Macrotec Consulting, LLC.

9724 Mild Weather Ct. · Las Vegas, NV 89148 Phone: (702) 338-8213 · Fax: (702) 629-5677

Renovation Investigation Report Asbestos and Lead Based Paint Survey

Project Information:

Nellis Air Force Base Bldg. 10203

Report Info:

Macrotec Project # 10619 February 8, 2010

Prepared For:

Vince Bowers 99th Civil Engineering Squadron – CES/CEV Nellis AFB, NV 89191

Prepared By:

Dustin McAllister - Macrotec Consulting, LLC.

Table of Contents:

Introduction Scope of Services Site Description Sample Collection Methodology Sample Analysis Methodology Sample Assessment Recommendations Inspection Limitations

Appendix A Asbestos Assessment Appendix B Lead Assessment Appendix C Asbestos Sample Location Diagram Appendix C.1 Lead Sample Location Diagram Appendix D Asbestos Laboratory Report Appendix D.1 Lead Laboratory Report

ATTACHMENT #7

Asbestos / Lead Survey Macrotec Project # 10619 Nellis Air Force Base – Bldg. 10203 Page 2

INTRODUCTION

Macrotec Consulting performed an inspection for Asbestos-Containing Building Materials and Lead Based Paint on February 1 & 2, 2010. The inspection was conducted for the project defined as: Renovation of building 10203 at Nellis Air Force Base in Las Vegas, NV.

The intent of this inspection was to identify materials containing asbestos and lead based paint, within the subject site, that may be impacted during planned renovation activities. Macrotec’s inspection services were conducted at the request of Vince Bowers of the 99th Civil Engineering Squadron.

Dustin McAllister, a certified lead inspector, License No. NV-I-16781-1, and a Nevada Asbestos Abatement Consultant, License No.IM0961, and Jason McAllister, a Nevada Asbestos Abatement Consultant, License No. IM0901, conducted these services for Macrotec Consulting.

SCOPE OF SERVICES

Asbestos

Macrotec’s inspection services were conducted to identify the presence of any materials containing asbestos pursuant to the requirements of NAC 618.960 and in accordance with the inspection requirements of the EPA’s: 40 CFR Part 61 National Emission Standard for Hazardous Air Pollutants (NESHAP).

These regulations outline inspection and abatement requirements for materials containing asbestos, prior to renovation and/or demolition activities.

Lead

Macrotec collected paint chip samples to identify the presence and content level of lead for compliance with the Occupational Safety and Health Administration’s (OSHA) and the Environmental Protection Agencies (EPA) regulatory requirements pertaining to worker protection and waste disposal.

SITE DESCRIPTION

The subject site was the interior and exterior of a three-level (two stories and a basement) building.

Macrotec’s inspection was limited to the location within the site planned for renovation as described above.

Nellis Air Force Base – Bldg. 10203 Page 3

SAMPLE COLLECTION METHODOLOGY

An initial walk through of the subject site was conducted to identify homogeneous suspect materials containing asbestos and/or lead based paint, and their respective locations. This information was then used to develop a sample collection strategy.

Samples were collected by pre-wetting sample areas with water, then cutting or scraping the sample from the substrate with an appropriate sampling tool.

Whenever possible, samples were collected from areas previously damaged or deteriorating. To avoid potential contamination due to unknown asbestos and/or lead based paint content; no building systems, components, or structures were demolished to obtain samples of potentially hidden materials containing asbestos.

Each suspect bulk sample was sealed in its own zip lock plastic container and labeled with a unique identification number. Sampling tools were individually cleaned before and after each sample was collected to avoid sample cross contamination. Decontamination was accomplished using single use, pre-moistened cloths.

Samples were recorded on Macrotec’s chain-of-custody form. This form accompanied the samples to Triangle Enivronmental Service Center, Inc.

