Atch 03- Nellis-Creech IFS appendix Comm Req.pdf
PDF 557 KB Posted
- Attached to
- Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation Federal contract opportunity
- Solicitation number
- FA486119RA001
About this file
This document provides specifications for telecommunications cabling systems at Nellis and Creech Air Force Bases. It details requirements for various components of the systems including backbone and horizontal cabling, telecommunications spaces, outlets, connectors, and more. Installation must adhere to standards like the TIA/EIA-568 series. Qualified contractors must be BICSI-certified and use registered cabling installers. The appendices provide additional requirements for interior distribution systems, underground electrical distribution, outside plant, and geospatial information collection. Drawings and as-built documentation must be submitted and approved. Testing is required to certify performance and functionality.
Not Listed
View the file
Other files for this federal contract opportunity
Show all 50
Nellis/Creech AFB Multiple Award Construction Contract (MACC) Solicitation has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NC 2710, 01/17
Nellis and Creech AFB Addendum NC 2710 NC 2710 (Jan 2017) Superseding NC 27 10 (Jun 2012)
NELLIS AND CREECH AFB ADDENDUM
BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 27-COMMUNICATIONS
SECTION 27 10 00
01 /17
TABLE OF CONTENTS
NOTE: This guide specification covers Nellis and Creech AFB requirements for building telecommunications cabling systems and shall be used in conjunction with the specifications outlined in Unified Facilities Guide Specifications (UFGS) Section 27 10 00 and appendixes listed below. This document does not replace, but further details the specifications in UFGS Section 27 10 00 and appendixes. Specifications and requirements in UFGS Section 27 10 00 must be adhered to while meeting the requirements and specifications within this document.
UFGS Sections are not covered in its entirety in this addendum, only specific paragraphs are addressed. All paragraphs directly correspond with UFGS Section 27 10 00, Building Telecommunications Cabling System, dated 08/11 and listed appendixes. Additionally, requirements and specifications not outlined in this document but required by UFC-3-580-01 must be met. The base communications squadron will make the final determination on any and all telecommunications cabling systems and related components.
SECTION 27 10 00 - BUILDING TELECOMMUNICATIONS CABLING SYSTEM
APPENDIX
A.1 SECTION 26 20 00 - INTERIOR DISTRIBUTION SYSTEM
A.2 SECTION 33 71 02.00 10 - ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
A.3 SECTION 33 82 00 - TELECOMMUNICATIONS, OUTSIDE PLANT
A.4 ATTACHMENT 1, SECTION 33 82 00, GEOSPATIAL INFORMATION
A.5 FIGURES - COMM ROOM & FRONT PANEL EXAMPLES
-- End of Section Table of Contents -
TABLE OF CONTENTS
BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 27-COMMUNICATIONS
SECTION 27 10 00
01/17
PART 1 GENERAL
1.1 REFERENCES
1.3 DEFINITIONS
1.5 SUBMITTALS
1.6.1.1 Telecommunications Drawings
1.6.2 Telecommunications Qualifications
1.6.2.2 Key Personnel
1.6.3 Test Plan
1.6.4 Testing
1.6.4.1 Telecommunications Cabling Testing
1.6.4.2 Inspection
1.6.4.3 Verification Tests
1.6.4.4 Performance/Certification Tests
1.6.4.4.1 Perform Category 6 link tests.
1.6.4.4.2 All Performance/Certification tests
1.6.4.5 Determining a FO loss budget
1.6.4.6 Final Verification Tests
1.6.4.6.1 Voice Tests.
1.6.4.6.2 Data Tests.
1.8 ENVIRONMENTAL REQUIREMENTS
PART 2 PRODUCTS
2.1 COMPONENTS
2.2 TELECOMMUNICATIONS PATHWAY
2.3 TELECOMMUNICATIONS CABLING
2.3.1.1 Backbone Copper
2.3.1.2 Backbone Optical Fiber
2.3.2.1 Horizontal Copper
2.3.2.2 Horizontal Optical Fiber
2.4 TELECOMMUNICATIONS SPACES
2.4.1 Backboards
2.4.2 Equipment Support Frame
2.4.2.1 Bracket
2.4.2.2 Racks
2.4.2.3 Cabinets Free standing
2.4.2.4 Cabinets Wall Mounted
2.4.3 Connector Blocks
2.4.4 Cable Guides
2.4.5 Patch Panels
2.4.5.1 Modular to 110 Block Patch Panel
2.4.5.2 Fiber Optic Patch Panel
2.4.6 Optical Fiber Distribution Panel
2.5 TELECOMMUNICATIONS OUTLET/CONNECTOR ASSEMBLIES
2.5.1 Outlet/Connector Copper
2.5.2 Optical Fiber Adapters (Couplers)
2.5.3 Optical Fiber Connectors
2.5.4 Cover Plates
2.13 ALARM CIRCUITS
2.14 ACCESS CONTROLS&IDS
2.15 CRITICAL COMM NODES
2.16 HEAT RESISTANT BULKHEADS
PART 3 EXECUTION
3.1.1.1 Open Cable
3.1.1.2 Backbone Cable
3.1.6.1 Terminations
3.1.7.2 Patch Panels
3.1.7.3 Equipment Support Frames
3.3.1 Painting Backboards
-- End of Section Table of Contents --
NELLIS AND CREECH
ADDENDUM SECTION 27 10 00
BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
NOTE: This guide specification covers Nellis and Creech AFB requirements for building telecommunications cabling systems and shall be used in conjunction with the specifications outlined in Unified Facilities Guide Specifications (UFGS) Section 27 10 00 and appendixes listed below. This document does not replace, but further details the specifications in UFGS Section 27 10 00 and appendixes. Specifications and requirements in UFGS Section 27 10 00 must be adhered to while meeting the requirements and specifications within this document. UFGS Sections are not covered in its entirety in this addendum, only specific paragraphs are addressed. All paragraphs directly correspond with UFGS Section 27 10 00, Building Telecommunications Cabling System, dated 08/11 and listed appendixes. Additionally, requirements and specifications not outlined in this document but required by UFC-3-580-01 must be met. The base communications squadron will make the final determination on any and all telecommunications cabling systems and related components.
