. System communication line between workstation and Entrostar?
iii. Device communication line between Entrostar and devices?
iv. Or all of the above.
The current assumption is that all existing lines are within specification and standard. There are no existing plans to replace unless deficiencies or lack of compatibility with upgrades are found.
2. Please confirm where is the server for B180? and workstation to be located B103?
The server for B180 is in Rm. 115; the workstation for B103 will be in Rm. 104.
3. How many existing SCIF/RMS , RADC’s and other Entrostars will connect to the new server.
39 existing Entrostars.
4. Please list current equipment/system devices to be attached to the new server.
12 x Cameras
39 x Entrostar panels
66 x Card Readers
See SOW for full details.
5. Please confirm, if this server is for the whole base IDS/ACS or just buildings listed in PWS Bldg. 103 1F, Bldg. 140 1F, Bldg. 140 2F, Bldg141 2F, Bldg. 143 1F, Bldg. 146 2F,Bldg. 140 1F, Bldg. 140 2F.
Only the buildings within the 1 SFG compound.
//SIGNED//
18 CONS/PKB