(TESC), located in Moseley, Virginia. The National Voluntary Laboratory Accreditation Program (NVLAP) accredits TESC for analysis of bulk building material samples for asbestos. The American Industrial Hygiene Association (AIHA) accredits Schneider Laboratories Inc. in Richmond Virginia, for analysis of paint chip samples for lead.

SAMPLE ANALYSIS METHODOLOGY

Asbestos

Suspect asbestos samples were subjected to analysis by polarized light microscopy (PLM). Bulk sample analysis was conducted in accordance with the EPA’s “Test Method for the Determination of Asbestos in Bulk Building Materials, EPA/600/R-93/116, 1993.

Lead

To determine lead content, the samples were submitted for analysis. Suspect paint chip samples were subjected to analysis in accordance with the EPA’s Method SW846-7420.

Nellis Air Force Base – Bldg. 10203 Page 4

SAMPLE ASSESSMENT

Asbestos

Macrotec’s inspection of the subject site found Thirty-Eight (38) separate suspect asbestos building materials, of which a total of Seventy-Four (74) samples were collected and submitted for analysis.

The sample results indicated that the suspect materials were “None Detected” for asbestos content.

See Appendix A for a listing of the materials, material locations, samples, sample locations and results for this project.

Lead

Macrotec collected Ninety-Four (94) paint samples of the predominate paint colors within the subject site.

The following table summarizes the painted surfaces that were found to be lead based paint (results above 5,000 parts per million), the locations where the painted surface is located, and laboratory result. Nellis AFB may have further regulations for the handling of materials with paint over 600 parts per million so those results are also included.

Painted Surface Description

Material Locations

Lab Result (Parts / Million)

Silver Metal Pipe Located on roof pipes. 1,079,850

Red Wood Fascia Located on the perimeter of the exterior of the building.

91,940

Red Metal Fascia Located on the perimeter of the exterior of the building.

4,211

Red Metal Handrail Located in the mechanical rooms in the basement.

21,844

Off White / Green Concrete Wall Located on the concrete walls in the basement.

(Including behind some sheet rock walls.)

6,910

Off White / Green Cinderblock Wall Located on the block walls in the three interior stairwells.

5,217

See Appendix B for a listing of the painted surfaces, samples, sample locations and results for this project.

Nellis Air Force Base – Bldg. 10203 Page 5

RECOMMENDATIONS

Asbestos

No asbestos containing materials were identified in this investigation. If suspect materials are found during renovation activities outside what was identified in this report, stop work immediately until further testing can be completed.

Lead

US EPA OSHA regulations require the implementation of worker protection if there is a potential that paint with lead in it will be disturbed during renovation activities. In accordance with these regulations Macrotec recommends:

Hiring an EPA Licensed Lead Consultant to develop a project specification based on this investigation and any other additional findings.

Hiring an EPA Licensed Lead Abatement Contractor to stabilize and/or remove all regulated lead painted materials.

Hiring an EPA Licensed Lead Consultant to monitor the removal activities and provide final clearance inspection reports.

INSPECTION LIMITATIONS

The information contained in this report is limited to those areas and suspect materials found to be visually accessible through reasonable means.

Macrotec conducted a non-destructive survey. No demolition of building materials was conducted to determine the presence of asbestos in wall cavities, chases or other inaccessible areas. Macrotec cannot warrant that these areas do not contain asbestos in locations other than those noted in this report, however, a good faith effort was made to conduct a comprehensive survey.

• Macrotec accepts no liability for additional materials or under reporting of asbestos materials that exist below other floor coverings.

• This report is not represented as, nor is it intended to be, an asbestos abatement scope of work or project specification.

• If suspect materials are discovered during future demolition operations, cease all general work activities which could impact the discovered suspect materials, until confirmation sampling can be conducted.

Nellis Air Force Base – Bldg. 10203 Page 6

Thank you for allowing Macrotec Consulting to assist you with your environmental consulting needs. Please contact me with any questions regarding this report at (702) 338-8213.

