2_-_Project_Drawings_-_Pt1.pdf
PDF 12 MB Posted
- Attached to
- Repair (Sustain) NDI Lab Federal contract opportunity
- Solicitation number
- FA487718B0005
About this file
Project Drawings Part 1
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Memo__Project_Requirement_Revision.pdf | ||
| Amendment_2.pdf | ||
| FA4877-19-B-0001-0001_NDI_Lab_Amendment_1.pdf | ||
| 2_-_Project_Drawings.pdf | ||
| Procurement_RFIs.pdf | ||
| FA4877-18-B-0005_NDI_Lab_Solicitation_2.pdf | ||
| NDI_lab_Site_Visit_Sign-in_Sheet.pdf | ||
| FA4877-18-B-0005_NDI_Lab_Solicitation.pdf | ||
| 2_-_Project_Drawings.pdf | ||
| 8_-_Contractor_Environmental_Guide.pdf | ||
| 2_-_Project_Drawings_-_Pt2.pdf | ||
| 3_-_AF_Form_66.pdf | ||
| 4_-_AF_Form_3052_(Blank).xlsx | XLSX spreadsheet | |
| 2_-_Project_Drawings_-_Pt3.pdf | ||
| FA4877-19-B-0001_-_NDI_Lab_solicitation.pdf | ||
| 7_-_Contract_Security_Requirements.pdf | ||
| 6_-_Wage_Determination_(AZ33)_21_Sept_18.pdf | ||
| 5_-_DMAFB_Design_Compatibility_Guidelines_2017.pdf | ||
| 1_-_Specifications_(Statement_of_Work).pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W
W
W
W
W
W
W
W
W
WV
WV
TB
WV
E x
E x
E x
ICV
SS
SS
SS
SS
SS
CO
UT
UT
UT
UT
UT
UT
UTUT
UT
UTUT
UT
UTUT
UT
UTUT
UT
UT
UT
SS
W
W W
SD
SD
FOUND MONUMENT
DRY 4
EL = 2615.78'
N: 11678436.20 E:1673959.24
FOUND MONUMENT
DORM 2
EL = 2639.07
N: 11681394.49 E:1678981.79
3 3
3 3
(4.2%)
(4.2%)
(4.0%
(3.6%)
(8.8%)
(7.6%
(0.2%)
(9.9%)
(8 .2
(0 .6
(7 .8
(1 .5
(0 .9
(0 .6
(0 .2
(9.1%
(1.0%)(1.9%)
(0 .9
(0.8%)
(0.5%) (0.6%)
NOTE 2
134.72' 3.00'
4.
19.52'
5.73'
5.83'
(1 .9
(6 .3
(0.2%
(2.0%)(5 .2
(8 .5
(0 .3
10.00'
NDI LAB PARKING LOT
5.
BASIS OF BEARING N59°30'07"E 5829.02'
N68°38'41"E 3499.02'
N 70°04'03"E 3468.71'
BEGIN
END
6" CAST IRON PIPE TYP.
PER RECORD DRAWINGS
1 14" PIPE PER RECORD
DRAWINGS
BLDG 5406
TYP.
TYP.
BEGIN
END
BEGIN
END
1.5" (E) DOMESTIC
WATER LINE TO
BE REPLACED
PER C-102
2.
3.
O:\Projects\Louisville\IER\01297\200-01297-16029\CAD\SheetFiles\CD-101 - CIVIL DEMOLITION.dwg
SCALE:
5' 10' 20'
1" = 10'
REMOVE EXISTING CONCRETE AND BASE
EXISTING BUILDING TO REMAIN
CONSTRUCTION NOTES:
EXISTING-PROTECT IN PLACE
REMOVE
1. CONCRETE SIDEWALK
2. BRICK WALL
3. TREE
4. AC PAVEMENT
5. CONCRETE PAD
6. POWER POLE
8. CATCH BASIN
9. GAS LINE
10. POWER EQUIPMENT
11. CONCRETE CURB
12. SEWER LINE
13. SANITARY SEWER CLEANOUT
14. SANITARY SEWER MANHOLE
15. GUY WIRE
16. OVERHEAD UTILITY
17. CONCRETE PAVEMENT
18. BUILDING
20. CHILLER
21. FIRE HYDRANT
22. WATER VALVE
23. WATERLINE
24. PAVEMENT MARKINGS
25. SAWCUT (NEAREST JOINT)
RELOCATE
NOTES
1. EXISTING LANDSCAPING TO BE PROTECTED IN PLACE OR
RESTORED IN KIND.
