This solicitation seeks proposals for a building renovation project. The Department of the Air Force Special Operations Command is soliciting proposals under solicitation number FA485521B0002 for renovations to Building 60. A site visit will be held on July 9th at 1:00PM MDT to review the requirement. Interested parties should review the attached solicitation documents for details on the scope of work, which includes renovating an existing building to update its facilities. The proposal due date is not specified in the document provided.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
27TH SPECIAL OPERATIONS CIVIL ENGINEER SQUADRON (AFSOC)
CANNON AIR FORCE BASE NEW MEXICO
AIR COMMANDOS
30 March 2021 MEMORANDUM FOR 27 SOCES/CEN (Mr. Chauvin)
FROM: 27 SOCES/CEIE
SUBJECT: Asbestos Survey – Building 60
1. On 17 March 21, Civil Engineer Environmental Element (CEIE) personnel, upon request from
27 SOCES/Engineering Flight (CEN), assessed the project site in Building 60 (Attachment 1) to determine the potential impacts projected work activities could have on suspect asbestos-containing materials (ACM). Thirteen (13) samples were collected for laboratory analysis.
2. Project Description: The project associated with this work effort is to demolish and replace carpeting throughout the building and replace drop ceiling and grid that does not meet current base architectural standard throughout the building. The project and work area encompassed by this survey is provided below and in the Floor Plan provided as Attachment 1.
3. This Asbestos Survey was performed by Mrs. Amanda Farr (CEIE) as the Lead Asbestos
Inspector for this survey; certification may be referenced in Attachment 2.
4. Findings:
a. Twelve (12) samples consisting of one (1) distinct layer were collected from the ceiling tiles and floors and one (1) sample consisting of two (2) distinct layers was collected from the flooring of Building 60 for laboratory analysis for asbestos as follows:
Gray Hard/Granular floor tile, Tan/Black Soft/Bituminous mastic, Yellow/Black Soft/Bituminous mastic, Off White Fibrous ceiling tile, and White Fibrous ceiling tile.
b. Analytical results provided in Attachment 3 and Attachment 4 indicate that all analyzed materials were below the regulatory limit for asbestos.
(1) Floor mastics (Samples # 60-210317-01 & 02) located in building 60 are asbestos-containing material with >1% asbestos by weight or volume as demonstrated in Attachment 3; samples were analyzed at a concentration of 2% using polarized light microscopy (PLM) method of testing. Further testing was done on the two samples (01 & 02) using the Point Count Method.
(2) Ceiling Tiles (Samples # 60-210317-03, 04, 05, 06, 07, 08, 09, 10, 11, 12) and floor mastic (Sample # 60-210917-13) located in building 60 had no asbestos fibers detected by PLM method of testing provided in Attachment 3. No further tests were performed on these samples.
(3) Sample numbers 60-210317-01 & 02 were tested using the Point Count Method.
These samples are <1% asbestos by weight or volume as demonstrated in Attachment 4; Samples were analyzed at 0.50% and 0.75% respectively.
c. Photos of homogeneous materials sampled during this Survey may be referenced in
Attachment 5.
5. Analytical Methods: Analysis was accomplished by polarized light microscopy (PLM) in a laboratory certified for Environmental Protection Agency (EPA) Method 600/R-93/116, as required by 40 CFR 763/Subpart E, Appendix E. Analysis results and laboratory certification may be referenced in Attachment 6. A summary of the analysis methods used for this effort include:
a. PLM EPA Method 600/R-93/116/EPA-600-M4-82-020: PLM is a technique used for the identification and quantification of asbestos in bulk materials. This method utilizes the polarized light microscope to observe specific optical properties. Using these optical properties the PLM analyst can distinguish asbestos from non-asbestos fibers and further classify the various species that compose the asbestos mineral family. The method separates the sample material into various layers based on their morphology and then detects for the presence for the different asbestos fibers in each of these layers. The results are expressed as the percentage of the different asbestos fibers detected in each of the different layers based upon visual estimation. Additionally, the results of the non-asbestos fibrous component of each bulk sample is reported. The detection limit set by the EPA for asbestos containing material is 1% asbestos. Any material greater than 1% asbestos would be presumed to be asbestos containing material (ACM) but may be verified through Point Count Analysis.
b. Asbestos EPA 400 Point Count Method 600/R-93/116/EPA-600-M4-82-020 – The Point Count method is a more labor-intensive technique for quantitating asbestos, and is less subjective than a visual estimation. This can be important especially at low asbestos concentrations. This methodology, which has a detection limit of 0.25% asbestos, increases the accuracy and precision of the asbestos concentration determined in a sample and is widely used to comply with National Emissions Standards for Hazardous Air Pollutants (NESHAP) regulations that recommend the use of better quantification methods with low concentrations of asbestos.
