Macrotec Consulting, LLC.

9724 Mild Weather Ct. · Las Vegas, NV 89148 Phone: (702) 338-8213 · Fax: (702) 629-5677

Renovation Investigation Report Asbestos and Lead Based Paint Survey

Project Information:

Nellis Air Force Base Bldg. 10204 Renovation Survey

Report Info:

Macrotec Project # 10615 February 8, 2010

Prepared For:

Vince Bowers 99th Civil Engineering Squadron – CES/CEV Nellis AFB, NV 89191

Prepared By:

Dustin McAllister - Macrotec Consulting, LLC.

Table of Contents:

Introduction Scope of Services Site Description Sample Collection Methodology Sample Analysis Methodology Sample Assessment Recommendations Inspection Limitations

Appendix A Asbestos Assessment Appendix B Lead Assessment Appendix C Sample Location Diagram Appendix D Laboratory Report Appendix E Certifications

FA4861-10-B-A045

ATTACHMENT #8 Page 1 of 33

Asbestos / Lead Survey Macrotec Project # 10615 Nellis Air Force Base – Bldg. 10204 Page 2

INTRODUCTION

Macrotec Consulting performed an inspection for Asbestos-Containing Building Materials and Lead Based Paint on January 29, 2010. The inspection was conducted for the project defined as: Renovation of building 10204 at Nellis Air Force Base in North Las Vegas, NV.

The intent of this inspection was to identify materials containing asbestos and lead based paint, within the subject site, that may be impacted during planned renovation activities. Macrotec’s inspection services were conducted at the request of Vince Bowers of the 99th Civil Engineering Squadron.

Dustin McAllister, a certified lead inspector, License No. NV-I-16781-1, and a Nevada Asbestos Abatement Consultant, License No.IM0961, conducted these services for Macrotec Consulting.

SCOPE OF SERVICES

Asbestos

Macrotec’s inspection services were conducted to identify the presence of any materials containing asbestos pursuant to the requirements of NAC 618.960 and in accordance with the inspection requirements of the EPA’s: 40 CFR Part 61 National Emission Standard for Hazardous Air Pollutants (NESHAP).

These regulations outline inspection and abatement requirements for materials containing asbestos, prior to renovation and/or demolition activities.

Lead

Macrotec collected paint chip samples to identify the presence and content level of lead for compliance with the Occupational Safety and Health Administration’s (OSHA) and the Environmental Protection Agencies (EPA) regulatory requirements pertaining to worker protection and waste disposal.

SITE DESCRIPTION

The subject site was a one story theater.

Macrotec’s inspection was limited to the location within the site planned for renovation as described above.

ATTACHMENT #8 Page 2 of 33

Nellis Air Force Base – Bldg. 10204 Page 3

SAMPLE COLLECTION METHODOLOGY

An initial walk through of the subject site was conducted to identify homogeneous suspect materials containing asbestos and/or lead based paint, and their respective locations. This information was then used to develop a sample collection strategy.

Samples were collected by pre-wetting sample areas with water, then cutting or scraping the sample from the substrate with an appropriate sampling tool.

Whenever possible, samples were collected from areas previously damaged or deteriorating. To avoid potential contamination due to unknown asbestos and/or lead based paint content; no building systems, components, or structures were demolished to obtain samples of potentially hidden materials containing asbestos.

Each suspect bulk sample was sealed in its own zip lock plastic container and labeled with a unique identification number. Sampling tools were individually cleaned before and after each sample was collected to avoid sample cross contamination. Decontamination was accomplished using single use, pre-moistened cloths.

Samples were recorded on Macrotec’s chain-of-custody form. This form accompanied the samples to Triangle Enivronmental Service Center, Inc.

(TESC), located in Moseley, Virginia. The National Voluntary Laboratory Accreditation Program (NVLAP) accredits TESC for analysis of bulk building material samples for asbestos. The American Industrial Hygiene Association (AIHA) accredits Schneider Laboratories Inc. in Richmond Virginia, for analysis of paint chip samples for lead.

SAMPLE ANALYSIS METHODOLOGY

Asbestos

Suspect asbestos samples were subjected to analysis by polarized light microscopy (PLM). Bulk sample analysis was conducted in accordance with the EPA’s “Test Method for the Determination of Asbestos in Bulk Building Materials, EPA/600/R-93/116, 1993.