2. CONTRACTOR TO USE EXISTING TAP AND VERIFY VALVE
IS IN PROPER WORKING ORDER.
REMOVE EXISTING AC AND BASE
CD-101
P
UTILITY METER (AS SHOWN)
UTILITY RISER (AS SHOWN)
UTILITY MANHOLE (AS SHOWN)
UTILITY VALVE (AS SHOWN)
LIGHT POLE
FIRE HYDRANT
POST
TRAFFIC SIGN
SPIGOT
DECIDUOUS TREE
CLEANOUT
FLAG (AS SHOWN)
CO
UTILITY POLE (AS SHOWN)GUY ANCHOR
UE (E) ELECTRICAL
(E) SEWER LINE
W (E) WATER LINE
SS
DRAINAGE ARROW
G (E) GAS LINE
BACKFLOW PREVENTER
(E) FENCEx x x x
MONUMENT
UT (E)COMMUNICATIONS CABLE
LEGEND
SAWCUT
PROJECT LIMITS
.0
4'
24.1690'
FINISHED FLOOR
FINISHED SURFACE
TOP OF CURB
FLOW LINE
FF
FS
TC
FL
EXISTING(XX)
PROPOSEDXX
WV
W W
W W
FHWV
W
W W
W
W
W
W
W
W
WV
WV
TB
WV
E x
E x
E x
ICV
SS
SS
SS
SS
SS
UT
UT
UT
UT
UT
UT
UTUT
UT
UTUT
UTUTUT
UT
UTUT
UT
UT
UT
SS
SD
SD
R 30.00'
STAN
D
O
FF
30.00' S
TA
N D
O
FF
30.00' S
TA
N D
O
FF
BLDG. NO. 5406
FF = 2635.41
CONTRACTOR TO HYDROSCRUB EXISTING
SEWER LINE FROM PROPOSED CLEANOUT
TO EXISTING SEWER MANHOLE
8.00'
R30.00'
STANDOFF
9 6" C900 CLASS 150 PVC
PIPE (FIRE SUPPLY)
2" C901 PE PIPE
(DOMESTIC SUPPLY)
SEE PLUMBING
PLANS FOR
CONTINUATION
SEE PLUMBING PLANS
FOR CONTINUATION OF
PIPE AND PIPE BACK
FLOW PREVENTOR
CONTRACTOR TO
VERIFY LOCATION OF
GAS LINE PRIOR TO
CONSTRUCTION
POC
POC
MATCH EXISTING
PVAEMENT
CONTRACTOR TO CONFIRM WATER
VALVE IS IN GOOD WORKING
ORDER. VALVE TO BE REMOVED
AND REPLACED IF IN POOR
CONDITION.
14.00'
11.55'23.00'
10.00'
6.00'
MATCH EXISTING
PAVEMENT
R30.00' STANDOFF
MATCH EXISTING
PVAEMENT
4.00'
8.46'
4.00'
NDI LAB PARKING LOT
135°
JOIN EXISTING
1.34'
6.00'
4.00'
4.00'
5% 2%
5.00'
MATCH
EXISTING
MATCH
EXISTING
7%
2%
2%
1.00'
12 12
NOTE 1
NOTE 1
NOTE 1
2%3%
10.65'
6.00'
6" C900 CLASS 150 PVC
PIPE (FIRE SUPPLY)
CONSTRUCT TO DRAIN
AWAY FROM CURB AT
0.5% MIN, 2.0% MAX
CONSTRUCT TO DRAIN AWAY FROM
CURB AT 0.5% MIN, 2.0% MAX
O:\Projects\Louisville\IER\01297\200-01297-16029\CAD\SheetFiles\C-102 - SITE.dwg
SCALE:
5' 10' 20'
1" = 10'
CONSTRUCTION NOTES
2 TWO WAY CLEANOUT PER DETAIL 3 SHEET C-501
4 CONCRETE WALKWAY PER DETAILS 4 AND 5 SHEET C-501
5 SINGLE CURB PER DETAIL 1 SHEET C-501
3 WATER/FIRE SUPPRESSION TRENCH PER DETAIL 6 SHEET C-501
1 REDUCED PRESSURE BACKFLOW PREVENTOR DETAIL 2 SHEET C-502
7 PAVEMENT MARKING WITH 6" STRIPE, WHITE, SPACED 3.75' AT 45
DEGREES, PER MUTCD.