6. Conclusion: Suspect ACM samples tested show to contain asbestos at a level lower than the regulated limit. At the tested levels there are no regulated requirements for work being done with the materials.
AMANDA M FARR, GS-12
Lead Certified Asbestos Inspector/CEIE
6 Attachments:
1. Floor Plan of Project Area
2. Asbestos Inspector Certification
3. PLM Analytical Results
4. Point Count Analytical Results
5. Sample Photo Log
6. Laboratory Accreditation cc: 27 SOCES/CEIA
Attachment 1. Floor Plan of Project Area
07 08
09 10 11 12 13
BUILDING INSPECTOR
Amanda Farr This certificate is awarded to:
In recognition of satisfactory completion of the EPA-approved initial asbestos training course under section 206 of the Toxic Substance Control Act (TSCA), Title II entitled:
Danaya N. BenedettoDanaya N. Benedetto
21246039
Aaron HixAaron Hix
Course Dates:
Expiration Date:
Course Hours:
July 27 - 29, 2020
I20-0902-AI
July 29, 2021 24.0
CHC Training Certificate No.Credential License ID:
Examination Date: July 29, 2020
Certificate of Achievement
InstructorCEO & Training Program Manager
CHC Training Nationwide Training & Certification Experts www.chctraining.com 303.412.6360
855.60.CERTIFY
1775 West 55th Avenue Denver, CO 80221, United States of America
Attachment 2.
Attn:
Address: 27 SOCES/CEIE: Amanda Farr Order #: 410249
506 N Air Commando Way
Cannon AFB, NM 88103-5003
Cannon Air Force Base (2764)Customer:
Received 03/22/21
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
03/27/21Analyzed
03/29/21Reported
Analysis Report
PLM Analysis
Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Flooring And Ceiling Tile
FA4855-07-A-0012Number: PO Number:
Location: Cannon AFB
Cannon AFB03/17/21 60-210317-01410249-001
Gray, Hard/Granular
Floor TileLayer 1: None Detected
Unable to separate individual layers.
NON FIBROUS MATERIAL100%
Tan/Black, Soft/Bituminous
MasticsLayer 2:
Unable to separate individual layers.
NON FIBROUS MATERIAL98%CHRYSOTILE2%
Cannon AFB03/17/21 60-210317-02410249-002
Yellow/Black, Soft/Bituminous
MasticsLayer 1:
Unable to separate individual layers.
NON FIBROUS MATERIAL98%CHRYSOTILE2%
Cannon AFB03/17/21 60-210317-03410249-003
Off White, Fibrous
Ceiling TileLayer 1: None Detected CELLULOSE FIBER40%
MINERAL/GLASS WOOL40%
NON FIBROUS MATERIAL20%
Cannon AFB03/17/21 60-210317-04410249-004
Off White, Fibrous
Ceiling TileLayer 1: None Detected CELLULOSE FIBER40%
MINERAL/GLASS WOOL40%
NON FIBROUS MATERIAL20%
Cannon AFB03/17/21 60-210317-05410249-005
Off White, Fibrous
Ceiling TileLayer 1: None Detected CELLULOSE FIBER40%
MINERAL/GLASS WOOL40%
NON FIBROUS MATERIAL20%
Cannon AFB03/17/21 60-210317-06410249-006
Off White, Fibrous
Ceiling TileLayer 1: None Detected CELLULOSE FIBER40%
MINERAL/GLASS WOOL40%
NON FIBROUS MATERIAL20%
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the laboratory. The test results reported relate only to the samples submitted.
Attachment 3.
