Attachment 1 - Salient Characteristics (Revised September 19 2024).pdf
PDF 68 KB Posted
- Attached to
- FA500024Q0084 - 673d Communications Squadron Uninterruptible Power Supply (UPS) Batteries
- Solicitation number
- FA500024Q0084
About this file
This document is an attachment to a Request for Quote (RFQ) for Uninterruptible Power Supply (UPS) batteries for the 673d Communications Squadron at Joint Base Elmendorf-Richardson, Alaska.
The attachment outlines the salient characteristics required for the UPS equipment, including the required runtime, rack-mountable form factor, power output, voltage, and plug type. It provides detailed specifications for the equipment needed in each communications closet, including the required kVA, number of outlets, and expected runtime. The total power requirements for each communications closet are also summarized.
The related federal contract opportunity is for the procurement of the UPS batteries, with a solicitation number of FA500024Q0084. Quotes are due by September 26, 2024, at 12:00 PM AKST, and the equipment must be delivered FOB Destination to the specified location within 90 days of the order. Vendors are required to submit a formal quote, the pricing schedule, and any other relevant documentation as part of their submission.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics (Updated September 19, 2024):
- Each UPS must be able to support networking equipment for up-to-40 minutes, until a generator can take the load.
- The UPS must be rack-mountable in a standard network equipment rack.
- L6-30 plugs are required, no hardwiring. Each comm closet only has one L6-30 plug.
- Equipment shall be shipped FOB Destination to 6230 Arctic Warrior Drive, Suite 8, Joint Base
Elmendorf-Richardson, AK 99506.
Basement:
- Comm Closet #1 at least 8kVA, have at least 12 outlets for equipment
- Comm Closet #2 at least 6kVA, have at least 12 outlets for equipment
- 200-240 VAC
- L6-30 plug
- Expected runtime of 40 minutes
1st Floor:
- Comm closet #1 at least 8kVA, have at least 12 outlets for equipment
- Comm closet #2 at least 6kVA, have at least 10 outlets for equipment
- 200-240 VAC
2nd Floor:
- Comm closet #1 at least 6kVA, have at least 10 outlets for equipment
- Comm closet #2 at least 8kVA, have at least 16 outlets for equipment
- 200-240 VAC
3rd Floor
- Comm closet #1 at least 5kVA, have at least 10 outlets for equipment
- Comm closet #2 at least 5kVA, have at least 10 outlets for equipment
- 200-240 VAC
Comm Closet #1 Summary:
- Basement: 6432 watts
- 1st Floor: 5976 watts
- 2nd Floor: 4801 watts
- 3rd Floor: 2815 watts
Comm Closet #2 Summary:
- Basement: 4605 watts
- 1st Floor: 4247 watts
- 2nd Floor: 6872 watts
- 3rd Floor: 2200 watts