374 CS Vault Upgrade Power Requirements.pdf

PDF 48 KB Posted

Attached to
Bldg 650 Vault Upgrade
Solicitation number
FA520925Q9029
Issued by

About this file

This document appears to be a detailed electrical load and power distribution specification for a data center facility with two rooms (Room A and Room B). The facility has redundant power systems with A and B sides, each capable of supporting 84 kVA, and includes comprehensive power calculations for HVAC, lighting, outlets, and equipment racks. Room A (Vault) has dimensions of 7350 mm x 7800 mm and contains 14 racks rated at 7 kVA each, while Room B (Front Room) has dimensions of 7350 mm x 4550 mm with 6 racks rated at 7 kVA each.

The power infrastructure includes 300 A 3-pole breakers for A and B sides, a 60 A 3-pole breaker for lighting/HVAC/outlets, and an alarm system. HVAC components consist of wall-mounted CRAC (Computer Room Air Conditioning) Liebert DateMate units - 8 US commercial tons in Room A and 17 US commercial tons in Room B. The load calculations account for various electrical requirements: HVAC power, convenience outlets, and lighting, with specific computations for square footage and VA/sqft. The documentation shows a 60% derate for rack power, resulting in 58.8 kVA for Room A and 25.2 kVA for Room B, ensuring precise power management and redundancy.

View the file

Other files

Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A Side Breaker = 300 A 3 -pole Breaker

A Side Load = 84 kVA

B Side Breaker = 300 A 3 -pole Breaker

B Side Load = 84 kVA (not to be double counted with A)

Lighting/HVAC/Outlet Breaker = 60 A 3 -pole

Lighting/HVAC/Outlet Load = 17.22 kVA

Place the alarm system on that 60 A too

BREAKER SPACE

A Side Breaker = 300 A 3 -pole Breaker

A Side Load 84 kVA

B Side Breaker = 300 A 3 -pole Breaker

B Side Load = 84 kVA (not to be double counted with A)

Lighting/HVAC/Outlet Breaker = 60 A 3 -pole

Lighting/HVAC/Outlet Load = 17.22 kVA

Room A (Vau1t

EQUIPMENT

7350 mm x 7800 mm

14 Racks @ 7kVA

HVAC (lx Wall CRAC Liebert DateMate)

8 US Commercial US tons of refrigeration

20A@220forHVAC 4.4kVA

Outlets

2* .180=.540kVA

Lights

360 sqft * 3 VA/sqft = kVA 1.080 VA

Therefore, A Side (UPS)

=58.8 kVA + 25.2 kVA =84 kVA

B Side (UPS redundant)

=58.8 kVA + 25.2 kVA =84 kVA

Non UPS Load (3 HVAC + 980 sqft LIGHTS+ 6 convenience OUTLETS)

= 4.4 kVA + 8.8 kVA + 0.540 kVA + 0.540 kVA + 1.860 kVA + 1.080 kVA = 17.22 kVA

Derate @ 60%

58.8 kVA

HVAC (2x Wall CRAC, Liebert DateMate)

17 US Commercial US tons of refrigeration

40A @ 220V

8.8 kVA

Outlets

3 * .180=

.540 kVA

Lights

620 sqft * 3 VA/sqft =

1.860 kVA

Room B (Front Room):

EQUIPMENT

7350 mm x 4550 mm

6 Racks @ 7 kVA

Derate @ 60%

25.2 kVA

scan09-12-2025-130626-1.pdf
scan09-12-2025-130700-1.pdf