8 UTILITY PATCH PER DETAIL 6 SHEET C-501
9 THRUST BLOCK PER DETAIL 1 SHEET C-502
10 HOT TAP PER DETAIL 5 SHEET C-502
WHITE NO PARKING MARKING
CONCRETE WALKWAY PER DETAIL 5 SHEET C-503
LEGEND
6 FIRE HYDRANT PER DETAIL 4 SHEET C-503
C-102
12 PIPE GATE PER DETAIL 1 SHEET C-504
13 DRIVEWAY ENTRANCE PER DETAIL 2 SHEET C-503
14 WALKWAY ENTRANCE PER DETAIL 1 SHEET C-503
15 PARKING PER DETAIL 3 SHEET C-503
AC PAVEMENT PER DETAIL 6 SHEET C-503
DECORATIVE ROCK COVER
16 DECORATIVE ROCK COVER
17 VALVE BOX AND COLLAR INSTALLATION PER DETAIL 3 SHEET C-502
18 CURB AND GUTTER PER DETAIL 1 SHEET C-501
NOTES:
1. MAINTAIN DRAINAGE AWAY FROM CURB TO
PREVENT PONDING. MINIMUM SLOPE IS 1.5%
MAXIMUM SLOPE IS 5%.
O:\Projects\Louisville\IER\01297\200-01297-16029\CAD\SheetFiles\C-501 - Detail 1.dwg
UTILITY PATCH2
NTS
CONCRETE CURB1
NTS
TWO WAY CLEANOUT3
NTS
CONCRETE WALKWAY4
NTS
W A
TE
R
" M
IN
. C O
V E
R
FI
R E
W A
TE
R
" M
IN
C O
V E
R
4" M
IN
6" CLEAR
BOTH SIDES OF PIPE
PIPE O.D.
" M
IN
INSTALL LOCATION WIRE AT TOP OF PIPE FOR
ALL PVC LINES
(PER SPECIFICATIONS)
PIPE PER PLAN
BACKFILL
(PER SPECIFICATIONS)
SAW CUT EXISTING PCC
FINISH SURFACE
INSTALL UTILITY
MARKING TAPE
SPRINGLINE
D /2
#5 GRADE 40 CORROSION
RESISTANT TIEBAR OR DEFORMED.
BAR 18" LONG AT 24" O.C.
12" MIN PCC
12" 12"
BEDDING MATERIAL
PER SPECIFICATIONS
WATER/FIRE SUPPRESSION TRENCH6
NTS
UNDER LANDSCAPE UNDER PCC PAVEMENT
C-501
ALKWAYCONCRETE WA CONCRETE WALKWAY SECTION5
NTS
CONCRETE SIDEWALK PER
DETAIL 4 THIS SHEET
O:\Projects\Louisville\IER\01297\200-01297-16029\CAD\SheetFiles\C-502 - Detail 2.dwg
VALVE BOX INSTALLATION3
NTS
REDUCED PRESSURE BACKFLOW PREVENTOR2
NTS
THRUST BLOCKS1
NTS
TYPE A
HOT TAPPING PIPES
VARYING IN DIAMETER
EXISTING 6" WATER MAIN
HOT TAPPING SLEEVE
CONCRETE THRUST
BLOCK PER DETAIL 2,
THIS SHEET
GRANULAR BEDDING
EXISTING 6" WATER MAIN
PROPOSED WATER
LINE
TYPE B
CONNECTING PIPES WITH
THE SAME DIAMETER
EXISTING 6" WATER MAIN
TEE
PROPOSED WATER
LINE
TRANSITION COUPLING
EXISTING 6" WATER MAIN
CONCRETE THRUST
BLOCK PER DETAIL 2,
THIS SHEET
GRANULAR BEDDING
WATER LINE
CONNECTION TO EXISTING MAIN5
NTS C-502
E BACKFLOW PREVENTORREDUCED PRESSUR
INSTALL
INSULATED
VALVE JACK
E BOX INSTALLATIONVALVE3
NTS
E X
IS
TI
N G
A C
P A
V E
M E
N T
A C
P A
V E
M E
N T
P E
R D
E
TA
IL
S