1.1 REFERENCES
ENGINEERING TECHNICAL LETTER
ETL 01-18 Fire Protection for Electronic Equipment
Installations UNIFIED FACILITIES CRITERIA
UFC-3-580-01 Telecommunications Building Cabling Systems Planning and Design
AIR FORCE INSTRUCTIONS
AFI 32-1065 Grounding Systems
1.3 DEFINITIONS
a. ITB = Information Transfer Building - All network backbone facilities that are designated as OSP cable concentration points requiring direct redundant OSP connections to at least two other ITB facilities.
b. CEB = Critical Edge Building - All facilities that support command and control missions that have been identified as requiring redundant OSP connections to at least two ITB facilities (either via diverse fiber cable paths to two different ITBs or via redundant uplink connections through a single fiber cable or path from the CEB to two different ITBs [referred to as logical diversity by BITI]).
c. EB = Edge Building - All remaining facilities that have OSP connectivity to at least one ITB (preferably by a direct fiber connection, however indirect connections through SONET, DWDM, daisy chained Ethernet switches, DSL, point to point wireless, or other means is allowed when direct fiber connectivity is either not possible or not economically feasible).
d. CEL = Communications Equipment Locations - For Nellis and Creech the CEL (also referred to as a Communications Closet or Intermediate Distribution Frame) is a location within a building where network equipment (switches, routers) is located. Within the CEL the network equipment is connected to the horizontal station cabling to attach end-users and patched to upstream network equipment to connect to the network backbone. CELs shall have sufficient heating, ventilation, air conditioning, cable pathway access, and space to allow for maintenance and operation of all equipment contained within it IAW equipment manufacturers installation recommendations. The CEL shall be a physically controlled area, with lockable room entrances or with lockable cabinets. Communication Equipment Locations must be kept clear and may not be used as storage facilities. CEL may be a combination of the TR (telecommunications room), EF (entrance facility), & ER (entrance room).
1.5 SUBMITTALS
Government approval is required for submittals with a ‘GA’ designation; submittals having a ‘FIO’ designation are for information only. The following shall be submitted in accordance with Section entitled, SUBMITTAL PROCEDURES:
Pre-construction Drawings - Communications Distribution System (FIO) Detail drawings including a complete list of equipment and material. Detail drawings shall contain complete wiring and schematic diagrams and other details required to show that the system has been coordinated and will function properly as a system. Drawings shall include vertical riser diagrams, equipment rack details, and elevation drawings of telecommunications closet walls, outlet faceplate details for all outlet configurations, sizes and types of all cables, conduits, and cable trays. Drawings shall show proposed layout and anchorage of equipment and appurtenances, and equipment relationship to other parts of the work including clearance for maintenance and operation.
Post-construction Drawings (As-Built Drawings) – Communications Distribution Systems (FIO) As-built drawings for the installed wiring systems infrastructure shall be submitted per TIA/EIA-606. The drawings shall show the location of all cable terminations, the location and routing of all cable terminations, and the location and routing of all backbone and horizontal cables. The identifier for each termination and cable shall appear on the drawings. The Base Communications Squadron shall be provided a copy of as-built drawings within 14 days after completion of installation on a CD or DVD in AutoCad & Adobe format (.dwg).
1.6.1.1 Telecommunications Drawings
Telecommunications drawings must be stamped and approved by a Registered Communications Distribution Designer (RCDD).
1.6.2 Telecommunications Qualifications
All work under this section shall be performed by and all equipment shall be furnished and installed by a Building Industry Consulting Services International (BICSI) certified Telecommunications Contractor. The contractor must be a BICSI Registered Cabling Installer at the Technician Level. The Electrical Contractor shall not perform the installation of communications distribution system cables, equipment, and associated hardware with the exception of furnishing and installing conduit, electrical boxes, grounding equipment and components, cable tray, and pull-wires.
1.6.2.2 Key Personnel
All installers assigned to the installation of this system or any of its components shall have a minimum 3 years of experience in the installation of the specified copper wire, fiber optic cable and components. General electrical trade staff (electricians) shall not be employed for the installation of the communications distribution system cables, equipment, and associated hardware.
Supervisors and installers assigned to the installation of this system or any of its components shall be BICSI Registered Cabling Installers, Technician Level. Submit documentation of current BICSI certification for each of the key personnel.
NOTE: Each installer may be required to make an approved dummy splice for each type to be employed in the execution of this contract in the presence of the Contracting Officer and a Quality Assurance Evaluator from the base communications squadron. Splices shall be in accordance with the cable manufacturer’s instructions. The contractor shall furnish all materials needed for dummy splices, at no cost to the government.
1.6.3 Test Plan
Provide a complete and detailed test plan for the telecommunications cabling system including a complete list of test equipment for the UTP, STP and optical fiber components and accessories 21 days prior to the proposed test date. The following tests and testing procedures shall be provided and followed:
Written test results and as-built drawings shall be provided to the Base Communications Squadron within 14 days after completion of tests on a CD or DVD; in Adobe Acrobat format (.pdf). This applies to all fiber optic cable and copper wire installations.
1.6.4 TESTING
1.6.4.1 Telecommunications Cabling Testing
Perform telecommunications cabling inspection, verification, and Performance/Certification tests in accordance with the most recent revision of the ANSI/TIA/EIA-568. Perform optical fiber field inspection tests via attenuation measurements on factory reels and provide results along with manufacturer certification for factory reel tests.
Remove failed cable reels from project site upon attenuation test failure.
