2011-7-7___Demolish_bldg_434.pdf

PDF 2 MB Posted

Attached to
Attachment 19: Past Performance Survey
Solicitation number
FA4861-13-R-A014
Issued by

About this file

Abatement report bldg 434

View the file

Other files

File Type Posted
RKMF_13-0135_as-builts.zip ZIP file
2011-7-8___Demo_bldg_433.pdf PDF
2011-7-7___Demolish_bldg_438.pdf PDF
2011-7-7___Demolish_Bldg_436.pdf PDF
Atch_5 _Bid_Schedule_RKMF_13-0135_revised_16Sep2013.docx DOCX document
Solicitation_Amendment_0002.docx DOCX document
13-R-A014_Site_Visit_Attendance_Sheet.pdf PDF
Attachment_19-_Past_Performance_Survey.docx DOCX document
FA4861-13-R-A014-P00001.pdf PDF
Atch_6 __Nellis-Creech_ID2_Handbook_2011.pdf PDF
Atch_10 _AF_Form_3064.xfdl XFDL file
Atch_2 _WD_NV130034_Hwy __Mod_34.docx DOCX document
Atch_13 _DD_Form_1354.pdf PDF
Atch_7 _ETL__02-12.pdf PDF
Atch_4 _AF_Form_3052_Cost_Estimate_Breakdown.xls XLS spreadsheet
Atch_1 _SOW_Demo_Pool_dtd_20_Aug_13.docx DOCX document
Atch_15 _ACC_Arch_ _Interior_Design_Stand.doc DOC document
Atch_09 _AF_Form_66.doc DOC document
Atch_17 __ID_Warranty.Guarantee_Items.doc DOC document
Atch_11 _AF_Form_3000.xfdl XFDL file
Atch_5 _Bid_Schedule_RKMF_13-0135.docx DOCX document
Atch_16 _AF_Form_103.xfdl XFDL file
Atch_19 _PastPerformance.pdf PDF
Atch_12 _AF_Form_3065 _ProgRpt.xls XLS spreadsheet
Atch_3 _WD_NV130004 _Bldg _Mod_05.docx DOCX document
Atch_14 _UFC_1-300-08_With_C2.pdf PDF
Atch_08 _UFC_3-580-01.docx DOCX document
FA4861-13-R-A014.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Macrotec Consulting, LLC.

9724 Mild Weather Ct. · Las Vegas, NV 89148 Phone: (702) 338-8213 · Fax: (702) 629-5677

Demolition Investigation Report Asbestos and Lead Based Paint Survey

Project Information:

Nellis Air Force Base Bldg. 434 (Swimming Pool)

Report Info:

Macrotec Project # 11801 July 20, 2011

Prepared For:

Vince Bowers 99th Civil Engineering Squadron – CES/CEV Nellis AFB, NV 89191

Prepared By:

Dustin McAllister - Macrotec Consulting, LLC.

Table of Contents:

Introduction Scope of Services Site Description Sample Collection Methodology Sample Analysis Methodology Sample Assessment Recommendations Inspection Limitations

Appendix A Asbestos Assessment Appendix B Lead Assessment Appendix C Asbestos Sample Location Diagram Appendix C.1 Lead Sample Location Diagram Appendix D Asbestos Laboratory Report Appendix D.1 Lead Laboratory Report

Asbestos / Lead Survey Macrotec Project # 11801 Nellis Air Force Base – Bldg. 434 Page 2

INTRODUCTION

Macrotec Consulting performed an inspection for Asbestos-Containing Building Materials and Lead Based Paint on July 7, 2011. The inspection was conducted for the project defined as: Demolition of building 438 (Swimming Pool) at Nellis Air Force Base in Las Vegas, NV.

The intent of this inspection was to identify materials containing asbestos and lead based paint, within the subject site, that may be impacted during planned demolition activities. Macrotec’s inspection services were conducted at the request of Vince Bowers of the 99th Civil Engineering Squadron.

Dustin McAllister, a certified lead inspector, License No. NV-I-16781-1, and a Nevada Asbestos Abatement Consultant, License No.IM0961, and Jason McAllister, a Nevada Asbestos Abatement Consultant, License No. IM0901, conducted these services for Macrotec Consulting.

SCOPE OF SERVICES

Asbestos

Macrotec’s inspection services were conducted to identify the presence of any materials containing asbestos pursuant to the requirements of NAC 618.960 and in accordance with the inspection requirements of the EPA’s: 40 CFR Part 61 National Emission Standard for Hazardous Air Pollutants (NESHAP).