Lead

To determine lead content, the samples were submitted for analysis. Suspect paint chip samples were subjected to analysis in accordance with the EPA’s Method SW846-7420.

ATTACHMENT #8 Page 3 of 33

Nellis Air Force Base – Bldg. 10204 Page 4

SAMPLE ASSESSMENT

Asbestos

Macrotec’s inspection of the subject site found Fourteen (14) separate suspect asbestos building materials, of which a total of Thirty (30) samples were collected and submitted for analysis.

The following table summarizes the materials that were found to be asbestos containing, the locations where the material is located, the material’s friability and its NESHAP classification.

Material Number

Material Description

Material Locations

Material Friability

NESHAP

22 Penetration Mastic Beneath Foam

This material is on the penetrations located beneath the foam on the roof

Non- Friable

Category I

See Appendix A for a listing of the materials, material locations, samples, sample locations and results for this project.

Lead

Macrotec collected Twenty-Eight (28) paint samples of the predominate paint colors within the subject site.

The following table summarizes the painted surfaces that were found to be lead based paint (results above 5,000 parts per million), the locations where the painted surface is located, and laboratory result. Nellis AFB may have further regulations for the handling of materials with paint over 600 parts per million so those results are also included.

Painted Surface Description

Material Locations

Lab Result (Parts / Million)

Brown Metal Pipe Located in the Theater 7,240

Gray Metal Railing Located in the north end of the Theater 4,296

Gray Concrete Floor Located on the Theater 1,240

White Wood Stage Trim Located on the stage of the Theater 2,142

White Metal HVAC Duct Located on the ceiling throughout the building 1,778

Brown Metal Theater Chairs Located in the Theater 33,086

Red Wood Overhang Located adjacent the roof on the exterior 83,360

Category I nonfriable asbestos-containing material means asbestos containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1% asbestos as determined by Polarized Light Microscopy (PLM)

ATTACHMENT #8 Page 4 of 33

Nellis Air Force Base – Bldg. 10204 Page 5

White Metal Large Vent Located on the roof of the building 1,360

See Appendix B for a listing of the painted surfaces, samples, sample locations and results for this project.

RECOMMENDATIONS

Asbestos

US EPA and Nevada Department of Industrial Relations regulations require the removal of all regulated asbestos-containing materials (RACM) prior to any renovation or demolition that could impact or disturb RACM. In accordance with these regulations Macrotec recommends:

Hiring a Certified Asbestos Consultant to develop a project specification based on this investigation and any other additional findings.

Hiring a Nevada licensed Asbestos Abatement Contractor to remove all asbestos materials, which are either regulated or may become regulated during the course of renovation and/or demolition activities.

Hiring a Certified Asbestos Consultant to monitor the removal activities and to provide final clearance inspection reports.

Lead

US EPA OSHA regulations require the implementation of worker protection if there is a potential that paint with lead in it will be disturbed during demolition activities. In accordance with these regulations Macrotec recommends:

Hiring an EPA Licensed Lead Consultant to develop a project specification based on this investigation and any other additional findings.

Hiring an EPA Licensed Lead Abatement Contractor to stabilize and/or remove all regulated lead painted materials.

Hiring an EPA Licensed Lead Consultant to monitor the removal activities and provide final clearance inspection reports.

ATTACHMENT #8 Page 5 of 33

Nellis Air Force Base – Bldg. 10204 Page 6

INSPECTION LIMITATIONS

The information contained in this report is limited to those areas and suspect materials found to be visually accessible through reasonable means.

Macrotec conducted a non-destructive survey. No demolition of building materials was conducted to determine the presence of asbestos in wall cavities, chases or other inaccessible areas. Macrotec cannot warrant that these areas do not contain asbestos in locations other than those noted in this report, however, a good faith effort was made to conduct a comprehensive survey.

• Macrotec accepts no liability for additional materials or under reporting of asbestos materials that exist below other floor coverings.

• This report is not represented as, nor is it intended to be, an asbestos abatement scope of work or project specification.

• If suspect materials are discovered during future demolition operations, cease all general work activities which could impact the discovered suspect materials, until confirmation sampling can be conducted.