Appendix A

Appendix A - Asbestos Assessment

Macrotec Job #10619 - 10203 Renovation

The following table lists each of the materials suspected to contain asbestos at the subject site. For each material the sample number, location and laboratory result are listed. If the material was found to contain asbestos, the friablity and NESHAP classification is identified.

1 Mopped Roofing Beneath Stone This material is located on the roof of the building.

No Asbestos Detected

AB1 Exterior - Main Roof - Center of W side None Detected

AB2 Exterior - Main Roof - SE corner None Detected

AB3 Exterior - Main Roof - Center None Detected

2 Gray Roll Roofing on Vent This material is located on the roof of the building.

No Asbestos Detected

AB4 Exterior - Main Roof - E side, N end None Detected

3 Gray Roof Mastic on Vent This material is located on the roof of the building.

No Asbestos Detected

AB5 Exterior - Main Roof - E side, N end None Detected

4 Silver Paint on Pipe This material is located on the roof of the building.

No Asbestos Detected

AB6 Exterior - Main Roof - Center of E side None Detected

5 Gray Roof Mastic on Pipe This material is located on the roof of the building.

No Asbestos Detected

AB7 Exterior - Main Roof - Center of W side None Detected

6 Gray Roof Mastic on Roof Perimeter This material is located on the roof of the building.

No Asbestos Detected

AB8 Exterior - Main Roof - SW corner None Detected

7 Exterior Stucco This material is located on the exterior walls of the building.

No Asbestos Detected

AB9 Exterior - S Side - W end None Detected

Asbestos Survey

Bldg. 10203

Macrotec Job #10619

Macrotec Job #10619 - 10203 Renovation

AB10 Exterior - S Side - Center None Detected

AB11 Exterior - S Side - Adj. W overhang None Detected

AB12 Exterior - S Side - E end None Detected

AB13 Exterior - E Side - S end, adj. stairs None Detected

AB14 Exterior - N Side - Center None Detected

AB15 Exterior - W Side - Center None Detected

8 Beige Roof Seam Mastic This material is located on the three overhang roofs.

No Asbestos Detected

AB16 Exterior - SW Overhang - NE corner None Detected

9 Brown Asphalt Roll Roofing This material is located on the three overhang roofs.

No Asbestos Detected

AB17 Exterior - SW Overhang - NE corner None Detected

10 White Mud on HVAC Duct Seam This material is located on the ducts on the east and west sides of the building.

No Asbestos Detected

AB18 Exterior - W Side - N end None Detected

11 Gray Mastic on HVAC Duct Seam This material is located on the ducts on the south side of the building.

No Asbestos Detected

AB19 Exterior - S Side - W end None Detected

12 Brown Asphalt Roof Shingle This material is located on the roof of the covered patio, south of the building.

No Asbestos Detected

AB20 Exterior - Covered Patio - NW corner None Detected

13 Black Tar Paper Beneath Shingles This material is located on the roof of the covered patio, south of the building.

No Asbestos Detected

AB21 Exterior - Covered Patio - NW corner None Detected

14 Sheet Rock, Mud & Tape This material is the component of the walls and ceilings in the first floor of the building.

No Asbestos Detected

AB22 1st Floor - Lav 1 - SE corner None Detected

AB23 1st Floor - N Hall - Adj. center stairwell None Detected

AB24 1st Floor - Room 21 - SW corner None Detected

Asbestos Survey

Bldg. 10203

Macrotec Job #10619

15 Spray Texture on Walls & Ceilings This material is on the walls and ceilings in the first floor of the building.

No Asbestos Detected

AB25 1st Floor - Room 2 - S wall None Detected

AB26 1st Floor - W Hall - NW corner None Detected

AB27 1st Floor - Room 4 - N wall None Detected

AB28 1st Floor - Room 7 - E wall None Detected

AB29 1st Floor - Room 14 - N wall None Detected

AB30 1st Floor - E Stairwell - Adj. 2nd floor None Detected

AB31 1st Floor - Room 20 - E wall None Detected

16 Yellow Mastic Behind FRP This material is on the walls of the lavatories.

No Asbestos Detected

AB32 1st Floor - Lav 1 - W wall None Detected

17 Beige Mastic Behind 4" Base Cove This material is at the base of the walls within the building.

No Asbestos Detected

AB33 1st Floor - Room 1 - S wall None Detected

18 12x12 Floor Tile - White w/ Gray Streaks This material is on the floors throughout the building.