PLM Analysis
Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Flooring And Ceiling Tile
FA4855-07-A-0012Number: PO Number:
Location: Cannon AFB
Cannon AFB03/17/21 60-210317-07410249-007
Off White, Fibrous
Ceiling TileLayer 1: None Detected CELLULOSE FIBER40%
MINERAL/GLASS WOOL40%
NON FIBROUS MATERIAL20%
Cannon AFB03/17/21 60-210317-08410249-008
Off White, Fibrous
Ceiling TileLayer 1: None Detected CELLULOSE FIBER40%
MINERAL/GLASS WOOL40%
NON FIBROUS MATERIAL20%
Cannon AFB03/17/21 60-210317-09410249-009
White, Fibrous
Ceiling TileLayer 1: None Detected FOAMED GLASS10%
MINERAL/GLASS WOOL80%
NON FIBROUS MATERIAL10%
Cannon AFB03/17/21 60-210317-10410249-010
White, Fibrous
Ceiling TileLayer 1: None Detected FOAMED GLASS10%
MINERAL/GLASS WOOL80%
NON FIBROUS MATERIAL10%
Cannon AFB03/17/21 60-210317-11410249-011
White, Fibrous
Ceiling TileLayer 1: None Detected FOAMED GLASS10%
MINERAL/GLASS WOOL80%
NON FIBROUS MATERIAL10%
Cannon AFB03/17/21 60-210317-12410249-012
White, Fibrous
Ceiling TileLayer 1: None Detected FOAMED GLASS10%
MINERAL/GLASS WOOL80%
NON FIBROUS MATERIAL10%
Cannon AFB03/17/21 60-210317-13410249-013
Yellow, Soft
MasticLayer 1: None Detected NON FIBROUS MATERIAL100%
Microscopy Manager
Reviewed By: Hind Eldanaf
Total layers analyzed on order: 14 410249-03/29/21 09:48 AM
EPA Regulatory Limit: 1%
Analyst Senhory Abdellatif
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the laboratory. The test results reported relate only to the samples submitted.
Attn:
Address: 27 SOCES/CEIE: Amanda Farr Order #: 411151
506 N Air Commando Way
Cannon AFB, NM 88103-5003
Cannon Air Force Base (2764)Customer:
Received 03/29/21
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
03/29/21Analyzed
04/05/21Reported
Analysis Report
PLM Analysis
Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763 with Point CountMethod:
Project: Flooring And Ceiling Tile
FA4855-07-A-0012Number: PO Number:
Location: Cannon AFB
Cannon AFB03/17/21 60-210317-01411151-001
Tan/Black, Soft/Bituminous, Homogenous
MasticsLayer 1:
Unable to separate individual layers.
NON FIBROUS MATERIAL99.50%CHRYSOTILE0.50%
Cannon AFB03/17/21 60-210317-02411151-002
Yellow/Black, Soft/Bituminous, Homogenous
MasticsLayer 1:
Unable to separate individual layers.
NON FIBROUS MATERIAL99.25%CHRYSOTILE0.75%
Approved Signatory
Reviewed By: Andrew Bruner
Total layers analyzed on order: 2 411151-04/05/21 11:18 AM
EPA Regulatory Limit: 1%
Analyst Senhory Abdellatif
Reporting limit: 0.25% Samples analyzed by the EPA Point Count test method. The EPA recommends that any attic loose fill vermiculite sample with a trace (<1) or greater amount of asbestos is a concern and should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the lab, and must not be used to claim NVLAP or other government agency endorsement. The test results reported relate only to the samples submitted.
Attachment 4.
Attachment 5. Sample Photo Log
Floor Mastic Samples:
Sample No. 20-210317-01 is a two (2) layer sample consisting of floor tile and tan/black mastic. Point Count analysis method found layer 1 to be 0.50% Chrysotile by weight or volume. Layer 2 was found to be non-detect for asbestos fibers via PLM analysis method.
Sample No. 60-210317-02 is a one (1) layer sample consisting of yellow/black mastic. Point Count analysis method found this sample to be 0.75% Chrysotile by weight or volume.
Sample No. 60-210317-13 is a one (1) layer sample consisting of yellow mastic. Sample was found to be non-detect for asbestos fibers.
Sample No. 60-210317-03 is a one (1) layer sample consisting of off white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-03 & 60-210317-04 are a homogenous material.
Sample No. 60-210317-04 is a one (1) layer sample consisting of off white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-03 & 60-210317-04 are a homogenous material.
Sample No. 60-210317-05 is a one (1) layer sample consisting of off white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-05 & 60-210317-06 are a homogenous material.
Sample No. 60-210317-06 is a one (1) layer sample consisting of off white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-05 & 60-210317-06
Sample No. 60-210317-07 is a one (1) layer sample consisting of off white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-07 & 60-210317-08 are a homogenous material.
Sample No. 60-210317-08 is a one (1) layer sample consisting of off white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-07 & 60-210317-08
Sample No. 60-210317-09 is a one (1) layer sample consisting of white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-09 & 60-210317-10 are a homogenous material.
Sample No. 60-210317-10 is a one (1) layer sample consisting of white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-09 & 60-210317-10
Sample No. 60-210317-11 is a one (1) layer sample consisting of white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-11 & 60-210317-12 are a homogenous material.
Sample No. 60-210317-12 is a one (1) layer sample consisting of white fibrous ceiling tile.
Sample was found to be non-detect for asbestos fibers. Samples 60-210317-11 & 60-210317-12 is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).
Attachment 6.