FA500024Q0084 - Questions and Answers.pdf
PDF 59 KB Posted
- Attached to
- FA500024Q0084 - 673d Communications Squadron Uninterruptible Power Supply (UPS) Batteries
- Solicitation number
- FA500024Q0084
About this file
This document is a set of Questions and Answers (Q&A) related to solicitation FA500024Q0084 for the procurement of Uninterruptible Power Supply (UPS) batteries and associated equipment for the 673d Communications Squadron at Joint Base Elmendorf-Richardson, Alaska.
The key details are: The solicitation requires UPS units ranging from 5kVA to 8kVA to provide 40 minutes of runtime at 100% load during power outages. Specific power requirements and receptacle types are provided for each communication closet location. Delivery is FOB Destination with a 90-day lead time. The solicitation is for all or none, and the quote submission deadline is Thursday, September 26, 2024 by 12:00PM AKST. The procuring agency is the Department of the Air Force Pacific Air Forces.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA500024Q0084 - Questions and Answers (Q&A)
1. Would you be able to provide us with the model and serial number of the UPS/battery module that needs the batteries? This is to verify the equipment and be able to supply the correct battery for the equipment
A: This requirement is for the UPS units, as well as battery modules, not just for batteries themselves. Here are the UPS unit requirements:
Basement:
- Comm Closet #1 at least 8kVA, have at least 12 outlets for equipment
- Comm Closet #2 at least 6kVA, have at least 12 outlets for equipment
- 200-240 VAC
- L6-30 plug
- Expected runtime of 40 minutes
1st Floor:
- Comm closet #1 at least 8kVA, have at least 12 outlets for equipment
- Comm closet #2 at least 6kVA, have at least 10 outlets for equipment
- 200-240 VAC
2nd Floor:
- Comm closet #1 at least 6kVA, have at least 10 outlets for equipment
- Comm closet #2 at least 8kVA, have at least 16 outlets for equipment
- 200-240 VAC
3rd Floor
- Comm closet #1 at least 5kVA, have at least 10 outlets for equipment
- Comm closet #2 at least 5kVA, have at least 10 outlets for equipment
- 200-240 VAC
2. The solicitation specifies that each UPS must maintain up to 40 minutes of runtime until a generator takes over the load. The RFQ does not appear to indicate the load percentage at which this runtime is required. Could you please clarify if the 40-minute runtime is expected under: Full load, or Partial load, and if Partial, at what percentage of load (e.g., 50%)?
A: Full load, there are no current UPS units in place to determine the current utilization of the UPS. Power utilization/requirements:
Comm Closet #1 Summary:
- Basement: 6432 watts
- 1st Floor: 5976 watts
- 2nd Floor: 4801 watts
- 3rd Floor: 2815 watts
Comm Closet #2 Summary:
- Basement: 4605 watts
- 1st Floor: 4247 watts
- 2nd Floor: 6872 watts
- 3rd Floor: 2200 watts
3. Is there is a loading dock at the delivery location?
A: No, but there is an elevator to bring the UPS between the floors. Furthermore, there is a short flight of stairs from the facility’s entrance to the elevator. Alaskan Command (ALCOM) J6 has a powered dolly that can bring the equipment up the stairs, if necessary.
4. Load information (total wattage)?
A: Power utilization/requirements:
Comm Closet #1 Summary:
- Basement: 6432 watts
- 1st Floor: 5976 watts
- 2nd Floor: 4801 watts
- 3rd Floor: 2815 watts
Comm Closet #2 Summary:
- Basement: 4605 watts
- 1st Floor: 4247 watts
- 2nd Floor: 6872 watts
- 3rd Floor: 2200 watts
The type of receptacles required to be on the UPS?
A: The power plug must be a L6-30, all power receptacles must be capable of supporting Cisco Catalyst 9400, 2960-X, 3850, 2750G, etc.
Runtime that is required (time you need the UPS to run when Utility Power drops)?
A: 40 minutes, without commercial/generator power, purely on UPS 100% load.
Rack Mount or Tower?
A: Rack mounted
5. The required voltage whether it’s 120 volt or 208 volt (240, 220)? 230 volt is international power.
A: 208V
6. Do all 4K, 5K, 6K, and 8K VA UPS need to be TAA compliance?
A: No, these are not being networked.
7. What output receptacles are you needing for all the UPS?
A: Must be capable of supporting Cisco Catalyst 9400, 2960-X, 3850, 2750G, etc.
8. 200-240 VAC Is this for all of the above units?
A: Yes, the UPS must be capable of providing 208 power to the equipment attached
L6-30 plug. What is this in reference to?
A: The power plugs the UPS utilize to connect to the facility’s power receptacles
Expected runtime of 40 minutes?
A: Yes, without commercial/generator power, purely on UPS 100% load.
File details come from the government source that posted it. Updated .