No Asbestos Detected

AB34 1st Floor - Room 2 - Center of E wall None Detected

19 Yellow Mastic Beneath 12x12 Floor Tile This material is on the floors throughout the building.

No Asbestos Detected

AB35 1st Floor - Room 2 - Center of E wall None Detected

20 12x12 Floor Tile - White w/ Beige Streaks This material is in various locations on the floors throughout the building.

No Asbestos Detected

AB36 1st Floor - Room 2 - Center of E wall None Detected

21 Gray Tile on Vertical Part of Stairs This material is on the stairs on the interior of the building.

No Asbestos Detected

AB37 1st Floor - W Stairwell - Adj. 2nd floor None Detected

Asbestos Survey

Bldg. 10203

Macrotec Job #10619

22 Yellow Mastic Beneath Rubber Stair This material is on the stairs on the interior of the building.

No Asbestos Detected

AB38 1st Floor - W Stairwell - Adj. 2nd floor None Detected

23 Black Mastic Behind Mirror This material is on the walls in the lavatories throughout the building.

No Asbestos Detected

AB39 1st Floor - Lav 4 - W wall None Detected

24 Yellow Mastic Behind Sign This material is behind various signs throughout the building.

No Asbestos Detected

AB40 1st Floor - N Hall - Adj. room 6 None Detected

25 Beige Mastic Beneath Shelf This material is in the hall of the first floor.

No Asbestos Detected

AB41 1st Floor - N Hall - Adj. room 6 None Detected

26 Black Window Putty This material is in the hall of the first floor.

No Asbestos Detected

AB42 1st Floor - N Hall - Adj. room 6 None Detected

27 Yellow Mastic Beneath Carpet This material is in the comm closet of room 11 of the first floor.

No Asbestos Detected

AB43 1st Floor - Room 11 - Comm closet None Detected

28 White Window Putty This material is in room 11 of the first floor.

No Asbestos Detected

AB44 1st Floor - Room 11 - Doorway None Detected

29 Sheet Rock, Mud & Tape This material is the component of the walls and ceilings in the 2nd floor.

No Asbestos Detected

AB45 2nd Floor - W Hall - SE corner None Detected

AB46 2nd Floor - Room 5 - S wall, adj. window None Detected

AB47 2nd Floor - Room 10 - E wall None Detected

Asbestos Survey

Bldg. 10203

Macrotec Job #10619

30 Spray Texture on Walls & Ceililngs This material is on the walls and ceilings in the 2nd floor.

No Asbestos Detected

AB48 2nd Floor - Room 2 - E wall None Detected

AB49 2nd Floor - Lav 1 - Center None Detected

AB50 2nd Floor - Room 3 - W wall None Detected

AB51 2nd Floor - Center Stairwell - Center None Detected

AB52 2nd Floor - Room 7 - N wall None Detected

AB53 2nd Floor - Room 8 - NE corner None Detected

AB54 2nd Floor - Room 9 - Center None Detected

31 Black Mastic Behind Mirror This material is on the walls in the lavatories throughout the building.

No Asbestos Detected

AB55 2nd Floor - Lav 2 - Center None Detected

32 Textured Floor Paint This material is on the floor of lavatory 3 on the 2nd floor.

No Asbestos Detected

AB56 2nd Floor - Lav 3 - Center None Detected

33 White Floor Fill Beneath Floor Tile This material is on various locations on the floors throughout the building.

No Asbestos Detected

AB57 2nd Floor - Room 8 - Center None Detected

34 Sheet Rock, Mud & Tape This material is the component of the walls and ceilings in the basement.

