This document is a Request for Quote (RFQ) for Uninterruptible Power Supply (UPS) batteries for the 673d Communications Squadron at Joint Base Elmendorf-Richardson, Alaska. The salient characteristics specify that each UPS must support networking equipment for up to 40 minutes until a generator can take over, be rack-mountable, and have L6-30 plugs. The requirements detail the power and outlet needs for each comm closet across the basement, 1st, 2nd, and 3rd floors. The total power requirements range from 2,200 to 6,872 watts per comm closet. Vendors are required to submit quotes FOB Destination to the specified location, with a lead time of 90 days After Receipt of Order. The quotes are due by September 26, 2024, at 12:00 PM AKST. This is an all-or-none solicitation for the Pacific Air Forces.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics:

- Each UPS must be able to support networking equipment for up-to-40 minutes, until a generator can take the load.

- The UPS must be rack-mountable in a standard network equipment rack.

- L6-30 plugs are required, no hardwiring. Each comm closet only has one L6-30 plug.

- Equipment shall be shipped FOB Destination to 6230 Arctic Warrior Drive, Suite 8, Joint Base

Elmendorf-Richardson, AK 99506.

Basement:

- Comm Closet #1 at least 8kVA, have at least 12 outlets for equipment

- Comm Closet #2 at least 5kVA, have at least 12 outlets for equipment

- 200-240 VAC

- L6-30 plug

- Expected runtime of 40 minutes

1st Floor:

- Comm closet #1 at least 6kVA, have at least 12 outlets for equipment

- Comm closet #2 at least 5kVA, have at least 10 outlets for equipment

- 200-240 VAC

2nd Floor:

- Comm closet #1 at least 5kVA, have at least 10 outlets for equipment

- Comm closet #2 at least 8kVA, have at least 16 outlets for equipment

- 200-240 VAC

3rd Floor

- Comm closet #1 at least 4kVA, have at least 10 outlets for equipment

- Comm closet #2 at least 4kVA, have at least 10 outlets for equipment

- 200-240 VAC

Comm Closet #1 Summary:

- Basement: 6432 watts

- 1st Floor: 5976 watts

- 2nd Floor: 4801 watts

- 3rd Floor: 2815 watts

Comm Closet #2 Summary:

- Basement: 4605 watts

- 1st Floor: 4247 watts

- 2nd Floor: 6872 watts

- 3rd Floor: 2200 watts