1.6.4.2 Inspection
Visually inspect UTP and optical fiber jacket materials for UL or third party certification markings. Inspect cabling terminations in telecommunications rooms and at workstations to confirm color code for T568A or T568B pin assignments, and inspect cabling connections to confirm compliance with the most recent revision of the ANSI/TIA/EIA-568 standards. Visually confirm marking of outlets, cover plates, outlet/connectors, and patch panels. Patch panel wiring should conform to manufacturer’s specifications and be available upon request.
1.6.4.3 Verification Tests
UTP backbone copper cabling shall be tested for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors, and between conductors and shield, if cable has overall shield. Test operation of shorting bars in connection blocks. Test cables after termination but prior to being cross-connected.
All category FO circuits shall be tested using a test set that meets the accuracy requirements of the most recent revision of the ANSI/TIA/EIA-568 standards for cabling. Unless otherwise stated, FO testing methods should conform to TIA/EIA-526-7.
NOTE: For verification/troubleshooting purposes of length or overall loss OTDR tests using a launch cable are acceptable. For all Performance/Certification tests a Bi-directional Measurement, using both wavelengths applicable to the FO cable type, is required.
1.6.4.4 Performance/Certification Tests
All Performance tests shall meet the accuracy requirements of the most recent revision of the ANSI/TIA/EIA-568 standards for cabling.
1.6.4.4.1 Perform Category 6 link tests.
Tests shall include wire map, length, insertion loss, NEXT, PSNEXT, ELFEXT, PSELFEXT, return loss, propagation delay, and delay skew.
NOTE: Though most smart test meters (i.e. Fluke DTX-1800) will show a pass with an asterisk for NEXT with a value less than 1 dB; that value is indicative of a sharp bend or improper termination. No Cat6 testing will be accepted with a NEXT value of less than 1 dB.
1.6.4.4.2 All Performance/Certification tests
Tests will be completed via Bi-directional Measurement, using both wavelengths applicable to the FO cable type.
When testing Multimode a mandrel will be used. The most recent revision of the ANSI/TIA/EIA-526 shall be used as reference for testing methods.
1.6.4.5 Determining a FO loss budget
Unless otherwise stated for specific equipment requirements, all loss budgets shall conform to the values in the ANSI/TIA/EIA-568. Cable transmission performance values can be referenced in 568 Section 4.2 Table 1. 0.75 dB loss will be allowed for mated connector pairs (i.e. patch panel transitions/bulkheads) and 0.3 dB loss will be allowed for fusion or mechanical fiber splices.
For example: An OS1 Single-mode cable installed from bulkhead to wall jack with 361m in length will have an acceptable loss value of 1.86 dB for both wave lengths. This is determined as both the bulkhead and jack count as mated connector pair. The transmission performance is rated at 1 dB/km for both wavelengths. (.75 dB x 2) + (.361km x 1 dB) = 1.86 dB
1.6.4.6 Final Verification Tests
Perform verification tests for UTP and optical fiber systems after the complete telecommunications cabling and workstation outlet/connectors are installed. Detailed test results will be provided to 99th Communication Sq. for verification and acceptance.
1.6.4.6.1 Voice Tests.
These tests assume that dial tone service has been installed. Connect to the network interface device at the demarcation point. Go off-hook and listen for a dial tone. If a test Number is available, make and receive a local, long distance, and DSN telephone call.
1.6.4.6.2 Data Tests.
These tests assume the Information Technology Staff has a network installed and are available to assist with testing. Connect to the network interface device at the demarcation point. Log onto the network to ensure proper connection to the network.
1.8 ENVIRONMENTAL REQUIREMENTS
Equipment shall be rated for continuous operation under the ambient environmental temperature, pressure, humidity, and vibration conditions specified or normally encountered for the installed location. Reference TIA-569-C for Dew Point and HVAC requirements.
PART 2: PRODUCTS
2.1 COMPONENTS
Each major component of equipment shall have the manufacturer’s name, address, type or style, model and/or serial number, and catalog number on a plate firmly secured to the equipment. The nameplate of the distributing agent is not an acceptable replacement.
2.2 TELECOMMUNICATIONS PATHWAY
Raceway or cable tray fill rate shall not exceed 40 percent. Primary mode of transport infrastructure will be cable tray unless authorized by base Communication Squadron.
2.3 TELECOMMUNICATIONS CABLING
Optical fiber and copper patch cords shall be provided. Provide cords with varying lengths accounting for cable management. Patch cords will be the same or greater quality of the cables installed.
1. Jacket color for all unclassified (e.g. NIPRNet, Data, & Voice) fiber and copper shall be Green.
2. Jacket color for all classified Secret (e.g. SIPRNet &/or secure Voice) fiber and copper shall be Red.
3. CENTRIX jacket color shall be purple (Creech AFB Only)
4. All other networks or systems shall be approved by the government customer and system accreditation authority.
5. Fiber optic patch cables must be factory-assembled using single coupling SC-type FOC connectors except where other connector types are required to interface with existing equipment
2.3.1.1 Backbone Copper
Copper backbone cable shall be solid conductor, 24 AWG, 100 ohm, minimum 25-pair, Category 3, UTP. Only install backbone copper cable between the 110 block in the entrance facility (EF) to patch panels in the Communications Equipment Locations (CEL). Home run the backbone copper from the patch panels in the CELs to the 110 block in the EF. 110 blocks are only installed in the EF.
2.3.1.2 Backbone Optical Fiber
Install a minimum of 12 strands fiber optic cable between each CEL and entrance facility. Install Single-Mode (OS1) backbone cable. The government will specify fiber optic adapters/connectors for renovation or addition to existing facilities requiring interface with existing equipment. Hybrid Laser Optimized (OM3) Multimode fiber optic cable and cable bundles are only approved by change requests.
2.3.2.1 Horizontal Copper
Horizontal cable shall meet the requirements of TIA-568 for Category 6 horizontal cable as a minimum.