No Asbestos Detected

AB58 Basement - Center Stairwell - Adj. N hall None Detected

AB59 Basement - E Hall - Adj. room 20 None Detected

AB60 Basement - Room 3 - S end None Detected

35 Spray Texture on Walls & Ceilings This material is on the walls and ceilings in the basement.

No Asbestos Detected

AB61 Basement - Room 1 - N wall None Detected

AB62 Basement - Room 6 - N, center None Detected

AB63 Basement - Room 15 - E wall None Detected

AB64 Basement - E Stairwell - Adj. 1st Floor None Detected

AB65 Basement - Room 21 - E wall None Detected

Asbestos Survey

Bldg. 10203

Macrotec Job #10619

36 Spray Texture on Block and Concrete This material is on the walls in the basement and stairwells.

No Asbestos Detected

AB66 Basement - Room 3 - W wall None Detected

AB67 Basement - Room 5 - Center None Detected

AB68 Basement - Room 14 - E wall None Detected

AB69 Basement - Center Stairwell - Adj. N hall None Detected

AB70 Basement - Room 22 - E wall None Detected

AB71 1st Floor - W Stairwell - Adj. W hall None Detected

AB72 2nd Floor - E Stairwell - Adj. stairs None Detected

37 White Debris This material is in the south end of the basement hall.

No Asbestos Detected

AB73 Basement - E Hall - S end None Detected

38 Gray Mastic on HVAC Duct Seam This material is in various rooms in the basement.

No Asbestos Detected

AB74 Basement - Room 4 - W side None Detected

Asbestos Survey

Bldg. 10203

Macrotec Job #10619

Appendix B

Appendix B - Lead Assessment

Macrotec Job #10619 - 10203 Renovation

The following table lists each of the painted surfaces suspected to contain lead at the subject site. For each painted surface, the sample number, location and laboratory result are listed.

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L1 Exterior - N Side - Center Below Reportable LimitBeige Stucco Name Slab

L2 Exterior - N Side - Center Below Reportable LimitRed Metal Hand Rail

L3 Exterior - N Side - Entrance Below Reportable LimitBrown Metal Door

L4 Exterior - N Side - Entrance Below Reportable LimitBrown Metal Door Frame

L5 Exterior - N Side - NW corner Below Reportable LimitBeige Concrete Base

L6 Exterior - N Side - NW corner Below Reportable LimitBeige Stucco Wall

L7 Exterior - Roof - Center 1,079,850Silver Metal Pipe

L8 Exterior - Roof - SW corner 91,940Red Wood Fascia

L9 Exterior - Roof - SW corner 4,211Red Metal Fascia

L10 Exterior - W Side - SW corner Below Reportable LimitBeige Metal HVAC

L11 Exterior - S End - HVAC Area - Door 150Red Metal Gate

L12 Exterior - S End - HVAC Area - Center Below Reportable LimitPurple Metal Heater

L13 Exterior - S End - HVAC Area - Center Below Reportable LimitGreen Metal Heater

L14 Exterior - S End - HVAC Area - Center 101Yellow Metal Gas Pipe

L15 Exterior - S End - HVAC Area - Center Below Reportable LimitBeige Metal Electrical Box

L16 Exterior - S End - HVAC Area - HVAC wall

Below Reportable LimitBrown Cinderblock Wall

L17 Exterior - S End - Center Below Reportable LimitBeige Stucco Wall

L18 Exterior - Covered Patio - N end Below Reportable LimitBeige Cinderblock Wall

Lead Paint Survey

Bldg. 10203

Macrotec Job #10619

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L19 Exterior - Covered Patio - Center Below Reportable LimitBeige Wood Ceiling

