6.1.5.1 100P Design Drawing Set - Mountain Home Chapel Kitchen Renovation2.pdf
PDF 10 MB Posted
- Attached to
- Renovate Base Chapel
- Solicitation number
- FA489726Q0025
About this file
This is a comprehensive set of architectural and engineering construction documents for the Chapel Kitchen Renovation at Facility 2606, Mountain Home Air Force Base, Idaho, under contract FA4897-19-C-A016. The project involves renovation of a kitchen facility (Room 101) with adjacent multi-purpose room (102), storage (103), and mechanical space (104).
The architectural scope includes new wall and ceiling construction with detailed finishes, door assemblies, window treatments, and cabinetry. The mechanical systems encompass HVAC modifications including removal of existing packaged unit components, installation of new supply/return ductwork with balancing dampers, two range hoods (RH-1, RH-1) operating at variable speeds, an exhaust fan (EF-1) with CO2 sensor controls, and combustion air/exhaust systems for the water heater. Fire dampers must be installed in existing ductwork above ceilings. The plumbing work includes extending domestic cold water and hot water lines, installing a 3-compartment sink with garbage disposal, grease interceptor, new water heater, recirculation pump, ice maker outlet, and drain extensions with proper venting through the roof. Natural gas service includes a solenoid shut-off valve controlled by fire alarm or manual switch. Electrical systems provide new panelboard (Panel D) with 100-amp service, lighting fixtures throughout (LED 2'x4' grid and down lights), GFCI receptacles, controls for mechanical equipment, and fire alarm integration. Fire alarm systems include replacement of pull stations, heat detectors, and door holders, with new NAC booster panel, smoke detectors, and notification devices. All work must comply with current building codes including IBC, IFC, NFPA 72, and NEC standards. Construction documentation was finalized in March 2020 with 31 sheets of plans and specifications.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Mike Perez Text Box
LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS
MECHANICAL
SYMBOLS
M E
C H
A N
I C
A L
S
Y M
B O
E G
E N
D
D
G
E N
E R
O T
E S
M-000
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
C T
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
U M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
I
H
M
E
A
R
F
R
B
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
W
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TAT E O F U TAH
JAMES E.
NIGHTINGALE
GENERAL NOTES
MECHANICALGENERAL NOTES
AutoCAD SHX Text W
AutoCAD SHX Text R
AutoCAD SHX Text 12/12
AutoCAD SHX Text
FD
AutoCAD SHX Text 8/8
AutoCAD SHX Text
FIRE DAMPER IN DUCT, W/ ACCESS PANEL REQD.
AutoCAD SHX Text
MANUAL VOLUME DAMPER
AutoCAD SHX Text
RECTANGULAR TO ROUND DUCT TRANSFORMATION
AutoCAD SHX Text RECTANGULAR TO RECTANGULAR OR ROUND TO ROUND DUCT TRANSFORMATION MAXIMUM 15° INCLUDED ANGLEEXCEPT WHERE SHOWN OTHERWISE.
AutoCAD SHX Text
R/W=1. ROUND DUCT SIMILAR TO RECTANGULAR
AutoCAD SHX Text
INCLINED DROP
AutoCAD SHX Text
INCLINED RISE
AutoCAD SHX Text
WITH RESPECT TO AIR FLOW 15°NOMINAL INCLINE WITH RADIUS TURNS=DEPTH OF DUCT.
AutoCAD SHX Text
ROUND DUCT WITH NET INSIDE DIMENSIONS SHOWN IN INCHES.
AutoCAD SHX Text
RECTANGULAR DUCT WITH NET INSIDE DIMENSIONS SHOWN IN INCHES.
AutoCAD SHX Text
CEILING AIR GRILLE WITH FLEXIBLE DUCT
AutoCAD SHX Text
CEILING SUPPLY DIFFUSER WITH FLEXIBLE DUCT
AutoCAD SHX Text
SIDEWALL EXHAUST OR RETURN REGISTER
AutoCAD SHX Text
SIDEWALL SUPPLY REGISTER
AutoCAD SHX Text
CEILING EXHAUST REGISTER, (BALANCE TO MATCH SUPPLY IF RETURN CFM IS NOT SHOWN)
AutoCAD SHX Text
CEILING RETURN REGISTER
AutoCAD SHX Text
CEILING SUPPLY DIFFUSER
AutoCAD SHX Text
TURNING VANES
AutoCAD SHX Text
ROUND DUCT - DROP
AutoCAD SHX Text
ROUND DUCT - RISE
AutoCAD SHX Text
NEGATIVE PRESSURE DUCT - DROP
AutoCAD SHX Text 12/8
AutoCAD SHX Text 12%%c
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text 12/12
AutoCAD SHX Text 12%%c
AutoCAD SHX Text
KEYED NOTE IDENTIFICATION
AutoCAD SHX Text
AutoCAD SHX Text
POSITIVE PRESSURE DUCT - RISE
AutoCAD SHX Text
POSITIVE PRESSURE DUCT - DROP
AutoCAD SHX Text
NEGATIVE PRESSURE DUCT - RISE
AutoCAD SHX Text
12/8 FO
AutoCAD SHX Text
FLAT OVAL DUCT WITH NET INSIDE DIMENSIONS SHOWN IN INCHES.
