Attachment 1 -9480 UPS Salient Characteristics (Revised September 24 2024).pdf
PDF 53 KB Posted
- Attached to
- FA500024Q0084 - 673d Communications Squadron Uninterruptible Power Supply (UPS) Batteries
- Solicitation number
- FA500024Q0084
About this file
This document is the Salient Characteristics for an Uninterruptible Power Supply (UPS) Contract Opportunity issued by the Department of the Air Force Pacific Air Forces.
The key details are:
- This requirement is for UPS units, battery modules, and associated networking equipment to provide up to 40 minutes of backup power in several communications closets at Joint Base Elmendorf-Richardson in Alaska.
- The UPS units must be rack-mountable, support L6-30 power plugs, and have sufficient capacity (5-8kVA) and outlets (10-16) to power the required network equipment in each closet.
- Responses to the associated Request for Quote (Solicitation #FA500024Q0084) are due by September 26, 2024 at 12:00PM AKST. Quotes must be FOB Destination with a 90-day lead time. Warranty information is also required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics (Updated September 24, 2024):
- This requirement is for the UPS units, as well as battery modules, not just for batteries themselves.
- Each UPS must be able to support networking equipment for up-to-40 minutes, until a generator can take the load.
- The UPS must be rack-mountable in a standard network equipment rack.
- L6-30 plugs are required, no hardwiring (except for 8kVA which can be hardwired). Each comm closet only has one L6-30 plug. All power receptacles must be capable of supporting Cisco Catalyst 9400, 2960-X, 3850, 2750G, etc. Typically ranges from 5-15s to 5-20s.
- Equipment shall be shipped FOB Destination to 6230 Arctic Warrior Drive, Suite 8, Joint Base Elmendorf-Richardson, AK 99506.
Basement:
- Comm Closet #1 at least 8kVA, have at least 12 outlets for equipment
- Comm Closet #2 at least 6kVA, have at least 12 outlets for equipment
- 200-240 VAC
- L6-30 plug or hardwired for 8kVA UPS
- Expected runtime of 40 minutes
1st Floor:
- Comm closet #1 at least 8kVA, have at least 12 outlets for equipment
- Comm closet #2 at least 6kVA, have at least 10 outlets for equipment
- 200-240 VAC
2nd Floor:
- Comm closet #1 at least 6kVA, have at least 10 outlets for equipment
- Comm closet #2 at least 8kVA, have at least 16 outlets for equipment
- 200-240 VAC
3rd Floor
- Comm closet #1 at least 5kVA, have at least 10 outlets for equipment
- Comm closet #2 at least 5kVA, have at least 10 outlets for equipment
- 200-240 VAC
- L6-30 plug
Comm Closet #1 Summary:
- Basement: 6432 watts
- 1st Floor: 5976 watts
- 2nd Floor: 4801 watts
- 3rd Floor: 2815 watts
Comm Closet #2 Summary:
- Basement: 4605 watts
- 1st Floor: 4247 watts
- 2nd Floor: 6872 watts
- 3rd Floor: 2200 watts