L20 Exterior - Covered Patio - W side Below Reportable LimitBeige Wood Column

L21 Exterior - S End - E corner Below Reportable LimitBeige Metal Door

L22 Exterior - S End - E corner Below Reportable LimitBeige Metal Door Frame

L23 Exterior - S End - E side 243Beige Metal Pole

L24 Exterior - S End - E side Below Reportable LimitGray Metal HVAC Seams

L25 Exterior - S End - E stairs Below Reportable LimitRed Metal Stair Stand

L26 Exterior - S End - E stairs Below Reportable LimitRed Metal Stair Hand Rail

L27 Exterior - E End - SE corner Below Reportable LimitRed Metal Hand Rail

L28 Exterior - E End - NE corner Below Reportable LimitBeige Metal HVAC

L29 Basement - Room 2 - Adj. door Below Reportable LimitOff-white Concrete Column

L30 Basement - Room 1 - S wall Below Reportable LimitOff-white Concrete Wall

L31 Basement - Room 2 - N wall Below Reportable LimitOff-white Sheet Rock Wall

L32 Basement - W Hall - W wall Below Reportable LimitGray Metal Door

L33 Basement - W Hall - W wall Below Reportable LimitGray Metal Door Frame

L34 Basement - Room 3 - N wall 463Off-white Cinderblock Wall

L35 Basement - Room 3a - Doorway Below Reportable LimitOff-white Wood Door Frame

L36 Basement - Room 4 - Center 21,844Red Metal Handrail

L37 Basement - Room 5 - Door to W hall Below Reportable LimitBrown Metal Door

L38 Basement - Room 5 - Closet Below Reportable LimitBrown Metal Door Frame

L39 Basement - Room 12 - Adj. door 14,575Red Metal Handrail

L40 Basement - Room 6 - Door Below Reportable LimitBrown Metal Window / Door Frame

L41 Basement - Room 6 - Door Below Reportable LimitBrown Metal Window / Door

Lead Paint Survey

Bldg. 10203

Macrotec Job #10619

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L42 Basement - N Hall - Adj. room 6 35Off-white Cinderblock Wall

L43 Basement - Room 14 - E end Below Reportable LimitOff-white Concrete Platform

L44 Basement - E Stairwell - Adj. E hallway 5,744Off-white / Green Concrete Wall

L45 Basement - Room 19 - Adj. door 18,414Red Metal Handrail

L46 Basement - Room 23 - N wall Below Reportable LimitOff-white Sheet Rock Wall

L47 Basement - E Hall - S end Below Reportable LimitOff-white Metal Panel

L48 Basement - Room 14 - S wall 6,910Off-white Concrete Wall

L49 Basement - Room 16 - W end Below Reportable LimitWhite Metal Duct

L50 2nd Floor - W Hall - Door to exterior Below Reportable LimitBrown Metal Door Frame

L51 2nd Floor - W Hall - Door to lav 1 Below Reportable LimitBrown Metal Door

L52 2nd Floor - Room 2 - E wall Below Reportable LimitOff-white Sheet Rock Wall

L53 2nd Floor - Lav 1 - W wall Below Reportable LimitOff-white FRP wall

L54 2nd Floor - Lav 1 - N wall Below Reportable LimitOff-white - Ceramic Base Cove

L55 2nd Floor - Lav 1 - Center Below Reportable LimitTan Ceramic Floor Tile

L56 2nd Floor - W Stairwell - Adj. W hall 5,217Off-white / Green Cinderblock

L57 2nd Floor - Room 3 - Closet door Below Reportable LimitGray Metal Door / Door Frame

L58 2nd Floor - Room 3 - Center Below Reportable LimitWhite Wood Shelf

L59 2nd Floor - Lav 2 - Door Below Reportable LimitBrown Metal Door Frame

L60 2nd Floor - Center Stairwell - Center 2,271Off-white / Green Cinderblock Wall

L61 2nd Floor - Room 6 - Door to center stairs

Below Reportable LimitBrown Metal Door

L62 2nd Floor - Room 6 - W wall Below Reportable LimitOff-white Sheet Rock Wall

L63 2nd Floor - Lav 3 - Center Below Reportable LimitGray Floor Coating

L64 2nd Floor - Room 6 - SE corner Below Reportable LimitOff-white Wood Coat Rack

