Attachment 10

7 Apr 10

57 Wing Advanced Programs Office

POC

Nicole Rall 702-652-6069

[CONTRUCTION REQUIREMENTS]

The following are standards required to operate a Secure Compartmentalized Information Facility in accordance with DCID 6/9. These requirements will be used at all construction meetings for planning and reference.

FACILITY CONSTRUCTION

REQUIREMENTS

Access Control

Access control panels will be housed in highest classification room in SCIF o Panel will be installed above the ceiling with a power outlet and NIPR connector adjacent to the box

Main SCIF door is required to have Access Control o Our system is the DSX-1048. Suggest you use this system. Must be compatible with our system.

If only two doors are required to be use a DSX-1022 can be used If more than two doors the DSX-1048 is required.

The DSX systems can only operate 8 doors. If more than 8 doors are to be controlled multiple panels will be required.

*See attachment

Any questions for Access Control specific can be brought to Ideal Communications-CCTV

1215 San Eduardo Ave Henderson, NV 89015 702-565-3663 Nev Lic #0043923

For IP addresses, contact Don Haeffele at 652-3306 and must have connectivity to bldg

Must preinstall conduit to all locations Access Control will be installed o Get with user to determine number of rooms to have card swipe

Reference DCID 6/9, Annex F

Power to operate electronic strike, magnet or LKM series lock will be route to each door frame requiring access control

Acoustics

Stated in DCID 6/9, Annex E, when normal construction and baffling measures have been determined to be inadequate for meeting Sound Group 3 or 4, as appropriate, sound masking shall be employed. Protection against interception of discussions may include use of sound masking devices, structural enhancements, or SCIF perimeter placement.

o White noise generating systems will be placed in all ducts penetrating the exterior SCIF wall and controlled from inside the SCIF.

o If doors do not meet STC ratings a sound masking can be used to protect against eavesdropping Sound masking may utilize a noise generator, tape, disc or record player as a noise source and an amplifier and speakers or transducers for distribution. *See attachment

Ensure facility drawings show internal wall specs (insulation and layers of sheetrock)

Blue Lights

Blue Lights will be installed in each room of the SCIF

Each SCIF will have ONE master control to turn light on and off

If there will be a SCIF inside the SCIF it will require its own blue light and switch, independent of the other blue light system *See attachment

Communication

Comm room must have capability to limit access to communication equipment and be located inside the facility o Controlled room with cipher lock on door, lock/key, or access control, etc

All communications to SCIF will enter via one point in the Comm Room

Access control panel will be installed in comm. Room and must have NIPR and power port to connect DSX system. Each access control panel can control up to 8 doors.

IDS system (PCU) will be installed above ceiling in highest security room- if cannot be installed in comm room o Need copper phone line and power outlet above ceiling o Must preinstall conduit just inside the main door for the alarm keypad

FIBER: Our preference for color coding networks are: Green (unclassified), Red (Siprnet), Orange (TS), Yellow (SCI). Unfortunately this does not cross over very well with fiber, as an example, yellow fiber tends to be single mode fiber, which should not be installed for workstation connections. Our recommendation is that you use different connectors for Niprnet (ST, along with Orange fiber cable) and Siprnet (SC, along with Red fiber cable). Poc for more information please contact Don Haeffele, IAO 57 WG/AP 702- 652-3306

Phone lines will be shielded copper

Doors

Main Vault Door o Only one primary entrance into SCIF will be used o SCIF Door will meet STC 50 rating

Wall framing must be built to withstand weight of STC 50 door

Door frame must meet STC 50 rating o Door 57 WG/AP suggest to be installed in all future facilities is Lockmaster STC 50 door with LKM7003 with key override lock

Has one motion emergency exit

X-09 lock

Access Control internal to door

Frame meets STC 50 rating

Lock installed at Factory

Lockmasters' door packages include the door, frame, hardware and fasteners shipped to you in one convenient package. Door packages are fabricated specifically to fit needs of the costumer.

