Performance Work Statement Summary

This is a Performance Work Statement for annual maintenance and 12-year hydrostatic inspection of fire extinguishers at 317 AMXS Dyess Air Force Base, Texas. The contractor shall service up to 50 Amerex model 600 wheeled 150 lb Halon extinguishers, up to 158 Amerex model B355T hand-portable 5 lb Halon extinguishers, and up to 10 Amerex model 775 wheeled 150 lb Novec extinguishers. All work must comply with NFPA Standard 10, Technical Orders 13F4-4-121 and 13F4-4-131, and original equipment manufacturer service manuals.

The contract covers a base year (FY26) plus four option years (FY27-FY30). The base year includes annual maintenance for all extinguishers and hydrostatic testing of 158 x 5 lb Halon units. Option Year 1 (FY27) adds hydrostatic testing of 50 x 150 lb Halon and 10 x 150 lb Novec extinguishers; subsequent option years include only annual maintenance. The contractor must possess appropriate licenses to inspect, maintain, and service the specified extinguishers and provide thorough training and supervision. Services are performed Monday through Friday, 0730-1630, at a government-provided location adjacent to building 4216, with no access to restricted flightline areas. The contractor furnishes all personnel, equipment, tools, replacement parts (up to 75 per item per year), a closed-loop recovery system for extinguishing agents, disposal services, and comprehensive reporting documenting all findings, repairs, weights, and service dates. The government furnishes the collection point, transportation, halogenated agent from existing stock, owner's manuals, and project oversight. All work must meet quality assurance standards verified through 100% government inspection of completed extinguishers.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

labels shall be self-destructing upon attempted removal and include: (1) Month and year of the test (via perforation), (2) The type of inspection conducted, and

(3) The name or initials of the person and agency performing the inspection.

4. Schedule Summary

The contractor shall perform services according to the following schedule:

Period Services Performed

FY26 (Base Year)

FY27 (Option Year 1)

FY28 (Option Year 2)

FY29 (Option Year 3)

FY30 (Option Year 4)

Task 1 : Annual Maintenance ( All Extinguishers)

Task 2 : Hydrostatic Testing (158 x 5 lbs Halon)

Task 1 : Annual Maintenance ( All Extinguishers)

Task 2 : Hydrostatic Testing (50 x 150 lbs Halon, 10 x 150 lbs Novec)

Task 1 : Annual Maintenance ( All Extinguishers)

Task 1 : Annual Maintenance ( All Extinguishers)

Task 1 : Annual Maintenance ( All Extinguishers)

5. Government-Furnished vs. Contractor-Furnished Items

• 5.1. Government-Furnished Services and Materials

• A single fire extinguisher collection, delivery, and work location behind building

4216.

• Transportation of all fire extinguishers to and from the designated collection point.

• Halogenated (Halon 1211) fire extinguishing agent from existing shop stock, as required. The 31 7 AMXS will decide on extra agent requirements.

• Access to each type/model fire extinguisher owner's manual or T.O.

• Government project managers for oversight and quality assurance.

• 5.2. Contractor-Furnished Services and Materials