H E
E T
C -5
ASPHALT CONCRETE
AGGREGATE BASE
SAWCUT
NEW AC PAVEMENT TO
EXISTING AC PAVEMENT3
NTS
SAW CUT 2 FEET
MIN. BACK FROM
PAVEMENT JOIN
TACK COAT
EXISTING
AGGREGATE BASE
NEW PAVEMENT
SECTION
12" MINIMUM
RECOMPACTED
SUBGRADE
RECOMPACT EXISTING
AGGREGATE BASE IN
KIND
EXISTING ASPHALT
EXISTING
SUBGRADE
SUBGRADE
METER TO BE
PLACED INSIDE OF
BUILDING PER
PLUMBING PLANS
O:\Projects\Louisville\IER\01297\200-01297-16029\CAD\SheetFiles\C-503 - Detail 3.dwg
DRIVEWAY ENTRANCE2
NTS
WALKWAY ENTRANCE1
NTS
FIRE HYDRANT4
CONRETE PAVEMENT/DRIVEWAY5
C-503
STANDARD PARKING DETAIL3
NTS
9. USE CLOW VALVE COMPANY MODEL 2545
10. FIRE HYDRANTS NOT IN SERVICE SHALL BE TAGGED
BY THE CONTRACTOR WITH "OUT OF SERVICE" RINGS OR
PLACE A BLACK BAG OVER THE HYDRANT UNTIL
ACCEPTED BY THE GOVERNMENT.
11. HYDRANTS SHOULD BE FLOW TESTED AND BONNETS
PAINTED PER NFPA 25. THE BARREL SHOULD ALSO BE
PAINTED.
BARREL - BROWN (FS COLOR 30045)
1500 GPM AND GREATER - BLUE (FS COLOR 15200)
1000 GPM TO 1499 GPM- GREEN (FS COLOR 14090)
500 GPM TO 999 GPM - ORANGE (FS COLOR 12246)
BELOW 500 GPM - RED (FS COLOR 11086)
12. INSTALL CONCRETE VALVE COLLAR PER DETAIL 3
SHEET C-502
6"
CLASS II AGGREGATE
BASE (95% COMPACTION) 6"
NOTE:
1. PROVIDE EXPANSION JOINTS AT INTERFACE WITH BUILDINGS, SEWER
AND WATER STRUCTURES, DRAINAGE INLETS, CURB OR GUTTER AND
WITH EXISTING PAVEMENT.
OVEREXCAVATION
(95% COMPACTTION) 6"
3" CLEAR
ASPHALT PAVEMENT6
NTS
1.
5"
CLASS II AGGREGATE
BASE (95% COMPACTION)
6"
OVEREXCAVATION
(95% COMPACTTION) 6"
NOTE:
1. PAVEMENT SECTION IS BASED ON RECORD DRAWINGS. ACTUAL
STRUCTURAL SECTION TO MATCH EXISTING STRUCTURAL SECTION.FIRE HYDRANT NOTES CONTINUED:
C900 CLASS 150 PVC
" M
A X
6"
NOTE 1: REFER TO DETAIL 5 THIS SHEET FOR ACTUAL STRUCTURAL SECTION.
PRIME COAT
PORTLAND CEMENT
CONCRETE
AC PAVEMENT
3" C
LE
A
R
O:\Projects\Louisville\IER\01297\200-01297-16029\CAD\SheetFiles\C-504 - Detail 4.dwg
C-504
PIPE GATE1
NTS REFERENCE SHEETS C-102
B
4' -0
2'-2"
3" M
IN
4' -3
11'-0"
SECTION A - GATE KEEPER SECTION
NOT TO SCALE
ENLARGEMENT B - GATE PIVOT PLAN SECTION
NOT TO SCALE
10" NOMINAL DIA. EXTRA STRONG STEEL PIPE
BOLLARD, CONCRETE FILLED.
2"x
2" FLATBAR WELDED TO CHAIN. WELD
CHAIN TO BOLLARD.
10" DIA. STEEL PIPES WELDED TOGETHER
AND TO 12" STEEL PIPE. CAP AT OPEN END.