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text 19540_M-000.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text 03/12/2020
AutoCAD SHX Text
1. NEW DUCTWORK, PIPING AND EQUIPMENT SHALL BE NEW DUCTWORK, PIPING AND EQUIPMENT SHALL BE COORDINATED WITH STRUCTURE, LIGHTS, REFLECTED CEILING PLANS, ELECTRICAL CONDUIT, PLUMBING, MECHANICAL AND FIRE PROTECTION PIPING, AUDIO/VISUAL SYSTEMS, ALL OTHER TRADES AND ALL OTHER EXISTING CONDITIONS. 2. NOT ALL INFORMATION IS SHOWN ON THE HVAC NOT ALL INFORMATION IS SHOWN ON THE HVAC DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING INFORMATION ON ALL OTHER CONSTRUCTION DOCUMENTS. THE CONTRACTOR WILL BE FAMILIAR WITH THE DRAWINGS, SPECIFICATIONS, AND ADDENDUMS. 3. THE WORKING DRAWINGS ARE DIAGRAMMATIC (DRAWINGS THE WORKING DRAWINGS ARE DIAGRAMMATIC (DRAWINGS ARE NOT TO BE SCALED). BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, THEY DO NOT SHOW EVERY OFFSET, BEND OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS FOR HVAC EQUIPMENT SHALL BE CHECKED AND COORDINATED WITH THE DRAWINGS. 4. THE DRAWINGS AND SPECIFICATION HAVE BEEN THE DRAWINGS AND SPECIFICATION HAVE BEEN PREPARED TO SUPPLEMENT EACH OTHER AND THEY SHALL BE INTERPRETED AS AN INTEGRAL UNIT WITH THE ITEMS SHOWN ON ONE AND NOT THE OTHER BEING FURNISHED AND INSTALLED AS THOUGH SHOWN AND CALLED OUT IN BOTH. 5. ANY PART OF THIS INSTALLATION THAT FAILS, IS UNFIT, ANY PART OF THIS INSTALLATION THAT FAILS, IS UNFIT, OR BECOMES DAMAGED DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. 6. THE CONTRACTOR IS RESPONSIBLE FOR ALL EQUIPMENT THE CONTRACTOR IS RESPONSIBLE FOR ALL EQUIPMENT (INCLUDED IN THIS BID) CHECK-IN, SAFEKEEPING, AND DAMAGE. 7. IF FOR ANY REASON THE ROUTING OF PIPE OR IF FOR ANY REASON THE ROUTING OF PIPE OR DUCTWORK DEVIATED FROM THAT SHOWN ON THE DRAWING THE GENERAL AND MECHANICAL CONTRACTOR AND OR TIER SUBS SHALL BE RESPONSIBLE FOR ANY ADDITIONAL COST RELATED TO EXTRA HANGERS. 8. ALL MATERIALS LOCATED ABOVE CEILING ARE TO BE ALL MATERIALS LOCATED ABOVE CEILING ARE TO BE RATED FOR PLENUM INSTALLATION, TYPICAL. 9. GENERAL MECHANICAL CONTRACTOR TO PROVIDE GENERAL MECHANICAL CONTRACTOR TO PROVIDE BACKING FOR EQUIPMENT AS REQUIRED. 10. DUCTWORK DIFFUSERS, REGISTERS OR GRILLES, DUCTWORK DIFFUSERS, REGISTERS OR GRILLES, EQUIPMENT ETC. SHOWN WITH X'S SHALL BE DEMOLISHED, TYPICAL. 11. THE LOCATION AND ROUTING OF ALL EXISTING THE LOCATION AND ROUTING OF ALL EXISTING DUCTWORK, EQUIPMENT AND PIPING (INCLUDING ALL BELOW FLOOR PIPING), IS ONLY APPROXIMATE AND IS SCHEMATIC IN NATURE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE EXACT LOCATION OF ALL EXISTING SYSTEMS AND CONDITIONS. 12. DUCTWORK, DIFFUSERS, GRILLES, EQUIPMENT, ETC. DUCTWORK, DIFFUSERS, GRILLES, EQUIPMENT, ETC. SHOWN LIGHT SHALL REMAIN, TYPICAL. 13. SHEET METAL CONTRACTOR SHALL TAKE CARE TO SHEET METAL CONTRACTOR SHALL TAKE CARE TO ENSURE THAT ALL DUCTWORK OPENINGS REMAIN FREE OF DEBRIS, TYPICAL.
AutoCAD SHX Text
1. FLEXIBLE DUCT MAXIMUM LENGTH IS 5'-0", EXCEPT FLEXIBLE DUCT MAXIMUM LENGTH IS 5'-0", EXCEPT AS NOTED. SUPPORT AS REQUIRED TO AVOID "KINKS", TYPICAL. 2. PROVIDE BALANCING DAMPER AT ALL BRANCH DUCTS PROVIDE BALANCING DAMPER AT ALL BRANCH DUCTS SERVING SINGLE DIFFUSER, REGISTER OR GRILLE, TYPICAL. 3. COORDINATE EXACT PLACEMENT OF DIFFUSERS, COORDINATE EXACT PLACEMENT OF DIFFUSERS, GRILLES AND REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN, TYPICAL. 4. SEE DETAIL FOR DIFFUSER CONNECTIONS TO SEE DETAIL FOR DIFFUSER CONNECTIONS TO DUCTWORK, TYPICAL. 5. BRANCH DUCTWORK SHALL BE SIZED TO MATCH THE BRANCH DUCTWORK SHALL BE SIZED TO MATCH THE NECK SIZE OF THE DIFFUSERS, REGISTER OR GRILLE IT SERVES UNLESS NOTED OTHERWISE, TYPICAL. 6. COORDINATE MOUNTING LOCATION OF THERMOSTAT COORDINATE MOUNTING LOCATION OF THERMOSTAT WITH ARCHITECTURAL FURNISHINGS, TYPICAL. 7. COORDINATE EXACT LOCATION OF DUCTWORK WITH COORDINATE EXACT LOCATION OF DUCTWORK WITH STRUCTURAL MEMBERS, LIGHTS, REFLECTED CEILING, PLUMBING, MECHANICAL PIPING, FIRE PROTECTION, AND OTHER TRADES, TYPICAL. 8. INSTALL TURNING VANES IN ALL SQUARE LOW INSTALL TURNING VANES IN ALL SQUARE LOW PRESSURE DUCTWORK AT ELBOWS OR TEES, TYPICAL. 9. FIELD VERIFY THE FIT OF ALL DUCTWORK BEFORE FIELD VERIFY THE FIT OF ALL DUCTWORK BEFORE FABRICATION, TYPICAL. 10. CONTRACTOR SHALL OFF-SET DUCTWORK AS CONTRACTOR SHALL OFF-SET DUCTWORK AS REQUIRED WHERE STRUCTURE, LIGHTING OR PIPING CONFLICTS EXIST, TYPICAL. 11. DUCTWORK SIZES ARE FREE AREA SIZES, TYPICAL. DUCTWORK SIZES ARE FREE AREA SIZES, TYPICAL. 12. IN HARD CEILING AREAS, INSTALL REMOTE DAMPER IN HARD CEILING AREAS, INSTALL REMOTE DAMPER OPERATOR IN CEILING, SEE SPECIFICATION, TYPICAL.
Mike Perez
EXISTING
PACKAGED
UNIT
M E
C H
A N
I C
M
O L
I T
I O
N
F
L O
P
A
N
MD-101
8'0 4' 16'
KEY NOTES
VERIFY BALANCING DAMPERS EXIST IN ALL DUCT
BRANCHES AND INSTALL NEW IF ANY ARE MISSING.
EXISTING HOOD OVER OUTSIDE AIR INLET TO BE
REMOVED AND INLET EXTENDED UNDER NEW
CONSTRUCTION PHASE.
DEMOLISH ALL GRILLES, REGISTERS, AND DIFFUSERS
WHEN ARCHIECTURAL CEILING TILES ARE REMOVED.
MECHANICAL DEMOLITION FLOOR PLAN
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TAT E O F U TAH
JAMES E.