2.3.2.2 Horizontal Optical Fiber
Inside Plant (ISP) cabling is all indoor fiber optic cables installed from the first fiber optic distribution panel (FODP) or splice case and interconnects between CELs. The minimum cable size between closets shall be 12 strands. Existing inter-CEL cable with less than 4 available strands is a candidate for replacement rather than re-use. ISP cable shall be single-mode (OS1) or multimode (OM3). The FODP or splice case is the boundary between OSP and ISP. The government will specify fiber optic adapters/connectors for renovation or addition to existing facilities requiring interface with existing equipment. Minimum four strands (Dual Duplex) per outlet/receptacle. Single-Mode (OS1) may also be required.
2.4 TELECOMMUNICATIONS SPACES
NOTE: AFOSH Standard 91-50, Section 2.10.2 – Storage is not allowed in the electrical and (or) electronic areas. Storage is permitted in approved areas only.
Provide connecting hardware and termination equipment in the telecommunications entrance facility and Communications Equipment Locations (CEL) to facilitate installation as shown on design drawings for terminating and cross-connecting permanent cabling. Provide telecommunications interconnecting hardware color coding in accordance with the latest revision of TIA/EIA-606. Floors, walls, and ceiling shall be treated to eliminate dust.
Finishes shall be light in color to enhance room lighting. Floor shall have anti-static properties. Carpet is not allowed in the entrance facility. Suspended ceilings are not allowed; open to full ceiling without obstructions to allow for cable trays. Sealed Concrete is acceptable in warehouses and limited occupancy facilities. Provide additional 120VAC duplex outlets placed at 6-foot intervals around the perimeter of the telecommunications room.
The door shall have a 5 button mechanical lock with passage (similar to Simplex L1031). Provide environmental controls IAW the latest revision of TIA-569. If sprinklers are installed, the heads shall be provided with wire head cages to protect against accidental discharge. Provide additional services for Core 1 Facilities IAW ETL 01-18, Fire Protection for Electronic Equipment Installations (Ref para 2.14 CRITICAL COMM FACILITES and NODES.)
2.4.1 Backboards
Provide void-free, interior grade A-C plywood, 3/4 inch thick, 4 by 8 feet. Backboards shall be fire rated by manufacturing process. Fire stamp shall be clearly visible. Backboards shall be provided on a minimum of three walls, excluding the wall containing the door, in the telecommunications spaces. Install no greater than
0.3 meter (1 foot) above the finished floor level to no less than 2.1 meters (7 feet) above the finished floor level in the telecommunications spaces. Painting is not authorized.
2.4.2 Equipment Support Frame
Install equipment cabinet(s) to allow for future expansion (additional cabinet). Do not center the cabinet in the room. Cabinets will have clearance of 3 feet front and back, 2 ½ feet on the sides. Multiple cabinets may be mounted together on the sides (ref: para 3.1.7.3.). Provide a minimum of two dedicated un-switched 20-amp, 120-VAC, 60Hz duplex receptacle power outlets, each on a separate branch circuit for communication equipment to the rack/cabinet. Increase these minimum requirements as necessary to meet equipment loads. Mount mid-cabinet level a 19 inch rack mounted power strip with surge protection and minimum 6 outlets. Install a UL-listed horizontal rack grounding bus bar (RGB). Connect the RGB to the telecommunications main ground bar (TMGB), telecommunications ground bar (TGB) or the telecommunications equipment bonding conductor (TEBC) with a #6 AWG ground cable and 2-hole compression lugs. Install an electrostatic discharge strap port on the front of the cabinet. All cabinets shall be keyed alike.
2.4.2.1 Bracket, wall mounted 8 gauge aluminum. This item is not authorized for installation or use unless authorized by an approved change request.
2.4.2.2 Racks, floor mounted modular type. This item is not authorized for installation or use unless authorized by an approved change request.
2.4.2.3 Cabinets, freestanding modular type, must be lockable. Cabinets, freestanding modular type will be permanently anchored to the floor and shall have an inside width of 19 inches and be minimum 41 RU (77”).
Cabinets shall be enclosures with side panels, acrylic plastic lockable front doors and mesh, metal, louvered rear doors with identical keys, depth-adjustable front and rear mounting rails, and louvered top. When cabinets are connected together, remove adjoining side panels for cable routing between cabinets. Top mounted ventilation fans shall be included. A/C shall enter the cabinet from the ceiling to the top of the cabinet, or through the floor to the bottom if on raised floor. Verify all cabinet placement with the 99CS prior to installation.
NOTE: ENSURE CABINET SIZE MEETS REQUIREMENTS TO SUPPORT NETWORK
EQUIPMENT
2.4.2.4 Cabinets, wall-mounted modular type, shall be mounted on a backboard. Mount cabinet so height of highest panel does not exceed 78 inches above floor. Cabinets shall have an inside width of 19 inches and be minimum 26 RU (45.50”). Cabinets shall be enclosures with side panels, acrylic plastic lockable front, depth-adjustable front and rear mounting rails, and louvered top. Top mounted ventilation fans shall be included. Include vertical cable management.
2.4.3 Connector Blocks
Install wall mounted IDC type 110 punch down block on the telecommunications backboard in the entrance facility. Rack mount is not authorized. 110 blocks are only permitted in the entrance facility. The 110 type punch down block shall be labeled to identify corresponding RJ-45 jacks in the patch panel. All wiring and components shall be TIA-568 compliant, wired to T568A wiring configuration. Label IAW TIA/EIA-606.
2.4.4 Cable Guides:
Hook and Loop (Velcro) style guides are only permitted as cable management in cabinets. Hook & Loop may be used in cable tray to separate copper & fiber, and to meet security separation requirements.
2.4.5 Patch Panels
Category 6 Common LAN/VOICE (CLV) patch panels shall consist of RJ-45 8-pin modular jacks (front of patch panel) with rear-installation type 110 insulation displacement terminations. Patch panels are wired identically to allow voice or data to be connected to any outlet. Wire 8-pin modular ports to T568A configuration. All wiring and components shall be TIA-568 compliant. Label patch panels IAW TIA/EIA-606.