ONE-THIRD OF 8" PIPE, 6" LONG. WELD TO
BOLLARD AT HEIGHT WHICH SUPPORTS
UPPER 8" PIPE IN A LEVEL POSITION.
NOTE: PROVIDE A 2" SPACE IN THE TOP 2" STEEL RING @ 120° FROM THE CLOSED POSITION.
WELD A CORRESPONDING 2" STEEL PLATE INSIDE THE 10" STEEL PIPE AT 120° FROM THE
CLOSED POSITION &1/4" BELOW THE TOP RING.
10" NOMINAL DIA. EXTRA
STRONG STEEL PIPE
BOLLARD, CONCRETE
FILLED.
GREASE FITTINGS (CONTRACTOR
SHALL GREASE THE TWO PIECES OF
STEEL)
10" NOMINAL DIA. EXTRA STRONG STEEL PIPE
BOLLARD, CONCRETE FILLED.
REFER TO SECTION D FOR CONC.
REINFORCEMENT.
"ROAD CLOSED" SIGN PER
MUTCD R11-2 INSTALLATION
GUIDELINES
10" NOMINAL DIA. EXTRA
STRONG STEEL PIPE BOLLARD,
CONCRETE FILLED.
REFER TO SECTION D FOR
CONC. REINFORCEMENT.
8" DIA. STEEL PIPES WELDED
TOGETHER AND TO 10" STEEL
PIPE. CAP AT OPEN END.
D
SECTION D - CIRCULAR CONCRETE
3" CLEAR,
TYP.
#4 TIES @ 12" O.C.
12"
LAP
EDGE OF FOOTING
10" POST
3 (1/8")
REINFORCEMENT
NOT TO SCALE
3/4" STL. PLATE CAP
WELD TO STL. PIPE.
ZERK FITTING
SECTION C - GATE PIVOT SECTION
NOT TO SCALE
8" DIA. STEEL PIPES WELDED TOGETHER
AND TO 12" STEEL PIPE. CAP AT OPEN
END.
10" NOMINAL DIA. EXTRA
STRONG STEEL PIPE
BOLLARD, CONCRETE
FILLED.
12" NOMINAL DIA. EXTRA
STRONG STEEL PIPE
SLEEVE.
3/4" STL. PLATE FLANGE
WELD TO STL. PIPE.
ALIGN HOLES IN TOP AND BOTTOM
FLANGES
90°
2"
6 PLACES
EQ. SPACES
2"
6 PLACES
EQ. SPACESC
10" NOMINAL DIA.
EXTRA STRONG STEEL
PIPE BOLLARD,
CONCRETE FILLED.
3/4" STL. PLATE
FLANGE WELD TO
STL. PIPE.
3/4" STL. PLATE
FLANGE WELD TO
STEEL BOLLARD.
3/8" DIA. HOLES (TYP.) FOR
MOUNTING "ROAD CLOSED"
SIGN
3"
MIN.
PAD LOCK
STD. AUTOMOTIVE 13" WHEEL HUB. BOLT TO
BOLLARD. ALIGN CENTERLINES OF HUB, 10"
PIPES TO ENSURE FREE ROTATION.
3/4" STL. PLATE CAP
WELD TO STL. PIPE.
10" NOMINAL DIA.
EXTRA STRONG
STEEL PIPE SLEEVE.
51 (2")
TYP. EA.
JOINT
51 (2")
TYP. EA.
JOINT
NOTE:
PROVIDE ADDITIONAL GATE KEEPER POST WITH ONE-THIRD
PIPE CRADLE, CHAIN AND PIN TO SUPPORT GATE IN OPEN
POSITION PER SECTION A.
11'-0"
CLEVIS AND PIN LOCK
OBJECT MARKER PER MUTCD OM-3L WITH RED AND
WHITE STRIPING
OBJECT MARKER PER MUTCD OM-3R WITH
RED AND WHITE STRIPING
3/8" DIA. HOLES (TYP.) FOR
MOUNTING OBJECT MARKER
GATE PIVOT
NOT TO SCALE
GATE KEEPER FOUNDATION PER GATE
PIVOT DETAIL AND SECTION D THIS SHEET
51 (2")
TYP. EA.
JOINT
51 (2")
TYP. EA.
JOINT
3/8" DIA. HOLES (TYP.) FOR
MOUNTING "ROAD CLOSED"
SIGN
1. ALL CONCEALED LOW PRESSURE SUPPLY DUCTWORK SHALL BE EXTERNALLY WRAPPED WITH
DUCTWRAP. SEE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS.
