Atch 05- Nellis-Creech IFS appendix Lighting Req.pdf

PDF 31 KB Posted

Attached to
Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation Federal contract opportunity
Solicitation number
FA486119RA001
Issued by
Department of the Air Force Air Combat Command

About this file

This document outlines lighting requirements for federal construction projects at Nellis and Creech Air Force Bases. Key details include specifications for interior and exterior lighting fixtures which must be solid-state LED luminaires rated for outdoor use between 0-120 degrees Fahrenheit. Interior fixtures within 20 feet of the ground shall be flat panel designs with full remote dimming controls, while high bay fixtures over 20 feet shall have motion sensors and adjustable light output. Exterior street, parking, security and airfield lighting is also specified, and must incorporate controls like photocells and motion sensors to reduce energy waste. The lighting requirements appear to relate to the Nellis/Creech AFB Multiple Award Construction Contract solicitation issued by the Department of the Air Force Air Combat Command to upgrade and maintain facilities at the bases in accordance with Installation Facilities Standards.

Not Listed

View the file

Other files for this federal contract opportunity

Other files attached to Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation, newest first.
File Type Posted
Atch_00-_MACC_Attachment_Index.pdf PDF
Solicitation_Conformed.pdf PDF
Solicitation_Amendment_FA486119RA0010008_SF_30.pdf PDF
Atch_00-_MACC_Attachment_Index.pdf PDF
Atch_48-_App_D_RKMF_17-0097_Electrical_REVISED_8-9-19.pdf PDF
Atch_00-_MACC_Attachment_Index.pdf PDF
Atch_52_Bid_Schedule,_RKMF_17-0097.pdf PDF
Atch_55-_19RA001_Preproposal_Site_Visit_(Slides_and_Sign-In_Sheet).pdf PDF
Atch_53-_RKMF_17-0097_VCC_SOW_Dated_11_July_19.pdf PDF
Atch 25- NTTR Visit Request.pdf PDF
19RA001_MACC_Attch_25-34.zip ZIP file
19RA001_MACC_Attch_12-24.zip ZIP file
Atch 14- UM3-14 1-Phase CJE Conduit Placement Standards.pdf PDF
Atch 00- MACC Attachment Index.pdf PDF
Atch 23- UM48-2 Multi-Grounds.pdf PDF
Atch 28- AF Form 103, Base Civil Engineering Work Clearance Request.pdf PDF
Atch 38- WD NV190012 20180012.pdf PDF
Atch 37- WD NV190024 20180061.pdf PDF
Atch 36- WD NV190038 20180075.pdf PDF
Atch 47- App C RKMF 17-0097 Elevations.pdf PDF
Atch 41- Past Peformance Information Sheet.pdf PDF
Atch 33- AIS Form 2015.pdf PDF
Atch 11- USAF Integrated Cultural Resources Mgmt Plan.pdf PDF
Atch 04- Nellis-Creech IFS appendix Electrical Req.pdf PDF
Atch 01- MACC SOW.pdf PDF
Atch 35- WD NV190001 20180001.pdf PDF
Atch 49- App E RKMF 17-0097 Site Contours.JPG JPG image
Atch 30- Progress Schedule Template.xls XLS spreadsheet
Atch 54- VCC Site Plan 2018-10-02.jpg JPG image
Atch 29- Cost Estimate Template.xlsx XLSX spreadsheet
Atch 24- VEA CONNECTION CHARGE AGREEMENT.docx DOCX document
Atch 13- UR2 S Primary and Secondary Trenching Requirements.pdf PDF
Atch 53- RKMF 17-0097 VCC SOW 20181203.pdf PDF
Atch 34- BUILDER inventory sheet.xls XLS spreadsheet
Atch 12- UM1-6C 3-Phase Pad and Vault.PDF PDF
Atch 17- Bulletin 1728F-806 UG Main VEA standard.pdf PDF
Atch 15- UM33 200 Amp 3-Phase CJE 4 inch Conduit Placement Standards.pdf PDF
Atch 32- Schedule of Vaules Template.xlsx XLSX spreadsheet
Atch 09- ACC Sole Source EMCS Letter.pdf PDF
Atch 45- App A RKMF 17-0097 Site Plan.pdf PDF
19RA001_MACC_Attch_12-24.zip ZIP file
Atch 02- Nellis-Creech IFS appendix Fire Protection Req.pdf PDF
Atch 31- Progess Report Template.pdf PDF
Atch 08- Environmental Permit Guidance.pdf PDF
Atch 42- Subcontractor Teaming Partner Consent Form.pdf PDF
Atch 26- Nuclear Gauge Form 1.xlsx XLSX spreadsheet
Atch 03- Nellis-Creech IFS appendix Comm Req.pdf PDF
Atch 52- Bid Schedule RKMF 17-0097.pdf PDF
Atch 10- NAFB Plan 32-7086 Hazardous Materials Management Plan.pdf PDF
Atch 19- UG 17-2 3-Phase Delta-Wye Pad Mounted Transformer Loop Feed.pdf PDF
Show all 50

Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NELLIS AND CREECH AFB

INSTALLATION FACILITIES STANDARDS (IFS)

LIGHTING REQUIREMENTS

22 JAN 2019

This document is an appendix to Nellis & Creech Air Force Bases IFS which is located here:

https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs

1. Codes and Standards: All design and construction shall be in compliance with the most recent versions of the following:

Nellis & Creech Air Force Bases Installation Facilities Standards (IFS) Unified Facilities Criteria (UFC) 3-530-01 Design: Interior, Exterior Lighting and

Controls Unified Facilities Guide Specification (UFGS) 26 51 00.00 40 for interior lighting UFGS 26 56 00 for exterior lighting UFGS 26 56 19.00 40 for roadway lighting UFGS 26 56 23.00 40 for area lighting UFGS 26 56 36 00 40 for flood lighting UFGS 26 56 20.00 10 for airfield and heliport lighting AFI 31-101 Integrated Defense for security applications

2. All interior and exterior lighting fixtures shall comply with the following:

2.1 Fixtures shall be solid-state LED luminaires designed specifically for LED technologies (typically flat to compliment the directional characteristics of LEDs) with integrated controls and remote lighting level adjustment/dimming capabilities.