NIGHTINGALE
AutoCAD SHX Text 19540_MD-101.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 3/16"=1'-0"
AutoCAD SHX Text 03/12/2020
Mike Perez
ATC
G-1 16x16
1000 CFM
(TYP 3)
D-1 8"Ø
250 CFM
(TYP 12)
D-1 8"Ø
250 CFM
(TYP 4)
8"Ø TO
WALL CAP
R x
C
F M
S
CO2
MD
14x12"
EXISTING
PACKAGED
UNIT
EF
RH
RH
FD
FD FD
M E
C H
A N
I C
O
A
N
M-101
8'0 4' 16'
KEY NOTES
PERFORM AIR BALANCE SURVEY OF ALL EXISTING
DIFFUSERS, REGISTERS, GRILLES, AND EXISTING
PACKAGED UNIT PRIOR TO ANY DEMOLITION / WORK
BEGINNING AND PROVIDE REPORT. REPLACE
EXISTING DIFFUSERS, REGISTERS, GRILLES AND
COORDINATE LOCATION WITHIN NEW CEILING GRID.
RECONNECT TO EXISTING DUCT BRANCH AND
BALANCE TO CFM SHOWN.
3" COMBUSTION AIR INTAKE AND EXHAUST SERVING
WATER HEATER TO DISCHARGE THRU WALL WITH
MANUFACTURER PROVIDED CONCENTRIC VENT KIT.
FAN CONTROLLER, COORDINATE LOCATION WITH
STORAGE ROOM SHELVING. PROVIDED AND
INSTALLED BY JOHNSON CONTROLS.
CO2 SENSOR FOR CONTROL OF EF-1. EXHAUST FAN
TO SERVE AS REMOTE POWERED EXHAUST FOR
EXISTING PACKAGING UNIT. CO2 SENSOR TO
ENERGIZE FAN WHEN CO2 RISES TO 800 PPM IN
DINING AREA. IT IS ASSUMED THE ROLL-UP WINDOW
BETWEEN THE DINING AREA AND THE KITCHEN IS UP
WHEN THE DINING AREA IS DENSELY OCCUPIED.
SATURATED ROOM AIR FROM DINING AREA IS DRAWN
ACROSS KITCHEN AND OUT THE RANGE HOOD(S) OR
THE EXHAUST, EF-1.
REMOVE OUTSIDE AIR (OA) HOOD FROM EXISTING
PACKAGED UNIT AND REPLACE WITH NEW PLENUM
FULL SIZE OF OA OPENING. EXTEND 24x24 OA DUCT
OVER TO, AND UP BUILDING WALL TERMINATING WITH
A GOOSENECK FITTING WITH BOTTOM OF OPENING AT
MIN. 10 FT. ABOVE FINISHED GRADE.
HVAC SHUTDOWN SWITCH. INTERLOCK WITH EXISTING
PACKAGED UNIT, RANGE HOODS, AND EXHAUST FAN.
ATC DAMPER TO OPEN & CLOSE BASED ON EXHAUST
FANS OPERATION. CONTRACTOR TO SET CLOSED
POSITION OF DAMPER TO ALLOW 2,000 CFM OF
RETURN AIR TO THE EXISTING PACKAGED UNIT.
CLOSE WHEN EF-1 AND RANGE HOODS RH-1 ARE
RUNNING. CLOSED POSITION ENABLES FLOW
BALANCE TO EXHAUST FAN, EF-1. PROVIDE ACCESS
DOOR IN DUCT FOR MAINTENANCE.
THIS AREA RESERVED FOR FIRE PROTECTION
STANDPIPE AND CONTROLS.
INSTALL NEW FIRE DAMPER IN EXISTING DUCTWORK
ABOVE CEILINGS AS FIRE RATING EXTENDS TO ROOF
DECK. 3 PLACES. PROVIDE NEW ACCESS DOORS AT
DUCT FOR DAMPER MAINTENANCE ABOVE DINING
AREA LAY-IN CEILING.
MOTORIZED DAMPER TO BE NORMALLY CLOSED
WHEN FAN IS DE-ENERGIZED. OPEN ONLY WHEN FAN
IS ENERGIZED.
CONTRACTOR TO PROVIDE AND INSTALL NEW
GRILLES, REGISTERS, AND DIFFUSERS. SEE
SCHEDULES FOR DETAILS. SUPPORT ANY FLEX DUCT
TRANSITIONS PER MECHANICAL DETAILS.
MECHANICAL FLOOR PLAN
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TAT E O F U TAH
JAMES E.
NIGHTINGALE
AutoCAD SHX Text 19540_M-101.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 3/16"=1'-0"
AutoCAD SHX Text 03/12/2020
Mike Perez
M
C H
A N
I C
T
A I L
S
M-501
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TA T E O F U TAH
JAMES E.
NIGHTINGALE
AutoCAD SHX Text 19540_M-501.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text 03/12/2020
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text L
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
BRANCH DUCT TAKE-OFF & DAMPER DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text NOTE: DAMPERS SHOULD NOT BE INSTALLED CLOSER THAN TWO DUCT WIDTHS TO ELBOWS OR INTERSECTIONS.
AutoCAD SHX Text
REMOTE CEILING OPERATOR WHERE DAMPER IS INACCESIBLE
AutoCAD SHX Text
NOTE L=1/4 W (4" MIN.)
AutoCAD SHX Text
VOLUME DAMPER PROVIDE CONCEALED CEILING DAMPER REGULATOR
AutoCAD SHX Text W
AutoCAD SHX Text 45%%D
AutoCAD SHX Text %%u45%%D Y TEE
AutoCAD SHX Text %%u2-WAY 45%%D Y
AutoCAD SHX Text %%u90%%D ELONGATED TEE
AutoCAD SHX Text %%u90%%D CONICAL TEE
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
ROUND DUCT BRANCH TAKE-OFF DETAILS
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
TRUNK DUCT
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
TRUNK DUCT
AutoCAD SHX Text
TRUNK DUCT
AutoCAD SHX Text
TRUNK DUCT
AutoCAD SHX Text 11.25%%D
AutoCAD SHX Text 22.5%%D
AutoCAD SHX Text 11.25%%D
AutoCAD SHX Text 15%%D
AutoCAD SHX Text 15%%D
AutoCAD SHX Text 20%%D
AutoCAD SHX Text 20%%D
AutoCAD SHX Text 10%%D
AutoCAD SHX Text 10%%D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
(MIN.)
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
(MIN.)
AutoCAD SHX Text
(MIN.)
AutoCAD SHX Text
(MIN.)
AutoCAD SHX Text
(MIN.)