2. OUTSIDE AIR DUCTWORK SHALL BE EXTERNALLY WRAPPED WITH DUCTWRAP.
3. CONCEALED EXHAUST AIR DUCTWORK SHALL NOT REQUIRE INSULATION, EXCEPT DUCTWORK INDICATED
ON THE DRAWINGS SHALL BE LINED WITH 1"-1.5 LB DENSITY DUCTLINER.
4. EXISTING DUCTWORK TO REMAIN SHALL BE CLEANED AND SHALL HAVE A DUCT AIR LEAKAGE TEST PERFORMED PER THE T&B SPECIFICATION. EXISTING DUCTWORK SHALL BE SEALED AS REQUIRED.
5. ALL DUCTWORK IS SHOWN AS FREE AREA INSIDE DIMENSIONS.
6. USE 45 DEG. TAPS FOR ROUND TO ROUND TAKE OFF'S. PROVIDE VOLUME DAMPER AT EACH TAKE OFF.
7. DO NOT CONSTRUCT OR INSTALL TAPS OUT OF REDUCERS, TEES AND OR ELBOWS.
8. ALLOW FOR FIELD MEASURED OFFSETS OR TRANSITIONS, ELBOWS ETC.
9. SUPPORT ALL FLEXIBLE DUCTWORK AS SHOWN IN SMACNA FIGURE 3-10, 2005.
10. DO NOT USE FLEX DUCT IN EXPOSED AREAS. MAXIMUM FLEX DUCT LENGTH AT ANY CONNECTION SHALL
NOT EXCEED TWO FEET. FLEX DUCT SHALL NOT BE USED FOR ELBOWS.
11. GRILLES, REGISTERS AND DIFFUSERS CONNECTED BY FLEXIBLE DUCT SHALL BE SUPPORTED
INDEPENDENTLY OF THE FLEXIBLE DUCT.
12. ELBOWS SHALL BE 90 DEG. ELLS WITH DOUBLE THICKNESS TURNING VANES OR WHERE SPACE PERMITS RADIUS FITTING WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES THE DUCT WIDTH CENTERLINE. NO
OTHERS WILL BE ALLOWED.
13. COORDINATE FINAL LOCATION OF ALL REGISTERS, GRILLES, DIFFUSERS ETC. WITH ARCHITECTURAL
DRAWINGS AND LIGHTING PLANS.
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES, AND CONTROLS, COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED WITH. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT OCCURING ANY ADDITIONAL COST TO THE OWNER.
CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING
SHOP DRAWINGS.
2. ALL DUCTWORK SHALL BE MOUNTED WITHIN 12-24 INCHES OF CEILINGS EXCEPT TO AVOID INTERFERANCES
WITH OTHER CONSTRUCTION.
3. COORDINATE EQUIPMENT AND PIPING WITH ALL OTHER DISCIPLINES AND TRADES. MAKE ALL OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER.
4. COORDINATE THE EXACT LOCATION AND SIZE OF ALL ROOF, WALL, AND SLAB PENETRATIONS WITH THE
ARCHITECTURAL DRAWINGS.
5. ALL NEW PIPING SHALL BE LOCATED AS HIGH AS POSSIBLE.
6. MOUNT THERMOSTATS WHERE INDICATED ON PLANS, 4'-0" A.F.F. UNLESS NOTED OTHERWISE.
7. ELECTRICAL CONTRACTOR TO VERIFY CONTROL VOLTAGES WITH EQUIPMENT AND PROVIDE ACCORDINGLY.
8. CELLULAR ELASTIC INSULATION SHALL NOT BE USED. CONTRACTOR SHALL USE MINERAL FIBER AND
FOAMGLASS INSULATION.