Thank you for allowing Macrotec Consulting to assist you with your environmental consulting needs. Please contact me with any questions regarding this report at (702) 338-8213.

ATTACHMENT #8 Page 6 of 33

Appendix A

ATTACHMENT #8 Page 7 of 33

Appendix A - Asbestos Assessment

Macrotec Job #10615 - WO #14278 - Bldg. 10204

The following table lists each of the materials suspected to contain asbestos at the subject site. For each material the sample number, location and laboratory result are listed. If the material was found to contain asbestos, the friablity and NESHAP classification is identified.

1 Sheet Rock Mud & Tape - Textured This material is located on the walls of the building.

AB1 Equipment Room - NW Corner None Detected

AB2 Theater - Adj. SW Door None Detected

AB3 Media Room - NW Corner None Detected

2 Texture on Sheet Rock This material is located on the walls of the building.

AB4 Men's Room - W Wall None Detected

AB5 Office - N Wall None Detected

AB6 Theater - NW Corner None Detected

AB7 Theater - SE Corner None Detected

AB8 Comm. Room - S Wall None Detected

3 Acoustic Ceiling Material This material is located on the ceiling of the theater.

AB9 Theater - SW Corner None Detected

AB10 Theater - SE Corner None Detected

AB11 Theater - Center None Detected

AB12 Theater - NW Corner None Detected

AB13 Theater - NE Corner None Detected

4 Yellow Mastic Beneath Carpet This material is located beneath the carpet in the office

AB14 Office - NW Corner None Detected

5 12X12 Tan Floor Tile This material is located on the floor in the north end of theater, media room, men's room, and handicap room.

AB15 Theater - Adj. Office None Detected

Asbestos Survey

Bldg. 10204

Macrotec Job #10615

ATTACHMENT #8 Page 8 of 33

Macrotec Job #10615 - WO #14278 - Bldg. 10204

6 Black Mastic Beneath Floor Tile This material is located on the floor in the north end of theater, media room, men's room, and handicap room.

AB16 Theater - Adj. Office None Detected

7 Yellow Mastic Beneath Floor Tile This material is located on the floor in the north end of theater, media room, men's room, and handicap room.

AB17 Media Room - NW Corner None Detected

8 White Base Cove Mastic This material is located behind the base cove in various areas of the building

AB18 Office - Adj. Door None Detected

9 Yellow Base Cove Mastic This material is located behind the base cove in various areas of the building

AB19 Theater - Adj. Media Room None Detected

10 Yellow/Black Carpet Mastic This material is located beneath the carpet on the stage in the Theater

AB20 Theater - On Stage None Detected

11 Stucco This material is located on the walls in the exterior

AB21 Exterior - E Wall None Detected

AB22 Exterior - SE Corner None Detected

AB23 Exterior - SW Corner None Detected

AB24 Exterior - NW Corner None Detected

AB25 Exterior - NE Corner None Detected

12 Penetration Mastic Beneath Foam This material is located on the penetration mastic of the roof

AB26 Exterior - Roof - NE Corner 10% Chrysotile

Asbestos Survey

Bldg. 10204

Macrotec Job #10615

ATTACHMENT #8 Page 9 of 33

13 Asphalt Coating Above Foam This material is located on the roof

AB27 Exterior - Roof - S End None Detected

AB28 Exterior - Roof - Center None Detected

AB29 Exterior - Roof - N End None Detected

14 White Penetration Mastic Above Foam This material is located on the roof

AB30 Exterior - Roof - N Side None Detected

Asbestos Survey

Bldg. 10204

Macrotec Job #10615

ATTACHMENT #8 Page 10 of 33

Appendix B

ATTACHMENT #8 Page 11 of 33

Appendix B - Lead Assessment

Macrotec Job #10615 - WO #14278 - Bldg. 10204

The following table lists each of the painted surfaces suspected to contain lead at the subject site. For each painted surface, the sample number, location and laboratory result are listed.