Door packages are pre-assembled, eliminating problems that often arise due to hardware inconsistencies. Lockmasters trained hardware installers mount the specified lock package during the door assembly process also assuring its compatibility with the door package and other hardware.

CDX-O9 Locks: CDX-09 security lock shall be installed for interior access door(s) to the security area (SCIF) shown in the concept plan. CDX-09 lock system shall have deadbolt locking system to meet FF-L-2890 specifications, heavy duty encapsulated strike with one push or pull of the lever to allow exit, ADA compliance lever handle, and key override option to allow entry without using an existing, integrated access control device during the event of a power outage, failure or malfunction of an access control device, and other emergency situations when expedited entry is the top priority. Access control device shall be proximity card reader and key pad. CDX-09 lock system shall be “Lock-One” LKM7003X09 Series or approved equal.

Emergency Exit Door o SCIF Door will meet STC 50 rating

Wall framing must be built to withstand weight of STC 50 door

Door frame must meet STC 50 rating o Must not have hardware affixed to outside

LockOne exit only with stainless steel cover & strike o Must be alarmed 24 hours a day o Must have system to annunciate to alarm others of emergency door activation o Must have BMS and PIR installed o Door will have device that will sound each time the door is opened.

Must be key deactivated. *See attachment

Door Seals o Must have STC 50 rated door seals to maximize sound attenuation.

Reference DCID 6/9, 3.3.3 and Intrusion Detection System (IDS) in DCID 6/9, Annex B

*See attachment

Ducts

All ducts penetrating the exterior wall of the SCIF will have sound masking system installed- See Acoustics for specs o Can either be sound baffles or white noise generator

Ducts over 96 square inches will have 1/2” bars welded inside the duct measured 6” on center both vertical and horizontal. *See attachment

Ducts over 96 square inches will have an access port on the interior side of the SCIF wall to inspect bars.

o If access port has to be on the exterior side of the SCIF wall the port will be locked with a high security lock.

All ducts (regardless of size or what they are for) will have a non-conductive material installed inside the facility at the penetration to the SCIF.

No bars required if an IDS system is installed in Duct, Access port still required.

If ducts are completely insulated on the exterior side of the duct no non-conductive material is required Reference DCID 6/9, 3.3.4

Fire/Mass Notification Control Panel http://www.lockmasters.com/index.asp?PageAction=VIEWPROD&ProdID=49543

Fire annunciation equipment is allowed in facility as long as a High Gain Amplifier Buffer is installed

If two way communication is required in building, must be isolated in SCIF to one way only o Must notify members in facility prior to using microphone as mass notification device Microphone on the remote panel inside the SCIF is not required o Horns and strobes are required, if speakers are not

Control line for annunciation equipment must enter SCIF at single point Reference DCID 6/9, Annex E, 7.0

Walls

All exterior walls will meet requirements stated in DCID 6/9 Chapter 4.2

4.2 SCIF Criteria for Permanent Dry Wall Construction

Walls, floor and ceiling will be permanently constructed and attached to each other. To provide visual evidence of attempted entry, all construction, to include above the false ceiling and below a raised floor, must be done in such a manner as to provide visual evidence of unauthorized penetration.

o Walls will be true floor to true ceiling to include interior room walls

All gaps/holes/penetrations of the wall will be filled with a spray foam or tape/mud

If wall will not go to true ceiling a cap must be installed meeting same standards as walls

All exterior walls of each Sensitive Compartmented Information Facilities (SCIF) will be built to Sound Group 3 (STC 45) or better.

1.2.3 Sound Group 3 - STC of 45 or better.

Loud speech can be faintly heard but not understood. Normal speech is unintelligible.

o Exterior walls will be constructed to meet DCID 6/9 requirements. 57 WG/AP suggest using one layer of 530 Quiet Rock on the interior of the exterior wall, one layer of 5/8” gypsum board (of Quiet Rock) on the exterior portion of the wall and insulation in the studs between the layers.