These regulations outline inspection and abatement requirements for materials containing asbestos, prior to renovation and/or demolition activities.

Lead

Macrotec collected paint chip samples to identify the presence and content level of lead for compliance with the Occupational Safety and Health Administration’s (OSHA) and the Environmental Protection Agencies (EPA) regulatory requirements pertaining to worker protection and waste disposal.

SITE DESCRIPTION

The subject site was the outdoor space that included three pools and a surrounding deck.

Macrotec’s inspection was limited to the location within the site planned for demolition as described above.

Nellis Air Force Base – Bldg. 434 Page 3

SAMPLE COLLECTION METHODOLOGY

An initial walk through of the subject site was conducted to identify homogeneous suspect materials containing asbestos and/or lead based paint, and their respective locations. This information was then used to develop a sample collection strategy.

Samples were collected by pre-wetting sample areas with water, then cutting or scraping the sample from the substrate with an appropriate sampling tool.

Whenever possible, samples were collected from areas previously damaged or deteriorating. To avoid potential contamination due to unknown asbestos and/or lead based paint content; no building systems, components, or structures were demolished to obtain samples of potentially hidden materials containing asbestos.

Each suspect bulk sample was sealed in its own zip lock plastic container and labeled with a unique identification number. Sampling tools were individually cleaned before and after each sample was collected to avoid sample cross contamination. Decontamination was accomplished using single use, pre-moistened cloths.

Samples were recorded on Macrotec’s chain-of-custody form. This form accompanied the samples to Triangle Enivronmental Service Center, Inc.

(TESC), located in Moseley, Virginia. The National Voluntary Laboratory Accreditation Program (NVLAP) accredits TESC for analysis of bulk building material samples for asbestos. The American Industrial Hygiene Association (AIHA) accredits Schneider Laboratories Inc. in Richmond Virginia, for analysis of paint chip samples for lead.

SAMPLE ANALYSIS METHODOLOGY

Asbestos

Suspect asbestos samples were subjected to analysis by polarized light microscopy (PLM). Bulk sample analysis was conducted in accordance with the EPA’s “Test Method for the Determination of Asbestos in Bulk Building Materials, EPA/600/R-93/116, 1993.

Lead

To determine lead content, the samples were submitted for analysis. Suspect paint chip samples were subjected to analysis in accordance with the EPA’s Method SW846-7420.

Nellis Air Force Base – Bldg. 434 Page 4

SAMPLE ASSESSMENT

Asbestos

Macrotec’s inspection of the subject site found Eight (8) separate suspect asbestos building materials, of which a total of Eight (8) samples were collected and submitted for analysis.

The sample results indicated that the suspect materials were “None Detected” for asbestos content.

Note: The plaster inside the pools was not sampled during this investigation.

The pools should be tested immediately prior to demolishing the area, when they are emptied and no longer in use.

See Appendix A for a listing of the materials, material locations, samples, sample locations and results for this project.

Lead

Macrotec collected Nineteen (19) paint samples of the predominate paint colors within the subject site.

Note: The ceramic tile inside the pools was not sampled during this investigation. The ceramic tile in the pools should be tested immediately prior to demolishing the area, when they are emptied and no longer in use.

See Appendix B for a listing of the painted surfaces, samples, sample locations and results for this project.

RECOMMENDATIONS

Asbestos

No asbestos containing materials were identified in this investigation. If suspect materials are found during demolition activities outside what was identified in this report, stop work immediately until further testing can be completed.

Conduct an investigation inside the pools prior to demolition, but after the they no longer in use.

Lead

None of the paints sampled in this investigation were found to be a lead based paint (above 5,000 parts per million). Please be advised that Nellis AFB may have further regulations for the handling of materials with paint over 600 parts per million. If suspect materials are found during renovation activities outside

Nellis Air Force Base – Bldg. 434 Page 5 what was identified in this report, stop work immediately until further testing can be completed.

Conduct an investigation inside the pools prior to demolition, but after the they no longer in use.

INSPECTION LIMITATIONS

The information contained in this report is limited to those areas and suspect materials found to be visually accessible through reasonable means.

Note: The pool area was occupied / in use at the time of the investigation, limiting the availability of some materials and areas.

Macrotec conducted a non-destructive survey. No demolition of building materials was conducted to determine the presence of asbestos in wall cavities, chases or other inaccessible areas. Macrotec cannot warrant that these areas do not contain asbestos in locations other than those noted in this report, however, a good faith effort was made to conduct a comprehensive survey.