2.2 Fixtures shall have a color temperature in KELVIN of between 4000K and 4500K.

Fixtures shall have appropriate illumination volume (foot candle/lumen) output to meet work surface UFC guidelines per fixture/space photometric analysis (using typical manufacturer software).

2.3 LED Luminaires shall have a minimum warranty of 10 years.

2.4 LED Drivers shall have a minimum warranty of 5 years.

2.5 Ballasts and lamps shall have a minimum rated life of 50,000 hours.

2.6 Fixtures shall be rated to operate at ambient temperatures between 0 degrees F and

120 degrees F or higher. This requirement does not apply to Interior Recessed, Downlight, and Wall Wash Fixtures.

2.7 T-8, T-5, Induction, and High Intensity Discharge fixtures are prohibited.

https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs

2.8 All interior (and all practicable exterior) facility lighting fixtures shall be controlled by motion detectors. Any exceptions shall be requested by Contractor for approval by the Contracting Officer. No exceptions will be made for restroom and conference room fixtures. Wall switches shall be installed to turn sensors/lights on and off as needed (i.e. lights off in a conference room in order to view wall screens). Sensors shall be placed in a location not affected by movement outside of open doorways.

Daylighting wall switches shall be installed to allow dimming/turn-off of fixtures located nearest to windows, hangar/truck doors or similar daylighting sources. This may also be accomplished with photocell controls for automatic dimming/turn-off.

3. Interior Fixtures located 20 feet or less above finished floor:

3.1 Luminaires shall be solid-state LED Luminaires (preferably flat plate as opposed to

Silver Bowl, recessed, or light scattering fixtures) with full remote dimming controls.

3.2 LED linear replacements for existing fluorescent fixtures may be used provided that the following conditions are met:

3.2.1 The existing ballast shall be replaced with LED Driver or electronic ballast specifically for LED applications.

3.2.2 Fixtures shall have a color temperature as indicated in 2.2. Other color temperatures may be considered in housing applications, hospitality applications, and in maintenance facilities. See UFC 3-530-01 for additional information.

3.3 Provide wire guards for all open LED linear replacements.

4. Interior High Bay Fixtures located higher than 20 feet above work surface:

Each fixture shall have on/off motion sensors (with partial shutoff delay before full off), and be remotely adjustable (infrared or Bluetooth) light output/on-off control.

5. Exterior Street and Parking Lot Fixtures:

5.1 All street and parking lot light fixtures shall include appropriate controls for dusk till dawn photocells (one photocell per fixture). Parking area fixtures shall have automatic dimming for late-night to dawn operation to increase energy savings when parking lots are typically vacant.

5.2 Glass fixture lens are preferred.

6. Exterior Wall Pack and Walkway Fixtures:

6.1 All wall pack lighting fixtures shall include dusk till dawn photocells; wall-packs away from ingress/egress points and not illuminating Air Force assets (mechanical and electrical equipment, trash enclosures, etc.) shall also have motion sensor controls to eliminate energy waste and night sky pollution.

6.2 All walkway lighting fixtures shall include dusk till dawn photocells.

6.3 Glass fixture lens are preferred.

6.4 Light bollards shall be full cutoff type and vandal resistant. Bollards shall not have exposed vertical plastic/acrylic lens. Electrical service shall be 208v maximum with 120v to ground.

7. Exterior Area, Flood, Canopy, and Security Lighting Fixtures:

7.1 As appropriate, Contractor shall obtain lighting design approval from base Security

Forces and/or base Antiterrorism Force Protection (ATFP) office.

7.2 Fixtures shall be compatible with CCTV, and night vision goggles.

7.3 Fixtures shall meet appropriate illumination requirements for security and ATFP.

7.4 Certain large area security lighting applications may employ individual fixture motion sensor on-controls to identify intrusion points with lighting where otherwise fixtures remain off, saving energy.

7.5 Automatic dimming/on-off and motion sensors shall be used to allow energy savings during low use times while maintaining some illumination for adequate security when dimmed.

8. Exterior Airfield / Apron Lighting Fixtures:

8.1 As appropriate, Contractor shall obtain lighting design approval from Airfield

Operations office, base Security Forces, and/or base ATFP office.

8.1.1 Fixtures shall be compatible with CCTV, and night vision goggles.

8.1.2 Fixtures shall meet appropriate illumination requirements for aircraft and equipment operations and ATFP/security.

8.2 Glass fixture lens are preferred.

8.3 Automatic Bi-level dimming with occupancy sensors shall be explored to allow energy savings when lights are used infrequently, or when instant-on LED capabilities enhance security achievement. Certain locations (i.e. personnel/vehicle doors or gates) shall have motion sensors that only dim lighting to maintain access point illumination.

9. Reference separate Nellis-Creech IFS appendix document for non-lighting Electrical

Requirements.

END OF LIGHTING REQUIREMENTS