* See attachment

Suggestion- Instead of using Quiet Rock you can use two layers of 5/8” gypsum board on the interior side of the SCIF perimeter wall, insulation between the studs and one layer of 5/8”exterior wall.

o All exterior walls will have insulation with an R value equivalent to the thickness of the wall o If carpet is to be used as a acoustic means, the carpet will be placed on the interior o Higher STC ratings, STC 50 at minimum, will be required where amplified speech will be used (Auditorium)

Wireless Technology

No wireless connections/ports will be installed in the facility

Reference DCID 6/9, Annex G, 2.5

SCIF PHOTOS

Door Seal

Door Lock

Sound Cover Generator, White/Pink Noise

½” Steel bars at air duct penetrations at 6” on center each way

Interior of STC 50 entry door with heavy duty closer, KABA- MAS CD X-09 and Balanced Magnetic Switch (BMS)

Exterior of STC 50 entry door with KABA-MAS CD X-09

Gasket seal on STC 50 entry door with KABA-MAS CD X-09

Gasket Seal at STC 50 doorframe

Lockmaster LKM 7000 with X-09

Lockmaster LKM 7000 with X-09

Beacon,Strobe,Blue

Strobe Indicating Beacon, Lens Blue, Voltage 120, Base Ring/Top Cover White, Diameter 50 Millimeters, Rated NEMA 12, IEC IP65, Rated 0.6 Joules, Includes Lamp

Grainger Item # 3XB47

Price (ea.) $144.75

Brand TELEMECANIQUE

Mfr. Model # XVPC6G6W

Ship Qty. 1

Sell Qty. (Will-Call) 1

Ship Weight (lbs.) 0.3

Catalog Page No. 333 http://www.grainger.com/Grainger/items/3XB47##

Emergency Exit/Panic Alarm Deadbolt Lock

The SirenLock™ Model 250 is a UL Listed Panic Alarm deadbolt device which restricts unauthorized use of exit doors by sounding an alarm, while providing instant egress in emergencies.

Deadbolt and deadlatch meets relatching requirements Free retrofit cover plates conceal mounting holes from 11A and 230 9 Volt Battery Operation Blaring 95db dual tone siren Selectable 2-minute alarm or constant alarm 9V battery powered and audible low battery warning Meets or exceeds UL, CFM, ADA, NYC housing requirements Changeable 2 minute alarm cutoff or manual reset.

Non-handed surface installations on single or double doors Accepts most standard size rim cylinder locks (not included)

Emergency Door Annunciater (to be used on swing in doors or in place of push to open list above)

Housing 1/8 in. Polycarbonate

Power Source 9 VDC Alkaline or 12-24 VDC Wired

Warning Horn at 1 foot 95 dB - low 105 dB - high

Relay Contacts Form C Dry 0-30 Volts AC/DC, 1 Amp

Dimensions 5.375 in. x 5.375 in. x 2 in.

137mm x 137mm x 51mm

Standby Current 10 uA

Alarm Current 200 mA

Recommended Operating Temperature

32°F to 120°F (0°C to 49°C)

Housing 1/8 in. Polycarbonate

Push to exit button

LKM7003X-09 SCIF

door lock

Adjustable Jamb Seal 599C (3 piece set 2 - 7' long & 1 - 3' long)

DSX-1048

Intelligent Controllers mult

13.56 MHz Contactless and 125 kHz Proximity Card

Readers • 6125, 6136, 6145

From the most popular proximity technologies to iCLASS®.

Provides flexible options for processing multi-technology cards and configuring the reader’s audio/visual characteristics.

Included in the U.S. General Services Administration (GSA) FIPS 201 Approved Products List.

Combine contactless card presentation with a PIN.

Scalable Architecture from 2 - 8 doors

TCP/IP Communications

Individual Intelligence

512K RAM / 512K Flash

ROM

UL 294

225+ Card and Keypad

Formats

Real Time Processing and

Communications

Integrated Power Supply and Distribution

Compatible with existing

DSX Controllers

K40