2.4.5.1 Modular to 110 Block Patch Panel
Voice Frequency (VF) patch panels shall consist of RJ-45 8-pin modular jacks (front of patch panel), with rear-installation type 110 insulation displacement terminations. Panel shall provide minimum 48 non-keyed ports wired to T568A configuration. All 8 wires of each RJ-45 jack shall be wired to the 110 type punch down block.
Install 24 AWG backbone copper cable from the back of VF patch panels to type 110 punch down blocks mounted on the telecommunications room plywood backboard. The 110 type punch down block shall be labeled to identify corresponding RJ-45 jacks in the patch panel. All wiring and components shall be TIA-568 compliant.
Label patch panels IAW TIA/EIA-606.
2.4.5.2 Fiber Optic Patch Panel
The government will specify fiber optic adapters/connectors for new construction or renovation of existing facilities requiring interface with communications equipment. Provide panels for maintenance and cross-connecting of optical fiber cables. Each panel shall provide adapters in accordance with the most recent revision of TIA/EIA-568 with zirconia ceramic alignment sleeves. Patch panels shall be sized to correspond to the number of fibers installed, plus 25 percent. Patch panels shall be a complete system of components by a single manufacturer, and shall provide termination, splice storage, routing, radius limiting, cable fastening, storage, and cross-connection. Panel shall be constructed of 11 gauge aluminum minimum and shall be cabinet/wall mounted and compatible with ECIA EIA/ECA 310 equipment rack. Provide dust cover for unused adapters. The rear of each panel shall have a cable management tray a minimum of 203 mm [8 inches] deep with removable cover, incoming cable strain-relief and routing guides. Panels shall have each adapter factory numbered and be equipped with laminated plastic nameplates above each adapter.
2.4.6 Optical Fiber Distribution Panel
Cabinet/Wall mounted optical fiber distribution panel (OFDP) shall be constructed in accordance with ECIA EIA/ECA 310 utilizing 11 gauge aluminum minimum. Panel shall be divided into two sections, distribution and user. Distribution section shall have strain relief, routing guides, splice tray and shall be lockable, user section shall have a cover for patch cord protection. Each panel shall provide adapters. Provide dust cover for unused adapters.
Provide optical fiber patch cords with LC connectors attached for patch panels. Provide patch cords, as complete assemblies, with matching connectors. Provide fiber optic patch cables with crossover orientation in accordance with TIA-568-C.3. Patch cords shall meet minimum performance requirements specified in TIA-568-C.1, TIA- 568-C.2 and TIA-568-C.3 for cables, cable length and hardware specified.
2.5 TELECOMMUNICATIONS OUTLET/CONNECTOR ASSEMBLIES
All telecommunications outlets, fiber optic & copper, shall be dual duplex or quad (SC type) receptacles unless otherwise noted. Provide a single RJ-45 outlet for each elevator. Provide a dual RJ-45 outlet within 3 feet of civil engineering Industrial Control System (ICS)/Utility Monitoring and Control System (UMAC), e.g. Johnson Controls. Run the CAT6 cable to the nearest UNCLAS copper patch panel.
NOTE: Provide a single outlet for interior/exterior wall mounted telephones Reference UFC 3-580-01 para 2-3.5 for receptacle/outlet density
2.5.1 Outlet/Connector Copper
Wire each 8-pin outlet/connector to T568A configuration.
2.5.2 Optical Fiber Couplers
Do not use couplers for new construction unless specifically required for interface with existing equipment reused on installations.
2.5.3 Optical Fiber Connectors
Provide in accordance with TIA-455-21. Optical fiber connectors shall be non-keyed duplex LC in accordance with TIA/EIA-604-10 with zirconia ceramic alignment sleeves compatible with OM3 multimode or OS1 single-mode fiber. The connectors shall provide a maximum attenuation of 0.3 dB with less than a 0.2 dB change after 500 mating cycles. Provide duplex fiber optic adapters and connectors with zirconia ceramic alignment sleeves for new construction. The government will specify fiber optic adapters/connectors for renovation or addition to existing facilities requiring interface with existing equipment. The government will specify fiber optic adapters/connectors for secure systems as required by the customer and accreditation authority.
2.5.4 Cover Plates
Telecommunications cover plates shall comply with UL 514C, and TIA-568 series flush design constructed to match color of receptacle/switch cover plates specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Provide labeling in accordance with TIA/EIA-606-A.
2.13 ALARM CIRCUITS
Government provides Voice Grade copper, dry-pair, circuits only. Provide thirty (30) calendar days’ notice for alarm circuit activation. The equipment must be compatible with the existing alarm system and telephone circuits.
2.14 ACCESS CONTROLS & IDS
The government will specify cable and connectors for Access Controls and IDS systems as required by the customer and accreditation authority.
2.15 CRITICAL COMM FACILITIES and NODES
All Core 1 facilities require the telecommunications cabinet(s) dedicated electrical outlets be connected to the facility generator, or facility UPS if installed. Information Transfer Node (ITN) facilities require four (4) dedicated NEMA L6-30R 208(240V), and one (1) dedicated 5-20R 120V quad outlet per cabinet. Reference ETL 01-18, Fire Protection for Electronic Equipment Installations for additional fire protection requirements. Per 99 CS do not place any sprinkler heads directly above communications equipment.
2.16 HEAT RESISTANT BULKHEADS IN OUTDOOR ENCLOSURES
When installing bulkheads in NEMA or metal outdoor enclosures, use heat resistant bulkheads due to the extreme desert temps in Southern Nevada.
PART 3 EXECUTION
3.1.1.1 Open Cable
Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. Placement of cable parallel to power conductors shall be avoided, if possible; a minimum separation of 300 mm [12 inches] shall be maintained when such placement cannot be avoided.
3.1.1.2 Backbone Cable
Only install backbone copper cable between the 110 block in the entrance facility (EF) to patch panels in the Communications Equipment Locations (CEL). Home run the backbone copper from the patch panels in the CELs to the 110 block in the EF. 110 blocks are only installed in the EF.