9. TEST AND BALANCE SHALL BE CONDUCTED FOR ALL NEW AND EXISTING SYSTEMS.
10. ALL NEW PIPING SHALL BE A MINIMUM OF 3/4" DIAMETER. NO 1/2" DIAMETER PIPING SHALL BE USED.
ABS ABSOLUTE
AD ACCESS DOOR
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
BHP BRAKE HORSEPOWER
CONC CONCRETE
CONN CONNECTION
CONT CONTINUATION
D DRAIN
DIA DIAMETER
DN DOWN
DWG DRAWING
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EUH ELECTRIC UNIT HEATER
F FAHRENHEIT
FLEX FLEXIBLE
FPM FEET PER MINUTE
GAL GALLONS
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
L LOUVER
LAT LEAVING AIR TEMPERATURE
MAX MAXIMUM
MIN MINIMUM
N.T.S. NOT TO SCALE
NG NATURAL GAS
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
SP STATIC PRESSURE
SPEC SPECIFICATION
STANDARDSTD
TEMP TEMPERATURE
T STAT THERMOSTAT
TYP TYPICAL
V VOLT
W WATT
WG WATER GAUGE
SYMBOL DESCRIPTION
EXH
FFE FINISH FLOOR ELEVATION
CP-1 CONTROL PANEL WITH DESIGNATION
AFG ABOVE FINISH GRADE
EXHAUST
FD FIRE DAMPER
3. ALL SYMBOLS WHICH APPEAR WITHIN THE LEGEND MAY NOT APPLY TO THIS PROJECT.
2. THIS LEGEND IS FOR REFERENCE ONLY.
ELBOW, TURNED UP
BUTTERFLY VALVE
ANCHOR, INTERMEDIATE
ELBOW, TURNED DOWN
NOTES:
BALL VALVE
GATE VALVE
TEE
DUCT SIZE, FIRST FIGURE IS DIMENSION SHOWN ON PLAN20x12
LOUVER AND SCREEN
GRILLE OR REGISTER, SIDEWALL
SUPPLY GRILLE OR REGISTER, CEILING
SUPPLY AIR FLOW
CONNECTION, TOP
CONNECTION, BOTTOM
CAP
DUCT TRANSITION
DUCT SECTION, POSITIVE PRESSURE
DUCT SECTION, NEGATIVE PRESSURE
FD
TURNING VANES
NEW DUCTWORK
FIRE DAMPER (1.5 HR) AND SLEEVE, PROVIDE ACCESS DOOR
1. ALL DUCT TAPS SHALL BE PER SMACNA STANDARDS LATEST EDITION.
THERMOSTAT
RETURN GRILLE OR REGISTER, CEILING
EXHAUST GRILLE OR REGISTER, CEILING
MECHANICAL ABBREVIATIONSMECHANICAL LEGEND
MOTORIZED DAMPER
CO SENSOR2
MASTER EMERGENCY SHUTDOWN SWITCH
SB SECURITY BARS
AP ACCESS PANEL
SAH SPLIT SYSTEM AIR HANDLING UNIT
ET EXPANSION TANK
APD AIR PRESSURE DROP
WPD WATER PRESSURE DROP
Ø DIAMETER
VAV VARIABLE AIR VOLUME
TYPE IN SCHEDULE
REFERENCE AIR DEVICE
FIRST THREE LETTERS
(CDA)
AIR QUANTITY DELIVERED
BY DEVICE IN CFM
LP LOUVERED PENTHOUSE
GH GRAVITY HOOD
OA OUTDOOR AIR
EA EXHAUST AIR
UH UNIT HEATER
CU CONDENSING UNIT
VOLUME DAMPER
AAV AUTOMATIC AIR VENT
HW HOT WATER
CW CHILLED WATER
FLEXIBLE DUCTWORK
TRANSFER AIRTA
RA RETURN AIR
SA SUPPLY AIR
EMCS ENERGY MANAGEMENT AND CONTROL SYSTEM
CDA 250
RL REFRIGERANT LIQUID LINE
RS REFRIGERANT SUCTION LINE
CAP. CAPACITY
3HR
FIRE DAMPER (3 HR) AND SLEEVE, PROVIDE ACCESS DOOR
MECHANICAL GENERAL NOTES:
DUCTWORK NOTES:
UC UNDERCUT
CONNECT TO EXISTING
PRESSURE GAUGE
THERMOMETER
VFS VARIABLE FREQUENCY STARTER
BDD BACKDRAFT DAMPER
LIMIT OF DEMOLITION
DEMOLISH EXISTING
NO LONGER EXISTING
\\tts024fs1\Projects\IER\01297\200-01297-16029\CAD\SheetFiles\M-001 - MECHANICAL LEGEND AND NOTES.dwg
M-001
File details come from the government source that posted it.