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
ROUND DUCT ELBOW DETAILS
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
5 PIECE 90°ELBOW
AutoCAD SHX Text
4 PIECE 60°ELBOW
AutoCAD SHX Text
3 PIECE 45° ELBOW
AutoCAD SHX Text
2 PIECE 30° ELBOW
AutoCAD SHX Text 11.25%%D
AutoCAD SHX Text 22.5%%D
AutoCAD SHX Text 22.5%%D
AutoCAD SHX Text 22.5%%D
AutoCAD SHX Text 11.25%%D
AutoCAD SHX Text
RECTANGULAR DUCT
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text 45%%D
AutoCAD SHX Text
FLEX DUCT (MAXIMUM 5'-0" LENGTH)
AutoCAD SHX Text
VOLUME DAMPER
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
HIGH EFFICIENCY TAKE-OFF DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
RECTANGLE TO ROUND TRANSITION
AutoCAD SHX Text 1"
AutoCAD SHX Text
SEE PLAN FOR SIZE AND LOCATION
AutoCAD SHX Text
SECURE FLEX DUCT TO BOOT INLET COLLAR
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CEILING SUPPORT CHANNEL
AutoCAD SHX Text
SUPPLY DIFFUSER- SEE PLANS FOR SIZE AND LOCATION
AutoCAD SHX Text
DIFFUSER CONNECTION BOOT LINED WITH 1" ACOUSTICAL INSULATION
AutoCAD SHX Text
FOLDED SHEET METAL STRAP EACH SIDE OF BOX UP TO STRUCTURE
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY DIFFUSER W/ FLEX DUCT DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text M-501
AutoCAD SHX Text
SUPPORT FLEX DUCT AND DIFFUSER FROM STRUCTURE ABOVE
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
DIFFUSER CONNECTION DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
NOTE: RETURN SIMILAR BUT WITHOUT DUCT
AutoCAD SHX Text
FLEX DUCT (MAXIMUM 5'-0" LENGTH) TO MIXING BOX - SEE PLAN FOR SIZE
AutoCAD SHX Text MAKE BEND RADIUS 1 1/2 x DUCT RADIUS
AutoCAD SHX Text
TIGHTENING BAND
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
RECTANGULAR DUCT SUPPORT
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
DOUBLE FOLD STRAP AND SECURE TO TOP CHORD OF TRUSSES.
AutoCAD SHX Text
#10 SHEET METAL SCREW 6" ON CENTER, TYP.
AutoCAD SHX Text
NOTE: USE SPECIFIED SPACING AND NOT LESS THAN ONE SUPPORT PER BRANCH.
AutoCAD SHX Text
BEND TAB UNDER
AutoCAD SHX Text
DUCT
AutoCAD SHX Text 1 1/4" x 16 GAUGE SHEET METAL STRAP, TYPICAL
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
ROUND DUCT SUPPORT DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
NOTE: USE SPECIFIED SPACING AND NOT LESS THAN ONE SUPPORT PER BRANCH.
AutoCAD SHX Text
3/8" DIA. BOLT AND NUT
AutoCAD SHX Text
ROUND DUCT
AutoCAD SHX Text
DOUBLE FOLD STRAP AND SECURE TO TOP CHORD OF TRUSSES.
AutoCAD SHX Text
1-1/4" X 16 GA. SHEET METAL STRAP
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
FIRE DAMPER & FIRE/SMOKE DAMPER DETAILS
AutoCAD SHX Text
NO SCALE
Mike Perez
C H
A N
I C
T
A I L
S
M-502
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TA T E O F U TAH
JAMES E.
NIGHTINGALE
Hilti Firestop Systems
Hilti Firestop Systems
System No. W-L-5028
SECTION A-A
W L
Page: 1 of 2
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC.
B. Gypsum Board* — 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 7-1/2 in.
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants — One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Copper Tubing — Nom 2 in. diam (or smaller) Type L (or heavier) copper tubing.
C. Copper Pipe — Nom 2 in. diam (or smaller) Regular (or heavier) copper pipe.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
February 08, 2006
F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4 Hr
L Rating at Ambient - Less Than 1 CFM/sq ft L Rating at 400 F - Less Than 1 CFM/sq ft
C US
CL
ASS IF IED
R
Page: 2 of 2
3. Tube Insulation — Plastics+ — Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact) to max 1-1/2 in. is required within the firestop system.
See Plastics+ (QMFZ2) category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.
The hour T Rating of the firestop system is dependent on the hourly fire rating of the wall assembly in which it is installed, the size and type of through penetrant and the pipe covering thickness, as shown in the table below:
C US
CL
ASS IF IED
R
System No. W-L-5028
W L
F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4 Hr
L Rating at Ambient - Less Than 1 CFM/sq ft L Rating at 400 F - Less Than 1 CFM/sq ft
Wall Assembly Hr Rating Type + Through Penetrant Max Diam In.
1 A 4
1 A, B, or C 2
2 A 4
2 A, B, or C 2
+Indicates penetrant type as itemized in Item 2.
4. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between pipe covering and gypsum wallboard, a min 1/2 in. diam bead of fill material shall be applied at the pipe covering/gypsum wallboard interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC — FS-ONE Sealant
*Bearing the UL Classification Mark
A
1A
1B
Hilti Firestop Systems
System No. W-L-7040
SECTION A-A
W L
1. Wall Assembly — The fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. Additional framing members shall be used to completely frame around opening.
B. Gypsum Board* — Nom 5/8 in. thick with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specified in the individual Wall and Partition Design Number. Max area of opening is 1300 in. with the dimension of 50 in. The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Steel Duct — Nom 24 in. by 48 in. (or smaller) No. 24 gauge (or heavier) galv steel duct to be installed within the firestop system. The annular space shall be min 0 (point contact) in. to a max 2 in. Duct to be rigidly supported on both sides of the wall assembly.
3. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Material*—Sealant — Min 5/8 in. thickness of fill material applied within annulus flush with both surfaces of wall. At point contact location, a min 1/2 in. diam bead of fill material shall be applied to the wall/duct interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant, CP601S Elastomeric Firestop Sealant or CP606 Flexible
Sealant.
B. Steel Retaining Angle — No. 18 MSG (0.048 in.) galv steel angles cut to fit contour of duct with a 2 in. overlap on the duct and a min 1 in. overlap on the gypsum board assembly on both sufaces of wall. 2 in. leg of angle secured to duct with min No. 8 by 3/4 in. long sheet metal screws, spaced a max of 6 in. OC. When bead of fill material is used at joint contact locations, angles shall be installed prior to full material curing.
*Bearing the UL Classification Mark
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
November 13, 2001
F Ratings — 1 and 2 Hrs (See Items 1 and 3) T Rating — 0 Hr
C US
CL
ASS IF IED
R
1A
3B3A
1B
3B 3A
System No. C-AJ-7051
F Rating - 3 Hr
T Rating - 1 Hr
R
A
3B
3A
A
SECTION A-A
Page: 2 of 2
4. Pipe Covering — Min 1/2 in. (13 mm) to max 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape.
Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and the edge of the periphery of the opening shall be min 1/2 in. (13 mm) to a max 2-1/4 in. (57 mm). When thickness of pipe covering is less than 2 in. (51 mm), the T Rating for the firestop system is 0 hr.
See Pipe Equipment Covering — Materials — (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
4A. Pipe Covering — (Not Shown) — As an alternate to Item 4, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf) units sized to the outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 8 AWG stainless steel wire spaced max 12 in. (305 mm) OC. The annular space shall be min 1/2 in. (13 mm) to max 2-1/4 in. (57 mm).
5. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant *Bearing the UL Classification Mark
C USR
CA
J 5
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
May 29, 2008Hilti Firestop Systems
System No. C-AJ-5091 F Rating — 2 Hr
T Ratings — 0 and 1 Hr (See Items 2 and 4) L Rating At Ambient — 4 CFM/Sq Ft
L Rating At 400 F — Less Than 1 CFM/Sq Ft
System No. C-AJ-1226
SECTION A-A
CA
J 1
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
June 27, 2007
F Rating — 3 Hr T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/Sq Ft L Rating At 400 F — 4 CFM/Sq Ft
C USRHilti Firestop Systems
1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 32 in.
2. Metallic Sleeve — (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wall.
2A. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded to the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
3. Through-Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be used:
A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. diam (or smaller) steel conduit.
F. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant
*Bearing the UL Classification Mark
A
34B
14B
4A
System No. C-AJ-5090
SECTION A-A
CA
J 5
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 8 in. (203 mm).
See Concrete Blocks (CAZT) Category in the Fire Resistance Directory for names of manufacturers.
2. Metallic Sleeve — (Optional) — Nom 8 in. (203 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. (76 mm) above floor or beyond both surfaces of wall.
3. Through Penetrants — One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper tubing.
C. Copper Tubing — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing.
4. Tube Insulation — Plastics+ — Nom 3/4 in. (19 mm), thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. A annular space shall be min 1/2 in. (13 mm) to max of 1-1/2 in. (38 mm).
See Plastics+ (QMFZ2) Category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.
5. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant
*Bearing the UL Classification Mark
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
May 29, 2008
F Rating — 3 Hr T Rating — 0 Hr
L Rating At Ambient — 4 CFM/Sq Ft L Rating At 400 F — Less Than 1 CFM/Sq Ft
C USR
A
2 1 5B
5A
5B
Hilti Firestop Systems
System No. C-AJ-5091
SECTION A-A
CA
J 5
Page: 1 of 2
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 19-1/2 in. (495 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance directory for names of manufacturers.
2. Metallic Sleeve — (Optional) — Nom 20 in. (508 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. (76 mm) above floor or beyond both surfaces of wall. If the steel sleeve extends beyond the top surface of the floor or both surfaces of the wall, the T Rating of the firestop system is 0 hr.
2A. Sheet Metal Sleeve — (Optional) - Max 6 in. (152 mm) diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam.
The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. (305 mm) diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor.
3. Through Penetrants — One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
May 29, 2008
F Rating — 2 Hr T Ratings — 0 and 1 Hr (See Items 2 and 4)
L Rating At Ambient — 4 CFM/Sq Ft L Rating At 400 F — Less Than 1 CFM/Sq Ft
C USR
A
5B
5A
Hilti Firestop Systems
AutoCAD SHX Text 19540_M-501.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text 03/12/2020
AutoCAD SHX Text
CAJ 7051
AutoCAD SHX Text
FIRESTOP SYSTEMS
AutoCAD SHX Text Reproduced by HILTI, Inc. Courtesy of
AutoCAD SHX Text Underwriters Laboratories, Inc.
AutoCAD SHX Text October 20, 2000
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text
US
AutoCAD SHX Text
1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any Underwriters Laboratories Inc. Classified Concrete Blocks*. Max area of Concrete Blocks*. Max area of Max area of opening is 1024 in. sq. with a max dimension of 32 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory Concrete Blocks (CAZT) category in the Fire Resistance Directory (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Steel Duct - Nom 30 by 30 in. (or smaller) No. 24 gauge (or heavier) galv steel duct. Nom 30 by 30 in. (or smaller) No. 24 gauge (or heavier) galv steel duct. One steel duct to be positioned within the firestop system. The annular space shall be min 1/4 in. to a max 1-3/4 in. Duct to be rigidly supported on both sides of floor or wall assembly. 3. Firestop System - The firestop system shall consist of the following: The firestop system shall consist of the following: A. Packing Materials - Min 3-1/2 in. thickness of min 4 pcf mineral wool batt A. Packing Materials - Min 3-1/2 in. thickness of min 4 pcf mineral wool batt - Min 3-1/2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form between the bare steel duct and the periphery of the opening . Packing material to be recessed from top surface of floor or both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1 in. thickness of fill material B. Fill, Void or Cavity Material* - Sealant - Min 1 in. thickness of fill material - Min 1 in. thickness of fill material applied within annulus, flush with top surface of floor or both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI, INC. - CP606 Flexible Firestop Sealant or FS-ONE Sealant - CP606 Flexible Firestop Sealant or FS-ONE Sealant 4. Steel Retaining Angle - Nom 2 in. by 2 in. by No. 16 gauge (or heavier) steel Nom 2 in. by 2 in. by No. 16 gauge (or heavier) steel angles attached to all four sides of the steel duct on the top surface or both surfaces of the wall. The angles shall be attached with No. 8 (or larger) steel sheet metal screws spaced max of 1 in. from each end and a max of 3 in. OC. *Bearing the UL Classification Marking
Mike Perez
C H
A N
I C
H
E D
U L
E S
M-601
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TAT E O F U TAH
JAMES E.
NIGHTINGALE
GRILLES, REGISTERS AND DIFFUSERS
MAX
ID MANUFACTURER MODEL NC DESCRIPTION
D-1 METALAIRE 5700 20 24 X 24 MODULE WITH ROUND NECK
R-1 METALAIRE H4004 30 SIDEWALL EXHAUST 24 X 12 ZERO DEFLECTION
PROVIDE PLASTER FRAME FOR GYP WALL
G-1 METALAIRE CC5 10 22 X 22 CEILING GRILLE
EXHAUST FAN SCHEDULE
AIR FAN ELECTRICAL PHYSICAL
MAXIMUM FAN DIAMETER
MANUFACTURER AIRFLOW STATIC FAN WHEEL MOTOR MOTOR MOTOR HEIGHT
AND RATE PRESSURE SPEED DIAMETER SIZE BHP SPEED
ID MODEL NUMBER LOCATION TYPE
(CFM) (IN. WATER) (RPM) (IN) (HP) (HP) (RPM)
VOLT/PH/HZ
(IN)
NOTES
EF-1 PENN BARRY WFX18VGP WALL CENTIFUGAL 1000 0.25 493 18 1/8 0.074 493 120/1/60 39 / 33 1,2
1. FAN TO BE ENABLED TO RUN WHEN EXISTING PACKAGED UNIT FAN IS ON. FAN SHALL RUN AT 100% RPM WHEN BOTH RANGE HOODS ARE OFF. FAN SHALL RUN AT 75% RPM WHEN ONLY ONE RANGE HOOD IS ON. FAN SHALL RUN AT 50% WHEN BOTH RANGE HOODS ARE ON.