• Macrotec accepts no liability for additional materials or under reporting of asbestos materials that exist below other floor coverings.

• This report is not represented as, nor is it intended to be, an asbestos abatement scope of work or project specification.

• If suspect materials are discovered during future demolition operations, cease all general work activities which could impact the discovered suspect materials, until confirmation sampling can be conducted.

Thank you for allowing Macrotec Consulting to assist you with your environmental consulting needs. Please contact me with any questions regarding this report at (702) 338-8213.

Appendix A

Appendix A - Asbestos Assessment

Macrotec Job #11801 - Bldg. 434 ; WO #17999

The following table lists each of the materials suspected to contain asbestos at the subject site. For each material the sample number, location and laboratory result are listed. If the material was found to contain asbestos, the friablity and NESHAP classification is identified.

1 Cool-Crete Concrete Coating This material is located around the pool

No Asbestos Detected

AB1 Pool Deck - Center None Detected

2 Concrete Deck This material is located around the pool

No Asbestos Detected

AB2 Pool Deck - Center None Detected

3 Deck Seam Caulk This material is located around the pool.

No Asbestos Detected

AB3 Pool Deck - Center None Detected

4 Cinderblock This material is located around the perimeter of the pool area.

No Asbestos Detected

AB4 Perimeter Wall - S side None Detected

5 Mortar This material is located around the perimeter of the pool area.

No Asbestos Detected

AB5 Perimeter Wall - S side None Detected

6 Gasket This material is located adjacent the pool slide.

No Asbestos Detected

AB6 Slide Pump - Center None Detected

7 Caulk This material is located adjacent the pool slide.

No Asbestos Detected

AB7 Slide Pump - Center None Detected

Asbestos Survey

Bldg. 434 (Swimming Pool)

Macrotec Job #11801

Appendix A Macrotec Job #11801 - Bldg. 434 ; WO #17999

8 Asphalt Roof Shingle This material is located adjacent the pool slide.

No Asbestos Detected

AB8 Shed - Roof None Detected

Asbestos Survey

Bldg. 434 (Swimming Pool)

Appendix B

Appendix B - Lead Assessment

Macrotec Job #11801 - Bldg. 434 ; WO #17999

The following table lists each of the painted surfaces suspected to contain lead at the subject site. For each painted surface, the sample number, location and laboratory result are listed.

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L1 Interior - Wall - N end Below Reportable LimitBeige Brick Perimeter Wall

L2 Interior - NE corner 57Beige Concrete Floor

L3 Interior - SW corner 56Beige Concrete Floor

L4 Interior - Baby Pool - E side Below Reportable LimitWhite Concrete Pool Edge

L5 Interior - Olympic Pool - E side Below Reportable LimitWhite Concrete Pool Edge

L6 Interior - Diving Pool - N side Below Reportable LimitWhite Concrete Pool Edge

L7 Interior - Adj. diving pool Below Reportable LimitBeige Concrete Diving Board Pole

L8 Interior - Large diving board Below Reportable LimitBeige Metal Ladder

L9 Interior - Large diving board Below Reportable LimitTan Metal Stair

L10 Interior - Lifeguard stations 231Blue Metal Lifeguard Pole

L11 Interior - Large overhang Below Reportable LimitWhite Metal Overhang Base

L12 Interior - SE overhang 130White Metal Overhang Pole

L13 Interior - Baby pool overhang 33White Metal Overhang Ceiling

L14 Interior - SW canopy Below Reportable LimitWhite Metal Canopy Pole

L15 Interior - NW corner Below Reportable LimitWhite Metal Slide Fence

L16 Interior - E side Below Reportable LimitBrown Wood Shed Wall

L17 Interior - E side Below Reportable LimitTan Wood Shed Wall

L18 Interior - N end Below Reportable LimitTan Metal Pipe

Lead Paint Survey

Bldg. 434 (Swimming Pool)

Appendix C

Asbestos & Lead Based Paint Survey

Nellis AFB, Bldg. 434

Macrotec Project # 11801

Appendix C

* Diagram Not Drawn To Scale

Sample Location Diagram

N

AB1

AB2

AB3

AB4

AB5

AB6

AB7

AB8

Asbestos & Lead Based Paint Survey

Nellis AFB, Bldg. 434

Macrotec Project # 11801

Appendix C

* Diagram Not Drawn To Scale

Sample Location Diagram

N

L1

L2

L3

L4

L5

L6

L7

L8

L9

L10

L11

L12

L13

L14

L15

L16

L17

L18

Appendix D

File details come from the government source that posted it. Updated .