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L1 Equipment Room - S Wall Below Reportable LimitBeige Sheet Rock Wall

L2 Theater - E Wall Below Reportable LimitBeige Sheet Rock Wall

L3 Handicap Bathroom - W Wall Below Reportable LimitBeige Sheet Rock Wall

L4 Equipment Room - E Wall Below Reportable LimitRed Metal Pipe

L5 Theater - Center - East 7,240Brown Metal Pole

L6 Theater - SE Door Below Reportable LimitBrown Metal Door Frame

L7 Theater - SE Door Below Reportable LimitBrown Metal Door

L8 Theater - NW Corner Below Reportable LimitWhite Metal Electric Box

L9 Theater - N End 4,296Gray Metal Railing

L10 Theater - N End 1,240Gray Concrete Floor

L11 Theater - N End Below Reportable LimitYellow Concrete Stair Ends

L12 Theater - Door to Office Below Reportable LimitBrown Wood Door Frame

L13 Theater - Door to Men's Room 527Brown Wood Door

L14 Theater - SE Corner 527Brown Metal Stage Trim - Top

L15 Theater - SE Corner 2,142White Wood Stage Trim - Bottom

L16 Theater - SE Corner 1,778White Metal HVAC Duct

L17 Theater - SE Corner 33,086Brown Metal Theater Chairs

L18 Exterior - SW Corner Below Reportable LimitBrown Metal Door

Lead Paint Survey

Bldg. 10204

Macrotec Job #10615

ATTACHMENT #8 Page 12 of 33

Appendix B

Sample

Painted Surface Description

Sample Location Description

Lab Result (Parts per Million)

L19 Exterior - SW Corner Below Reportable LimitBrown Metal Door Frame

L20 Exterior - SW Corner 83,360Red Wood Overhang

L21 Exterior - SW Corner Below Reportable LimitBrown Concrete Base

L22 Exterior - E End Below Reportable LimitBrown Stucco Wall

L23 Exterior - SE Corner Below Reportable LimitRed Metal Handrail

L24 Exterior - Roof - SE Corner Below Reportable LimitGray Metal HVAC

L25 Exterior - Roof - Center 1,360White Metal Large Vent

L26 Exterior - Roof - NE Corner 44White Metal Small Vent

L27 Exterior - Roof - Center Below Reportable LimitBeige Metal Roof Trim

L28 Exterior - Roof - NE Corner Below Reportable LimitRed Metal Facia

Lead Paint Survey

Bldg. 10204

Macrotec Job #10615

ATTACHMENT #8 Page 13 of 33

Appendix C

ATTACHMENT #8 Page 14 of 33

Asbestos & Lead Survey

NAFB Bldg. 10204

Macrotec Project # 10615

Appendix A

Sample Location Diagram N

AB1

AB2

AB3

AB4

L1

* Diagram Not Drawn To Scale

AB5

AB6

AB7

AB8

AB9

AB10

AB11

AB12

AB14

AB15

AB16

L2

L3

L4

L5

L7

L8

L9

L10

L11

L12

L13

L14

L15

L16

L17

L6

Comm.

Room

Equipment Room

Stage

Theater

Office Media Room

Men’s Room

Handi-cap

Room

AB13

AB17

AB19

AB18

AB20

ATTACHMENT #8 Page 15 of 33

Asbestos & Lead Survey

NAFB Bldg. 10204

Macrotec Project # 10615

Appendix A

Sample Location Diagram N

* Diagram Not Drawn To Scale

AB21

AB22AB23

AB24

AB25

AB26

AB27

AB28

AB29

AB30

L18

L19

L20

L21

L22

L23

L24

L25

L26

L27

L28

Roof

ATTACHMENT #8 Page 16 of 33

Appendix D

ATTACHMENT #8 Page 17 of 33

ATTACHMENT #8 Page 18 of 33

ATTACHMENT #8 Page 19 of 33

ATTACHMENT #8 Page 20 of 33

ATTACHMENT #8 Page 21 of 33

ATTACHMENT #8 Page 22 of 33

ATTACHMENT #8 Page 23 of 33

ATTACHMENT #8 Page 24 of 33

ATTACHMENT #8 Page 25 of 33

ATTACHMENT #8 Page 26 of 33

ATTACHMENT #8 Page 27 of 33

ATTACHMENT #8 Page 28 of 33

Appendix E

ATTACHMENT #8 Page 29 of 33

ATTACHMENT #8 Page 30 of 33

ATTACHMENT #8 Page 31 of 33

ATTACHMENT #8 Page 32 of 33

ATTACHMENT #8 Page 33 of 33