Lead Paint Survey

Bldg. 10203

Macrotec Job #10619

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L65 2nd Floor - W Stairwell - Center 4,295Off-white / Green Cinderblock Wall

L66 2nd Floor - Lav 4 - Center Below Reportable LimitGray Metal Stall Divider

L67 2nd Floor - E Hall - Center Below Reportable LimitOff-white Sheet Rock Wall

L68 2nd Floor - E Hall - Door to exterior Below Reportable LimitBrown Metal Door

L69 2nd Floor - E Hall - Door to lav 4 Below Reportable LimitBrown Metal Door Frame

L70 1st Floor - Room 18 - W wall Below Reportable LimitOff-white Sheet Rock Wall

L71 1st Floor - Lav 7 - Adj. door Below Reportable LimitWhite Ceramic Base

L72 1st Floor - Lav 8 - Adj. door Below Reportable LimitTan Ceramic Floor Tile

L73 1st Floor - E Hall - Door to exterior Below Reportable LimitBrown Metal Door

L74 1st Floor - E Hall - Door to lav 6 Below Reportable LimitBrown Metal Door Frame

L75 1st Floor - Room 16 - Closet 688Off-white Cinderblock Wall

L76 1st Floor - Room 7 - S wall Below Reportable LimitOff-white Sheet Rock Wall

L77 1st Floor - Center Hall - Door to room 5 Below Reportable LimitBrown Metal Door Frame

L78 1st Floor - Center Stairwell - Door to hall Below Reportable LimitBrown Metal Door

L79 1st Floor - Room 15 - S wall Below Reportable LimitWhite Wood Cabinet

L80 1st Floor - Room 9 - Door to room 11 Below Reportable LimitWhite Wood Door / Window Frame

L81 1st Floor - Center Stairwell - Center 3,747Off-white / Green Cinderblock Wall

L82 1st Floor - Center Stairwell - Center Below Reportable LimitGray Wood Stair

L83 1st Floor - Room 6 - Adj. door to hall Below Reportable LimitOff-white Ceramic Floor Tile

L84 1st Floor - Room 3 - Center Below Reportable LimitOff-white Wood Shelf

L85 1st Floor - W Stairwell - Center 2,636Off-white / Green Cinderblock Wall

L86 1st Floor - Lav 1 - Center Below Reportable LimitOff-white FRP Wall

L87 1st Floor - W Hall - Center Below Reportable LimitOff-white Sheet Rock Ceiling

Lead Paint Survey

Bldg. 10203

Macrotec Job #10619

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L88 1st Floor - W Hall - Door to lav 1 Below Reportable LimitBrown Metal Door

L89 1st Floor - W Hall - Door to exterior Below Reportable LimitBrown Metal Door Frame

