JA-9 QA 02.pdf

PDF 267 KB Posted

Attached to
Eielson AFB Anti Vehicle Barrier Fence Installation Amendment 05
Solicitation number
FA500420B0003
Issued by

About this file

This document contains questions and answers regarding a federal solicitation for an anti-vehicle barrier fence installation at Eielson Air Force Base in Alaska.

The solicitation seeks to replace a section of perimeter fence running from the South Gate to the Hursey Gate. Bidders must attach the new fence to existing fencing at the gate locations. The period of performance is 120 days with a completion date of 30 September 2020. Questions must be submitted by 21 February 2020 and bids are due by 9 March 2020. The estimated value of the contract is between $1 million and $5 million. The selected contractor will utilize Alaskan labor but does not need to be a registered Alaskan entity. The project manager can be a non-Alaskan resident.

View the file

Other files

File Type Posted
Amendment 05.pdf PDF
JA-1 SOW.pdf PDF
Amendment 04.pdf PDF
JA-3 Fence Map Location.pdf PDF
JA-4 Submittal Register.pdf PDF
JA-5 Photos of Existing Fence.pdf PDF
JA-7 Electric Distro.JPG JPG image
JA-8 QA.pdf PDF
Amendment 03.pdf PDF
JA-6 Wage Determination.pdf PDF
JA-1 SOW.pdf PDF
JA-2 Specs.pdf PDF
JA-4 Submittal Register11 Mar 20.pdf PDF
JA-2 Specs 11 Mar 20.pdf PDF
JA-3 Fence Map Location 11 Mar 20.pdf PDF
JA-7 Wage Determination 11 Mar 20.pdf PDF
JA-1 SOW 11 Mar 20.pdf PDF
Amendment 02.pdf PDF
JA-5 Compiled UCF Drawings 11 Mar 20.pdf PDF
JA-8 Electric Distro11 Mar 20.JPG JPG image
JA-6 Photos of Existing Fence 11 Mar 20.pdf PDF
Amendment 01.pdf PDF
JA-6 Environmental Work Plan.pdf PDF
JA-8 Wage Determination.pdf PDF
JA-7 Photos of Existing Fence.pdf PDF
JA-4 Submittal Register.pdf PDF
JA-5 Compiled UFC Drawings.pdf PDF
Solicitation - FA500420B0003.pdf PDF
JA-1 SOW.pdf PDF
JA-3 Fence Map Location.pdf PDF
JA-2 Div Specs.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA500420B0003, Eielson AFB AVB Fence Questions

1. We are concerned that with possible award delays, known lead times, possible weather delays, possible delays associated with the Coronavirus, etc that the 120 day POP, or the 9/30/2020 completion date may not be sufficient to complete the project. We see that the 360 day POP will also not be allowed. Is it possible, however, that the requirement allow for the new fence to be completed within that time frame, and allow the demo of the existing fence to extend past that. It is possible, depending on the temperatures, that the demo work would/could be possible into October. With consideration of the requirement for seeding after the fence is complete, (and the new fence demolished), successful planting seems unlikely that late in the fall. Please consider and advise the bidders if any concessions can be made on this.

The period of performance shall not be extended.

2. The specs state that for line posts the only acceptable grade is "2.0" OD pipe weighing

3.65 pounds per linear foot". I believe that this is misstated. There is no readily available 2" OD fencing pipe that meets that weight. I believe that it should either be 2.375" weighing 3.65 lbs per foot, which would be Sch40 pipe, or it should be 2.375" pipe weight 3.12lbs per foot‐‐This would be SS40 pipe. The specs allow corner posts, pull posts, and gates post to be SS40 pipe, and seems that this grade should be allowed for line posts as well. SS40 pipe is lighter, stronger, less expensive, and more readily sourced from US suppliers than Sch40 pipe. SS40 has become the standard for fencing pipe. Please advise.

This was addressed in the revised specs. Use SS40 (industry standard for fencing). Both are acceptable, however.

3. The specs are calling for 2.0 oz/ft of galvanizing. The standard material, unless being used in highly corrosive environments, is 1.2oz of galvanize per sq.ft. Is the stated requirement correct? or should it be 1.2 oz/sq.ft?

Use 1.2 oz/sq ft.

4. Does the awardee need to be a registered Alaskan entity? If not, can the awardee provide a non‐Alaskan resident to perform as the Project Manager/Site Supervisor?

The awardee does not need to be a registered Alaskan entity, however they shall utilize Alaskan labor. A non‐Alaskan resident may act as the project manager/site supervisor, as they are considered management.

01 April 2020

File details come from the government source that posted it. Updated .