Attachment 5 - Building List and Electrical Data.pdf
PDF 172 KB Posted
- Attached to
- Electric Meter Installation
- Solicitation number
- FA480326R0017
About this file
This document is a Building List and Electrical Data table for contract VLSB 26-0077, providing a comprehensive inventory of electrical infrastructure across 42 buildings or facilities.
The table lists 42 buildings with associated transformer identifications, secondary voltages, kilovolt-ampere (kVA) ratings, and electrical service sizes. Secondary voltages are predominantly 208Y/120, with several facilities utilizing 480Y/277 and one using 240/120. kVA ratings range from 75 to 1500, while service sizes vary from 100 to 2500 amperes. Notable specifications include six wells (Buildings 1415, 1835, 2004, 2233, 3656, and one unnumbered) integrated into the electrical system. Two buildings require special attention: Building 1930 requires meter and current transformer (CT) installation at the transformer location, and Buildings 1042 and 1996 may require weekend power outages to accommodate installation or maintenance work. This data appears to support planning for electrical metering, upgrade, or installation activities across the portfolio of buildings under this contract.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building List & Electrical Data
VLSB 26-0077
Building # Transformer ID Secondary Voltage kVA Rating Service Size 2 T2 208Y/120 300 800
402 T402A 208Y/120 300 1200 406 T406 208Y/120 300 400 407 T407B 208Y/120 112.5 600 419 T419 208Y/120 500 2500 421 T421 208Y/120 500 2500 801 T801 208Y/120 150 400 903 T903 208Y/120 500 1200 904 T904 208Y/120 500 800 905 T905B 208Y/120 500 800 927 T927 208Y/120 150 600 928 T928 208Y/120 300 600 931 T932 208Y/120 500 600 932 T932 208Y/120 500 600 933 T932 208Y/120 500 600 934 T932 208Y/120 500 600 937 T937 208Y/120 300 800
1042** T1042 480Y/277 1500 2000 1044 T1044 208Y/120 113 400 1046 T1046 480Y/277 500 1200 1052 T1052 208Y/120 225 225 1062 T1062 208Y/120 225 600 1405 T1405 208Y/120 225 1200 1406 T1406 208Y/120 75 200
1415 (well 5) T1415 208Y/120 225 400 1420 T1420 480Y/277 1000 1600 1440 T1440 208Y/120 75 400
1835 (well 1) T1835 208Y/120 150 600 1900 T1900 208Y/120 500 400
1930* T1930 208Y/120 225 200* 1951 T1951 480Y/277 1000 1600 1957 T1957 480Y/277 500 600 1958 T1958 480Y/277 500 600
1996** T1996 480Y/277 1500 2500 2004 (well 4 ) T2004A 240/120 mt 225 400 2233 (well 3) T2233 208Y/120 225 400
2790 T-GOLF 480/277 150 225
2798 T2798 208Y/120 150 100 2799 T2799 208Y/120 225 400
3656 (well 6) T3656 208Y/120 225 225
* 1930 will need to have the meter and CTs located at the transformer.
**1042 and 1996 may require weekend work for the power outage.