3.1.6.1 Terminations
Terminate UTP cable to T568B wiring configuration. Validate configuration to currently installed cabling.
3.1.7.2 Patch Panels
Patch panels shall be mounted in equipment cabinets with sufficient ports to accommodate the installed cable plant plus 25 percent spares.
3.1.7.3 Equipment Support Frames
Install equipment cabinet(s) to allow for future expansion (additional cabinet). Cabinets will have a clearance of 3 feet front and back, 2 ½ feet at the sides (ends of cabinet run). Each cabinet will have a rack grounding bus bar (RGB). Connect each cabinet RGB to the TMGB, TGB or TEBC with a #6 AWG ground cable and 2-hole compression lugs.
a. Bracket, wall mounted, 8 gauge aluminum. This item is not authorized for installation or use unless authorized by an approved by a change request.
b. Racks, floor mounted modular type. This item is not authorized for installation or use unless authorized by an approved by a change request.
c. Cabinets, freestanding modular type. When cabinets are connected together, remove adjoining side panels for cable routing between cabinets. Install the rack-mounted fan in the roof of the cabinet. Cabinets will be permanently anchored to the floor. Do not center the cabinet in the room. A/C shall enter the cabinet from the ceiling to the top of the cabinet, or through the floor to the bottom if on raised floor.
d. Cabinets, wall-mounted modular type. Mount cabinet to plywood backboard in accordance with manufacturer's recommendations. Mount cabinet so height of highest panel does not exceed 1980 mm [78 inches] above floor. Install rack-mounted fan in the roof of the cabinet. Cabinets shall open freely and not be obstructed, allowing for maintenance in the back of the cabinet.
3.3.1 Painting Backboards: Painting of Backboards is not authorized
-- End of Section --
A.1- SECTION 26 20 00 INTERIOR DISTRIBUTION SYSTEM
NELLIS AND CREECH ADDENDUM
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
NOTE: This appendix covers Nellis and Creech AFB requirements for building telecommunications cabling systems and shall be used in conjunction with the specifications outlined in Unified Facilities Guide Specifications (UFGS) Section 26 20 00. This document does not replace, but further details the specifications in UFGS Section 26 20 00. Specifications and requirements in UFGS Section 26 20 00 must be adhered to while meeting the requirements and specifications within this document. UFGS Section 26 20 00 is not covered in its entirety in this appendix, only specific paragraphs are addressed. All paragraph nomenclature directly corresponds with UFGS Section 26 20 00, Interior Distribution System dated 02/14. The base communications squadron will make the final determination on any and all telecommunications cabling systems and related components.
2.5 CABLE TRAYS: Raceway/Cable tray fill shall not exceed 40 percent.
2.6 OPEN TELECOMMUNICATIONS CABLE SUPPORT
J-supports & D-rings are permitted for short cable runs with a minimal number of cables.
2.7.2 OUTLET BOXES FOR TELECOMMUNICATIONS SYSTEM
Outlet boxes for wall-mounted telecommunications outlets shall be 4 inches by 2-1/8 inches by 2-1/8 inches deep. Depth of boxes shall be large enough to allow manufacturers' recommended conductor bend radii.
Outlet boxes for all telecommunication outlets shall include a minimum 3/8 inch deep single or two gang plaster ring as shown and be installed using a minimum 1 inch conduit system.
2.28.3. Minimum dimensions of 0.25 inch thick by 4 inches wide by 10 inches long for TMGB and TGB. TMGB/TGB shall be copper. TMGB/TGB will be copper. Perform and provide TMGB/TGB Ground Bus resistance test results (5 ohms or less) in accordance with NEC art 501-510, MIL-STD-188-124B, para 5.1.1.1.7.
3.1.8 CABLE TRAY INSTALLATION
Install and ground in accordance with NFPA 70. In addition, install and ground telecommunications cable tray in accordance with the latest version of TIA-569-C, and TIA-607-B. Install cable trays parallel with or at right angles to ceilings, walls, and structural members. Support in accordance with manufacturer recommendations but at not more than 5 foot intervals. Contact surfaces of aluminum connections shall be coated with an antioxidant compound prior to assembly. Adjacent cable tray sections shall be bonded together by connector plates of an identical type as the cable tray sections. Terminate cable trays 255 mm [10 inches] from both sides of smoke and fire partitions.
Conductors run through smoke and fire partitions shall be installed in 4 inch rigid steel conduits with grounding bushings, extending 305 mm [12 inches] beyond each side of partitions. Seal conduit on both ends to maintain smoke and fire ratings of partitions. Penetrations shall be firestopped in accordance with Section 07 84 00, FIRESTOPPING. Provide supports to resist forces of 0.5 times the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.
3.1.8.1 Vertical Cable Supports, Drop-Outs or Waterfalls will be installed from the cable tray to cabinets to protect cable installation as it exits the cable tray and maintain the cable manufacturer's minimum standard bend radius.
3.1.8.2 Install cable tray system so it is accessible. A minimum of 12 inches should be left above or between installed systems to allow for cable installation and maintenance
3.1.9 Telecommunications Cable Support Installation
Install J-supports & D-rings not to exceed 5 feet apart. Cables routed in a suspended ceiling shall not be draped across the ceiling tiles or light fixtures. Hook & Loop fasteners (e.g. Velcro) will not be used for cable support, but may be used for cable management.
3.1.19.5 TMGB and TGBs shall be a minimum dimensions of 0.25 inch thick by 4 inches wide by 10 inches long.
TMGB/TGB will be copper. Install bus bars in all telecommunications equipment rooms. Install between 2 and 4 feet above floor level. Connections to the TMGB/TGB: utilize listed compression two-hole lugs, exothermic welding, or other irreversible compression type connections as per the UFGS 26 20 00, para 3.1.19.5c. Single-hole lugs are not permitted.