2. BASIS OF DESIGN MANUFACTURERS LISTED REFERENECE EQUAL MANUFACTURERS MEETING ALL SCHEDULED PERFORMANCE DATAT AND CRITERIA IN SPECIFICATIONS ARE ACCEPTABLE.
RANGE HOOD SCHEDULE
MANUFACTURER AIR PHYSICAL ELECTRICAL
AND MAXIMUM STATIC DRIVE MAX CONTROL
MODEL NUMBER AIRFLOW PRESSURE TYPE SONES TYPE
RATE
ID LOCATION TYPE
(CFM) (IN. WATER)
NOTES
RH-1 BROAN BCSEK130SS ABOVE RANGE DUCTED 250 0.1 DIRECT 1.5 MANUAL
120 VAC,60 HZ 1,2
1. INTEGRAL FAN AND LIGHT TO BE MANUALLY CONTROLLED BY UNIT MOUNTED SWITCHES
2. BASIS OF DESIGN MANUFACTURERS LISTED FOR REFERENCE EQUAL MANUFACTURERS MEETING ALL SCHEDULED PERFORMANCE DATA AND CRITERIA IN SPECIFICATIONS ARE ACCEPTABLE
AutoCAD SHX Text 19540_M-601.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text 03/12/2020
Mike Perez
U M
B I N
G
S
Y M
B O
G
E
D
G
E N
E R
T
E S
P-000
VTR
LEGEND OF PLUMBING SYMBOLS AND ABBREVIATIONS
RPBP
GPM0.0
O F
S
T
A
S
PLUMBING PLUMBING CONT.
LINETYPES
SYMBOLS
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TAT E O F U TAH
JAMES E.
NIGHTINGALE
PLUMBING
GENERAL NOTES
PLUMBING CONT.
GENERAL NOTES
AutoCAD SHX Text 19540_P-000.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
PS
AutoCAD SHX Text
LB/HR.
AutoCAD SHX Text
GPM
AutoCAD SHX Text LATERAL STRAINER WITH BLOW-OFF VALVE, PROVIDE HOSE END WITH CAP WHERE DISCHARGE IS NOT PIPED TO DRAIN
AutoCAD SHX Text
(NAME)
AutoCAD SHX Text
FLANGE
AutoCAD SHX Text
PRESSURE GAUGE WITH PIGTAIL
AutoCAD SHX Text
PRESSURE GAUGE WITH SHUT-OFF COCK
AutoCAD SHX Text
DEMOLITION
AutoCAD SHX Text
FLEXIBLE EXPANSION JOINT
AutoCAD SHX Text
EXISTING PIPING TO BE REMOVED
AutoCAD SHX Text
EXISTING PIPING
AutoCAD SHX Text
NATURAL GAS
AutoCAD SHX Text
(NAME)
AutoCAD SHX Text
E(NAME)
AutoCAD SHX Text G
AutoCAD SHX Text
DN
AutoCAD SHX Text
UNION
AutoCAD SHX Text
FLOW METER ORIFICE
AutoCAD SHX Text
FLOW SWITCH
AutoCAD SHX Text
TEMPERATURE AND PRESSURE TEST PORT
AutoCAD SHX Text
PRESSURE SWITCH
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
GAS COCK
AutoCAD SHX Text
RELIEF VALVE
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
GLOBE VALVE
AutoCAD SHX Text
CALIBRATED BALANCING VALVE WITH GPM INDICATED
AutoCAD SHX Text
SHUT-OFF COCK FOR USE WITH PRESSURE GAUGE
AutoCAD SHX Text
FLOW METER
AutoCAD SHX Text
90° ELBOW
AutoCAD SHX Text
45° ELBOW
AutoCAD SHX Text
THERMOMETER - TEMP RANGE AS INDICATED
AutoCAD SHX Text
ARROW INDICATES DIRECTION OF FLOW IN PIPE
AutoCAD SHX Text
LEADER INDICATES DOWNWARD SLOPE
AutoCAD SHX Text
RISER - DOWN (ELBOW)
AutoCAD SHX Text
RISER - UP (ELBOW)
AutoCAD SHX Text
BRANCH - SIDE CONNECTION
AutoCAD SHX Text
CLEAN-OUT
AutoCAD SHX Text
FLOOR CLEAN-OUT OR CLEAN-OUT TO GRADE
AutoCAD SHX Text
VENT THRU ROOF
AutoCAD SHX Text
DOMESTIC COLD WATER (DCW)
AutoCAD SHX Text
DOMESTIC HOT WATER (DHW)
AutoCAD SHX Text
DOMESTIC HOT WATER RETURN (DHWR)
AutoCAD SHX Text
PLUMBING FIXTURES
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text
SECTION TAG - TOP FIGURE IS SECTION NO. BOTTOM FIGURE IS SHEET NO.
AutoCAD SHX Text
DETAIL TAG - TOP FIGURE IS DETAIL NO. BOTTOM FIGURE IS SHEET NO.
AutoCAD SHX Text
EQUIPMENT IDENTIFICATION
AutoCAD SHX Text
KEYED NOTE IDENTIFICATION
AutoCAD SHX Text
FIXTURE FROM LEVEL ABOVE
AutoCAD SHX Text P-1
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text M-101
AutoCAD SHX Text A
AutoCAD SHX Text M101
AutoCAD SHX Text
BRANCH - BOTTOM CONNECTION
AutoCAD SHX Text
BRANCH - TOP CONNECTION
AutoCAD SHX Text
FLOOR SINK
AutoCAD SHX Text
FLOOR DRAIN
AutoCAD SHX Text
AIR VENT-MANUAL
AutoCAD SHX Text
AIR VENT-AUTO
AutoCAD SHX Text
REDUCER
AutoCAD SHX Text
HOSE BIBB
AutoCAD SHX Text
PIPE CAP
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
SENSOR
AutoCAD SHX Text
INLINE PUMP
AutoCAD SHX Text
INLINE PUMP
AutoCAD SHX Text
AutoCAD SHX Text
WATER HAMMER ARRESTOR
AutoCAD SHX Text
CONCENTRIC REDUCER
AutoCAD SHX Text
ECCENTRIC REDUCER
AutoCAD SHX Text
SEWER (BELOW GRADE)
AutoCAD SHX Text
SEWER (ABOVE GRADE)
AutoCAD SHX Text
VENT (SEWER)
AutoCAD SHX Text
FCO
AutoCAD SHX Text
COTG
AutoCAD SHX Text
GATE VALVE - NON RISING STEM
AutoCAD SHX Text
ANGLE VALVE
AutoCAD SHX Text
BALANCING COCK
AutoCAD SHX Text
VALVE IN RISE
AutoCAD SHX Text
FILL PORT
AutoCAD SHX Text
DRAIN PAN AND P-TRAP
AutoCAD SHX Text
RISE OR DROP
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW PREVENTOR W/ DRAIN PAN