L90 Basement - Room 8 - E end 137Gray Concrete Floor

L91A 1st Floor - E Stairwell - Bottom Below Reportable LimitBlack Wood Stair

L91 1st Floor - Center Stairwell - Bottom Below Reportable LimitWhite Wood Stair

L92 1st Floor - Room 15 - N wall Below Reportable LimitOff-white Metal Pole

L93 1st Floor - Room 6 - SE corner Below Reportable LimitRed Metal Box

Lead Paint Survey

Bldg. 10203

Macrotec Job #10619

Appendix C

Asbestos & Lead Based Paint Survey

Nellis AFB, Bldg. 10203

Macrotec Project # 10619

Appendix C

* Diagram Not Drawn To Scale

Sample Location Diagram N

AB3

AB1

AB2

AB4

Exterior

AB5

AB6

AB7

Asbestos

Main Roof

Covered Patio

AB8

AB9

AB10

AB11

AB12

AB13

AB14

AB15

AB16

AB17

AB18

AB19

AB20

AB21

Macrotec Project # 10619

Appendix C

* Diagram Not Drawn To Scale

Sample Location Diagram N

Basement

AB58

Room

Room

Room

Room

Room

Room

Room

Room

E Hall

W Hall

N

H a l l

E

SW

W

SW

Cen

SW

Asbestos

Rm 9

Room

Room

Room

Room

Room

Room

Room 3a

Room

Room

Room

Room

Room

Room

Room

Room

AB59

AB60

AB61

AB62

AB63

AB64

AB65

AB66

AB67

AB68

AB69

AB70

AB73

AB74

Macrotec Project # 10619

Appendix C

* Diagram Not Drawn To Scale

Sample Location Diagram N

AB22

1st Floor

Room

Room

Lav

Room

Room

Lav

Lav 3

Room

Room

Room

Lav

Room

E Hall

W Hall

N

H a l l

E

SW

W

SW

Cen

SW

Asbestos

Lav 4

Rm 7

Rm 8

Rm 10

Rm 12

Rm 13Rm 11

Rm 9

Lav 5

Room

Room

Lav

Lav

Room

Room

Room

Room

Room

AB23

AB24

AB25

AB26

AB27

AB28

AB29

AB30

AB31

AB32

AB33

AB34

AB35

AB36

AB37

AB38

AB39

AB40

AB41

AB42

AB43

AB44

AB71

Macrotec Project # 10619

Appendix C

* Diagram Not Drawn To Scale

Sample Location Diagram N

AB45

2nd Floor

Room

Room

Lav

Room

Room

Lav

Lav

Room

Room

Room

Room

Lav

Room

Room

E Hall

W Hall

N

H a l l

E

SW

W

SW

Cen

SW

Asbestos

AB46

AB47

AB48

AB49

AB50

AB51

AB52

AB53

AB54

AB55

AB56

AB57

AB72

Appendix C.1

Macrotec Project # 10619

Appendix C.1

* Diagram Not Drawn To Scale

Sample Location Diagram N

Exterior

Lead Based Paint

Main Roof

Covered Patio

L1

L2

L3

L4

L5

L6

L7

L8

L9

L10

L11

L12

L13

L14

L15

L16

L17

L18

L19

L20

L21

L22

L23

L24

L25

L26

L27

L28

Macrotec Project # 10619

Appendix C.1

* Diagram Not Drawn To Scale

Sample Location Diagram N

Basement

Room

Room

Room

Room

Room

Room

Room

Room

E Hall

W Hall

N

H a l l

E

SW

W

SW

Cen

SW

Lead Based Paint

Rm 9

Room

Room

Room

Room

Room

Room

Room 3a

Room

Room

Room

Room

Room

Room

Room

Room

L90

L91

L29

L30

L31

L32

L33

L34

L35

L36

L37

L38

L39

L40

L41

L42

L43

L44

L45

L46

L47

L48

L49

Macrotec Project # 10619

Appendix C.1

* Diagram Not Drawn To Scale

Sample Location Diagram N

1st Floor

L70

Room

Room

Lav

Room

Room

Lav

Lav 3

Room

Room

Room

Lav

Room

E Hall

W Hall

N

H a l l

E

SW

W

SW

Cen

SW

Lead Based Paint

Lav 4

Rm 7

Rm 8

Rm 10

Rm 12

Rm 13Rm 11

Rm 9

Lav 5

Room

Room

Lav

Lav

Room

Room

Room

Room

Room

L71

L72

L73

L74

L75

L76

L77

L78

L79

L80

L81

L82

L83

L84

L85

L86

L87

L88

L89

L91A

L92

L93

Macrotec Project # 10619

Appendix C.1

* Diagram Not Drawn To Scale

Sample Location Diagram N

2nd Floor

Room

Room

Lav

Room

Room

Lav

Lav

Room

Room

Room

Room

Lav

Room

Room

E Hall

W Hall

N

H a l l

E

SW

W

SW

Cen

SW

Lead Based Paint

L50

L51

L52

L53

L54

L55

L56

L57

L58

L59

L60

L61

L62

L63

L64

L65

L66

L67

L68

L69

Appendix D

Appendix D.1

Appendix E