3.1.19.5. Telecommunications Grounding Label: Label near point of connection at panel board and each TMGB and TGB in accordance with the most recent revision TIA-607, “If this connector or Cable is loose or must be removed, please call the building telecommunications manager.”
3.1.19.5.1 Ground on each end (one end to TMGB/TGB) and at intervals not to exceed 18m (60 feet). Use a #6 AWG cable with green/yellow stripe to jumper between discontinuous segments on both side rails. The jumper shall be made with 2-hole compression lugs terminated on both ends.
-- End of Section –
A.3 SECTION 33 71 02 - ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
NELLIS AND CREECH ADDENDUM
SECTION 33 71 02.
UNDERGROUND ELECTRICAL DISTRIBUTION
NOTE: This appendix covers Nellis and Creech AFB requirements for building telecommunications cabling systems and shall be used in conjunction with the specifications outlined in Unified Facilities Guide Specifications (UFGS) Section 33 71 02. This document does not replace, but further details the specifications in UFGS Section 33 71 02. Specifications and requirements in UFGS Section 33 71 02 must be adhered to while meeting the requirements and specifications within this document. UFGS Section 33 71 02 is not covered in its entirety in this appendix, only specific paragraphs are addressed. All paragraph nomenclature directly corresponds with UFGS Section 33 71 02, Electrical Distribution System, Underground, dated 02/15. The base communications squadron will make the final determination on any and all telecommunications cabling systems and related components.
2.14.3 COMMUNICATIONS MANHOLES
Communications manholes (CMH) shall be 7 feet high by 12 feet long by 6 feet wide. The CMH will consist of pre-cast reinforced concrete box, extensions, base and cover. The manhole will be equipped with a standard ladder of hot dipped galvanized steel construction with non-slip rungs.
One end of the ladder will be formed into hooks to engage the manhole step. Provide pulling-in irons installed on each wall, positioned 6" to 12" below duct entrances. Provide four cable support brackets on each sidewall and one cable support bracket on each end wall of manhole. Each cable support will have a minimum of three 7-inch cable steps installed. Finish conduit flush with interior walls and grout around conduits. Bell-ends are required on the end of each conduit and finish grout applied. Install bell-ends flush with wall of the manhole.
The cover for the manhole will be able to withstand traffic load bearing applications. Cover will be marked "TELEPHONE” or “TELECOMMUNICATIONS.”
The manhole will be equipped with one 8 foot copper clad ground-rod pounded or the manhole will be grid grounded. Leave ground rod exposed 6" in a corner of the manhole. Install manholes with long wall parallel to the main duct run.
Features and qualities similar to an EMBARQ 6000.
Install ducts in the first available knockout from the bottom of the manhole. Label the destination of installed conduit next to the duct. Label letters shall be a minimum 2 inches high in permanent paint or ink.
Communications manholes will be shall be located within 50 feet of the building communications entrance.
2.14.4 COMMUNICATIONS HANDHOLES
Communications handholes (HH) shall be a minimum 3 feet high by 5 feet long by 4 feet wide. HH will have a minimum of 4 total, 2 per side, 18-hole cable racks. 8 total 2 inch terminators will be provided on the HH; each side wall will have 4 terminators. Each end well will contain intercept knockouts.
The cover for the handhole will be able to withstand traffic load bearing applications. Cover will be marked "TELEPHONE" or “TELECOMMUNICATIONS.” The HH will consist of aluminum 2 door hinged lay back torsion spring assisted cover. Cover will be capable of being opened 180 degrees to full layback position. Cover will be attached to a galvanized steel frame mounted within a collar riser.
The handhole will be equipped with one 8 foot copper clad ground-rod pounded or the handhole will be grid grounded. Leave ground rod exposed 6" in the corner of a handhole. Install handholes with long wall parallel to the main duct run.
Features and qualities similar to an EMBARQ 400.
Install ducts in the first available knockout from the bottom of the handhole. Label the destination of the installed duct next to the duct. Label letters shall be a minimum 2 inches high in permanent paint or ink. Communications handholes shall be located within 50 feet of the building communications entrance.
-- End of Section -
A.4 SECTION 33 82 00 - TELECOMMUNICATIONS, OUTSIDE PLANT
NELLIS AND CREECH ADDENDUM
SECTION 33 82 00
TELECOMMUNICATIONS, OUTSIDE PLANT
NOTE: This appendix covers Nellis and Creech AFB requirements for building telecommunications cabling systems and shall be used in conjunction with the specifications outlined in Unified Facilities Guide Specifications (UFGS) Section 33 82 00. This document does not replace, but further details the specifications in UFGS Section 33 82 00. Specifications and requirements in UFGS Section 33 82 00 must be adhered to while meeting the requirements and specifications within this document. UFGS Section 33 82 00 is not covered in its entirety in this appendix, only specific paragraphs are addressed. All paragraph nomenclature directly corresponds with UFGS Section 33 82 00, Telecommunications, Outside Plan, dated 04/06. The base communications squadron will make the final determination on any and all telecommunications cabling systems and related components.
SD-12 Geospatial Information (GPS) Submittals The Contractor shall use GPS technology to locate and collect data on outside plant infrastructure features and communications pathways installed or modified as a result to the Contractor’s installation work. See Attachment 1 of this NC Addendum.
1.6.2 TELECOMMUNICATIONS QUALIFICATIONS
All work under this section shall be performed by and all equipment shall be furnished and installed by a Building Industry Consulting Services International (BICSI) certified Telecommunications Contractor who uses BICSI Registered Cabling Installers, Technician Level. The Electrical Contractor shall not perform the installation of communications distribution system cables, equipment, and associated hardware with the exception of furnishing and installing conduit, electrical boxes, grounding equipment and components, cable tray, and pull-wires.
1.6.2.2 KEY PERSONNEL
All installers assigned to the installation of this system or any of its components shall have a minimum of 3 years of experience in the installation of the specified copper wire, fiber optic cable and components.
General electrical trade staff (electricians) shall not be employed for the installation of the communications distribution system cables, equipment, and associated hardware.