AutoCAD SHX Text
THERMOSTATIC MIXING VALVE
AutoCAD SHX Text 03/12/2020
AutoCAD SHX Text
1. UNLESS OTHERWISE NOTED, SLOPE PIPE AS FOLLOWS: UNLESS OTHERWISE NOTED, SLOPE PIPE AS FOLLOWS: WASTE BRANCHES: 1/4" PER FOOT; WASTE MAINS: 1/4" PER FOOT. 2. ALL WORK DONE SHALL BE PERFORMED WITH WATER ALL WORK DONE SHALL BE PERFORMED WITH WATER CONTROL IN MIND. CONTAINMENT OF WATER IS NECESSARY TO PREVENT WATER FROM DAMAGING AREAS BELOW. 3. PLUMBING DRAWINGS ARE SCHEMATIC IN NATURE. PLUMBING DRAWINGS ARE SCHEMATIC IN NATURE. FIELD VERIFY EXACT PIPE ROUTING AND COORDINATE WITH ALL OTHER TRADES. 4. NO PIPING TO RUN OVER ELECTRICAL PANELS, VFD'S NO PIPING TO RUN OVER ELECTRICAL PANELS, VFD'S OR MCC'S. PROTECT EQUIPMENT WITH A 42" DEEP ZONE IN FRONT OF PANELS, VFD'S, AND MCC'S. 5. CONTRACTOR TO PROVIDE VALVE IDENTIFICATION AND CONTRACTOR TO PROVIDE VALVE IDENTIFICATION AND LOCATION ON ALL CEILING TILES WHERE VALVES ARE LOCATED. 6. PIPING AND ROUTING SHOWN, INCLUDING ALL BELOW PIPING AND ROUTING SHOWN, INCLUDING ALL BELOW FLOOR DECK PIPING, IS APPROXIMATE. IT IS UP TO THE CONTRACTOR TO FIELD VERIFY THE EXACT LOCATION AND SIZE OF ALL PIPING. 7. REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE MOUNTING HEIGHTS, DIMENSIONS, AND OTHER REQUIREMENTS. 8. CONTRACTOR TO VERIFY CONNECTION SIDE OF CONTRACTOR TO VERIFY CONNECTION SIDE OF ACCESSIBILITY COMPLIANT FIXTURES AND ADJUST ACCORDINGLY. INSTALL FLUSH VALVES HANDLES ON WIDE SIDE OF ALL FIXTURES. 9. INSTALL ALL DOMESTIC WATER LINES BELOW INSTALL ALL DOMESTIC WATER LINES BELOW DUCTWORK. 10. INSTALL A 24" X 24" ACCESS DOOR BELOW ALL INSTALL A 24" X 24" ACCESS DOOR BELOW ALL ISOLATION VALVES, BALANCING VALVES AND WATER HAMMER ARRESTORS WHERE MOUNTED ABOVE HARD CEILINGS. 11. MOUNT ALL ISOLATION VALVES, CONTROL VALVES, MOUNT ALL ISOLATION VALVES, CONTROL VALVES, BALANCING VALVES, ETC. NEAR CEILING HEIGHT FOR ACCESSIBILITY. 12. INSTALL ALL EQUIPMENT WITH SUFFICIENT CLEARANCE INSTALL ALL EQUIPMENT WITH SUFFICIENT CLEARANCE FOR MAINTENANCE PER MANUFACTURERS RECOMMENDATION. 13. COORDINATE ALL FLOOR PENETRATIONS WITH COORDINATE ALL FLOOR PENETRATIONS WITH STRUCTURAL AND PROVIDE SLEEVES AS NECESSARY. 14. COORDINATE EXACT LOCATION OF PLUMBING WITH COORDINATE EXACT LOCATION OF PLUMBING WITH STRUCTURAL MEMBERS, LIGHTS, REFLECTED CEILING, DUCTWORK, MECHANICAL PIPING, FIRE PROTECTION, AND OTHER TRADES, TYPICAL. 15. COORDINATE THE LOCATION OF THE FLOOR DRAIN, COORDINATE THE LOCATION OF THE FLOOR DRAIN, SHOWER DRAIN, OR FLOOR SINK WITH ARCHITECTURAL AND STRUCTURAL, TYPICAL. 16. SEE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZES SEE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZES OF WASTE, VENT AND DOMESTIC WATER TO/FROM SINGLE FIXTURE. 17. COORDINATE EXACT LOCATION OF PLUMBING PIPING COORDINATE EXACT LOCATION OF PLUMBING PIPING WITH STRUCTURAL MEMBERS, LIGHTS, REFLECTED CEILING PLANS, ELECTRICAL CONDUITS, DUCTWORK, MECHANICAL AND FIRE PROTECTION PIPING, AND ALL OTHER TRADES AND ALL EXISTING CONDITIONS. 18. LOCATE CIRCUIT SETTERS, VALVES, WATER HAMMER LOCATE CIRCUIT SETTERS, VALVES, WATER HAMMER ARRESTORS, ETC. IN ACCESSIBLE LOCATIONS. PROVIDE 24"X24" ACCESS PANEL WHERE ITEM IS LOCATED ABOVE A HARD CEILING. 19. ALL PIPE AND DUCT SIZES SHALL REMAIN THE SAME ALL PIPE AND DUCT SIZES SHALL REMAIN THE SAME SIZE SHOWN, IN THE DIRECTION OF FLOW, UNTIL SHOWN OTHERWISE.
AutoCAD SHX Text INSTALL CLEANOUTS IN DRAIN PIPING AS INDICATED, AND WHERE NOT INDICATED, ACCORDING TO THE FOLLOWING. SIZE SAME AS DRAINAGE PIPING UP TO 4" NPS. USE 4" NPS FOR LARGER. DRAINAGE PIPING UNLESS LARGER CLEANOUT IS INDICATED. LOCATE AT MINIMUM INTERVALS OF 50 FT FOR PIPING 4" NPS AND SMALLER AND 100 FT FOR LARGER PIPING. LOCATE AT THE BASE OF EACH VERTICAL STACK.
AutoCAD SHX Text 20.
AutoCAD SHX Text a)
AutoCAD SHX Text b)
AutoCAD SHX Text c)
AutoCAD SHX Text CONTRACTOR TO PROVIDE VALVE IDENTIFICATION AND LOCATION ON ALL CEILING TILES WHERE VALVES ARE LOCATED. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PERTAINING TO THE PLUMBING SYSTEMS AND COORDINATE ALL DEMOLITION WORK WITH THE OWNER PRIOR TO ANY SYSTEM SHUT-DOWN. EXISTING SYSTEMS SHOWN LIGHT. PATCH AND REPAIR ALL EXISTING SURFACES DAMAGED BY DEMOLITION TO MATCH EXISTING.
AutoCAD SHX Text 21.
AutoCAD SHX Text 22.
AutoCAD SHX Text 23.
AutoCAD SHX Text 24.
Mike Perez
RPBP
EXISTING RPBP
(E)NFH
EXISTING ICE MACHINE
EXISTING
PACKAGED
UNIT
P L
U M
B I N
G
D
E M
O L
I T
I O
N
F
L O
A
N
PD-101
8'0 4' 16'
KEY NOTES
EXTEND NEW 4" SANITARY AND CONNECT TO
EXISTING APPROXIMATELY AS SHOWN. VERIFY
EXISTING INVERT AND CONTACT COR IF DEPTH IS NOT
SUFFICIENT FOR NEW WORK.
DRAIN FOR EXISTING ICE MACHINE IS CONNECTED TO
A CONDENSATE PUMP AND PUMPED TO CLOSEST
DRAIN. DEMOLISH DRAIN SYSTEM.
REMOVE EXISTING RPBP AND PIPING THAT SERVES
ICE MACHINE. INSTALL IN NEW LOCATION UNDER NEW
CONSTRUCTION PHASE.
EXISTING NON-FREEZE WALL HYDRANT TO REMAIN.
PLUMBING DEMOLITION FLOOR PLAN
181 East 5600 South
Murray, Utah 84107
O: (801) 530-3148
F: (801) 530-3150 www.vbfa.com vbfa project #: 19540
C O
N T
R A
F I
M
E
D W
N
B
Y
C K
D
B
Y
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F I
M
B E
R
S I Z
E
S U
B M
I T
T E
D
B
Y
P L
A
L E
P
L O
T
D
A T
E
D A
T E
M A
R K
D E
S C
R I P
T I O
N D
A T
E A
P P
R
C
E S
C
E N
M O
U N
T A
M
E
A
R
S
E
7654321
A N
S I
D
N
O V
E M
B E
R
T
E D
A
K
E
C
I T
Y
U
T
SHEET OF 31
F A
C
A
C H
A P
E L
K
I T
C H
N
O V
A T
I O
N
F
A C
I L I T
Y
M O
U N
T A
M
E
A
R
S
E
I D
A H
O
L
IC
EN
SE
D P
ROFESS I ONAL ENG
IN
E
ER
No. 354088
S TA T E O F U TAH
JAMES E.
NIGHTINGALE
AutoCAD SHX Text 19540_PD-101.dwg
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text
M. POND
AutoCAD SHX Text
J. NIGHTINGA
AutoCAD SHX Text
J. NIGHTINGALE
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 3/8"=1'-0"
AutoCAD SHX Text 03/12/2020
Mike Perez
(E)NFH
S-1
S-3
S-2
FS-1
OB-1
GI-1
S
EXISTING
PACKAGED
UNIT
RCP
WH
4"
3"
1 1/4"
1"
G
G
3"
2"
G
1 1/4"
FS-1
1/2"
3/4"
OB-1
1/2"
3/4"
3/4"
1/2"
2"
1 1/2" V
3" VTR
G
BELOW FLOOR
1/2"
EXPANSION
TANK
1 1/4"
1 1/4"
P L
U M
B I N
G
F
L O
A
N
P-101
8'0 4' 16'
KEY NOTES
EXTEND NEW 4" SANITARY AND CONNECT TO
EXISTING APPROXIMATELY AS SHOWN. VERIFY
EXISTING INVERT AND CONTACT COR IF DEPTH IS NOT
SUFFICIENT FOR NEW WORK.
CONNECT NEW NATURAL GAS LINE TO EXISTING,
EXTEND INTO BUILDING AND CONNECT TO NEW GAS
APPLIANCES. CONTRACTOR TO VERIFY EXISTING GAS
PRESSURE REGULATOR CAN HANDLE INCREASED
LOAD AND REPLACE IF NECESSARY. SEE SCHEMATIC
FOR PIPE SIZES.
SOLENOID VALVE IN NATURAL GAS SERVICE TO
KITCHEN. VALVE SHALL CLOSE ON ACTIVATION OF
THE BUILDING FIRE ALARM OR MANUAL SWITCH.
CONNECT NEW 1-1/4" DCW INTO EXISTING MAIN
LOCATED WITHIN THE CRAWL SPACE AND EXTEND UP
INTO STORAGE ROOM AND ROUTE TO NEW WATER
HEATER AND FIXTURES AS SHOWN.
EXTEND 3/4" DCW, 3/4" DHW AND 1/2" DHWR THRU
BACK OF CABINETRY, IN CONDITIONED SPACE, TO
3-COMPARTMENT SINK. INSULATE ALL PIPING WITH
PVC JACKETED INSULATION.
SAW CUT / PATCH FLOOR AND INSTALL 2" SAN WITHIN
THE CRAWL SPACE TO SINK S-1 & S-3. INSTALL 3" PVC
PIPE WITH LONG SWEEP ELBOW WITHIN CRAWL
SPACE FROM MECH ROOM TO 6" ABOVE FLOOR
UNDER SINK CABINETRY. ROUTE 1/2" TYPE 'L' SOFT
COPPER DCW, DHW, & DHWR LINES WITHIN 3" PVC
PIPE TO SINKS.
GREASE INTERCEPTOR UNDER 3 COMPARTMENT SINK,
DISCHARGE TO FLOOR SINK. SEMI-RECESSED INSTALL
REQUIRED FOR VERTICAL CLEANING REQUIREMENT.
MANUAL SWITCH TO CLOSE NATURAL GAS SOLENOID
SHUT OFF VALVE SERVING KITCHEN GAS APPLIANCES.
OUTLET BOX (OB-1) FOR WATER CONNECTION TO ICE
MAKER IN REFRIGERATOR. ROUTE 1/2" DCW FROM
MAIN TO OB-1 AS SHOWN.
THIS AREA RESERVED FOR FIRE PROTECTION
STANDPIPE AND CONTROLS. SEE FIRE PROTECTION
DRAWINGS. DOMESTIC COLD WATER SOURCE FROM
FIRE PROTECTION STANDPIPE.
PROVIDE TWO DOMESTIC WATER BALANCE VALVES.
ONE FOR EACH BRANCH TO ENSURE FLOW IN BOTH.
SEE ISLAND VENT DETAIL.
INSTALL RELOCATED RPBP FOR ICE MACHINE WATER
SUPPLY.
OUTLET BOX (OB-1) FOR RELOCATED ICE MAKER
ROUTE 1/2" DCW TO BOX.
PROVIDE 1/2" DHW TO UNDER COUNTER DISHWASHER
AT ISLAND. EXTEND WASTE & VENT TO ISLAND
SOURCE.
2-HORSEPOWER FOOD DISPOSAL INSTALLED AT LEFT
FACING SINK COMPARTMENT AND DIRECT
CONNECTED TO WASTE LINE BELOW.
ROUTE VENT PIPING FROM DISPOSAL WASTE PIPE
AROUND WINDOW FRAME TO CEILING CAVITY THEN
ONTO VENT PIPING CONNECTED TO VENT PIPING
CONNECTED TO VENT THRU ROOF.
PLUMBING FLOOR…