Supervisors and installers assigned to the installation of this system or any of its components shall be BICSI Registered Cabling Installers, Technician Level. Submit documentation of current BICSI certification for each of the key personnel.
NOTE: Each installer may be required to make an approved dummy splice of each type to be employed in the execution of this contract in the presence of the Contracting Officer and a Quality Assurance Evaluator from the base communications squadron. Splices shall be in accordance with the cable manufacturer’s instructions.
The contractor shall furnish all materials needed for dummy splices, at no cost to the government.
2.2.1 BUILDING PROTECTOR ASSEMBLIES: Use 5-pin self-contained units only.
2.3.1.1 AERIAL CABLE CLOSURES: This item is not authorized for installation or use.
2.3.1.2 UNDERGROUND CABLE CLOSURE: This item is not authorized for installation or use.
2.3.2.1 AERIAL: This item is not authorized for installation or use.
2.8.1.2 AERIAL: This item is not authorized for installation or use.
2.8.1.3 SCREEN: This item is not authorized for installation or use.
2.8.2 Fiber Optic Cable: Indoor-outdoor rated distribution fiber optic cable is not authorized
2.8.2.1 STRENGTH MEMBERS
Use metallic strength members with sufficient tensile strength for installation and residual rated loads to meet the applicable performance requirements in accordance with ICEA S-87-640.
2.9 T-SPAN LINE TREATMENT REPEATERS: This item is not authorized for installation or use.
2.10 POLES AND HARDWARE: This item is not authorized for installation or use.
2.16.1 FACTORY REEL TEST DATA: Enhanced performance air core OSP copper cables are not authorized for installation or use.
3.1.5 Underground Duct
a. Fiber Innerduct - Install three, 3 inch 3-Cell fabric innerduct in one conduit. One of the fabric innerducts shall be detectable (tracer wire embedded in fabric). Features/style similar to MaxCell MX_3456
b. Do not install or mix copper cable and fiber cable in the same conduit
c. Conduit entering the facility shall be sealed at the building end to prevent rodents, water, or gases from entering the facility.
3.1.8 CABLE PULLING: Do not bend cable and wire in a radius less than 20 times the outside diameter of the cable or wire.
3.1.9 AERIAL CABLE INSTALLATION: This item is not authorized for installation or use.
-- End of Section -
Attachment 1, SECTION 33 82 00, GEOSPATIAL INFORMATION
Nellis & Creech AFB Addendum
SECTION 33 82 00
Attachment 1
COLLECT AND DELIVER GEOSPATIAL INFORMATION
1.1 GENERAL: The Contractor shall use GPS technology to locate and collect data on outside plant infrastructure features and communications pathways that are installed or modified as a result to the Contractor’s installation work.
Outside plant features include manholes, vaults, handholes, pedestals, underground cables, marked direct buried splices, terminals etc. The communications pathways include duct routes, direct-buried cable, and communication pathway entry points on building exterior walls that lead to interior building entry terminals, etc. The Contractor shall augment the GPS survey by using conventional land surveying equipment and electronic cable locating (underground utility toning) equipment when necessary to accurately locate features. The Contractor shall convert the GPS data to an ESRI Shape file set suitable for the Government to load the file and transcribe information from the Shape file into the CVC database.
1.2 GPS DATA COLLECTIONS REQUIREMENTS
1.2.1 GPS ACCURACY STANDARDS: The Contractor shall use GPS to determine the horizontal position of communications outside plant infrastructure and communications pathways features in accordance with the Federal Geographic Data Committee (FGDC)-STD-007.4-2002. FGDC publications are downloadable from the website:
http://www.fgdc.gov/.
GPS ACCURACY OF FEATURE LOCATIONS: Each outside plant infrastructure feature and communications pathway requiring geospatial coordinates shall be located to within 50 cm after post processing in the horizontal plane, with a 95% spatial accuracy confidence level as defined in FGDC-STD-007.3-1998 (Refer to paragraph 1.2.2.
for documentation requirements). Geospatial coordinates for the location of manholes and cable vaults shall be recorded for the center of the manhole lid. Geospatial coordinates for the location of handholes, pull boxes, pedestals, and marked direct buried splices shall be recorded for the top center of the feature. Geospatial coordinate data for the location of communication pathways lines shall be recorded at a minimum every 50 feet and coordinates for points along the pathway and at each turn or bend in a cable installation pathway a sufficient number of data points must also be collected and recorded so that the coordinates for any point along the pathway will fall within the allowable accuracy.
1.2.2 GPS DATA FORMAT: The Contractor shall format the data dictionary in the GPS data loggers by using the entity naming convention, attribute fields and domain values as specified in Table A. GPS data loggers shall be set up to record and export the GPS Data Collector Setup properties listed in Table B.
1.2 GEOSPATIAL DATA REQUIREMENTS
1.2.1 SHAPE FILES: The GPS collected outside plant infrastructure features and communications pathways attribute, metadata, and location information shall be converted to, stored, and submitted in Environmental Systems Research Institute (ESRI) Shape File format. Each shape file set shall contain all the files that make up the general shape file, i.e., “.shp”, “.shx”, “.dbf”, etc. along with the specified metadata file. Each shape file set shall have a geospatial reference (.prj) file included that specifies the parameters of the spatial reference system. Also, the dbf component of the shape file set shall contain the Table A entities, attributes, and domain values for communication features and the GPS Data Collector Setup Properties listed in Table B.
1.2.1 METADATA: For each set of outside plant infrastructure features and communications pathways data using GPS, the Contractor shall complete all metadata elements marked mandatory as defined by the FGDC–STD-001- 1998. Metadata shall be formatted and stored as an XML document that is compatible with the submitted shape files.
http://www.fgdc.gov/
1.2.2 ACCURACY WORKSHEETS: Calculation worksheets showing compliance with the National Standard for Spatial Data Accuracy (NSSDA) statement at the 95% confidence level, as required by paragraph…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .