This document is a Questions and Answers (Q&A) file related to an electrical roof remodel project at Global Strike Command, Malmstrom Air Force Base, Montana, specifically for Repair Building 1840 Roof.
The project involves installation of heat tape in all existing gutters and downspouts connected to a new heat trace control cabinet located in the electrical room. Heat tape shall be self-regulating type, Raychem GM-2XT Series, 12 watts per foot or approved equal. Circuiting requirements include 12 anticipated circuits, each fed by 30-amp circuit breakers with 30mA GFCI protection, connected via 2#8 and #10G conductors in 3/4" conduit to avoid excessive voltage drop. Heat tape must be looped down and back up each roof drain and downspout. The electrical work requires engineered shop drawings from the heat tape manufacturer detailing circuiting requirements, zoning, moisture/thermostat locations, and wiring requirements. The project also includes disconnecting and reconnecting an exhaust fan once mechanical and roofing contractors complete their modifications, with conduit and wire extensions as required. Q&A Question 38 addresses contractor inquiries regarding the specific locations of downspouts shown on elevation views and whether heat tape is supposed to be extended to the next gutter, with yellow flag notes indicating government clarification is needed on these points.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Q&A question 12 &13
1 ELECTRICAL ROOF REMODEL PLAN
SCALE: 1/32"=1'-0"
160 8 32 48 64 12896 N
SPECIFIC SHEET NOTES:
PROVIDE HEAT TAPE IN ALL EXISTING GUTTERS AND DOWNSPOUTS
AND CONNECT TO NEW HEAT TRACE CONTROL CABINET LOCATED
IN ELECTRICAL ROOM. PROVIDE ENGINEERED SHOP DRAWINGS
FROM HEAT TAPE MANUFACTURER NOTING CIRCUITING
REQUIREMENTS FROM CONTROL CABINET, ZONING, AND
MOISTURE/THERMOSTAT LOCATIONS AND WIRING REQUIREMENTS.
HEAT TAPE SHALL BE SELF REGULATING TYPE, RAYCHEM GM-2XT
SERIES, 12 WATTS PER FOOT, OR APPROVED EQUAL. CONNECT
HEAT TAPE CIRCUITS VIA 2#8 AND #10G IN 3/4" CONDUIT PER EACH
CIRCUIT TO AVOID EXCESSIVE VOLTAGE DROP. 12 CIRCUITS ARE
ANTICIPATED, EACH FED BY 30 AMP CIRCUIT BREAKER WITH 30mA
GFCI PROTECTION.
LOOP HEAT TAPE DOWN AND BACK UP EACH ROOF DRAIN/
DOWNSPOUT (NOTED BY "RD"). SEE STRUCTURAL ELEVATIONS FOR
ROOF HEIGHTS AND/OR DOWN SPOUT LENGTHS.
DISCONNECT EXHAUST FAN AND RECONNECT ONCE MECHANICAL
AND ROOFING CONTRACTORS HAVE MADE THEIR MODIFICATIONS.
EXTEND CONDUIT AND WIRE AS REQUIRED.
1 TYPICAL2 TYPICAL
GLOBAL STRIKE COMMAND
MALMSTROM AIR FORCE BASE, MONTANA
GENERAL NOTE:
RESTRICTED AREA ACCESS: ACCESS TO PORTIONS OF THE ROOF WILL BE RESTRICTED AT CERTAIN TIMES DUE TO OPERATIONS WITHIN THE FACILITY. CONSTRUCTION PERSONNEL MUST REMAIN WITHIN THE DESIGNATED CONSTRUCTION LIMITS AT ALL TIMES, AS DETERMINED BY THE GOVERNMENT, AND MUST NOT ENTER INTO OR ABOVE RESTRICTED AREAS. MOVEMENT OUTSIDE APPROVED WORK ZONES IS PROHIBITED UNLESS AUTHORIZED AND ESCORTED BY GOVERNMENT PERSONNEL. VIOLATIONS OF THIS REQUIREMENT MAY RESULT IN IMMEDIATE REMOVAL FROM THE PROJECT SITE. REGULARLY OCCURRING PROJECT SCHEDULE MEETINGS WILL BE HELD IN ORDER TO COORDINATE WORK AREAS AND RESTRICTED AREAS.
BRAD M.
KAUFFMAN
No. 14587 PE
Q&A Question 38
Austin Wall Type
Austin Wall Type
Austin Callout Question to the government.
Are these downspouts and heat tape supposed to be extended to the next gutter?
Austin Line
Austin Note 3/32"
Austin Callout Question to the government.
Are these downspouts locations that show on the elevation view suppose to get heat tape as well?
East Exterior Elevation
West Exterior Elevation
North Exterior Elevation
South Exterior Elevation
GLOBAL STRIKE COMMAND
MALMSTROM AIR FORCE BASE, MONTANA
NF
N
SE
OIS LA
IGNE
N
OR
P
M
O AT
EE
AN
R
FLAG NOTES
EPOXY INJECT CRACKS SEE
SPECIFICATION
32" = 1'-0"
32" = 1'-0"
32" = 1'-0"
32" = 1'-0"
Q&A Question 38
AutoCAD SHX Text 9'-9 "34"
AutoCAD SHX Text 23'-2"
AutoCAD SHX Text 11'-10"
AutoCAD SHX Text 36'-0"
AutoCAD SHX Text 8'-8"
AutoCAD SHX Text 27'-4 "14"
AutoCAD SHX Text 7'-4"
AutoCAD SHX Text 3'-2"
AutoCAD SHX Text 19'-2"
AutoCAD SHX Text 12'-6"
AutoCAD SHX Text 11'-4"
AutoCAD SHX Text 12'-5 "34"
AutoCAD SHX Text 6'-5 "12"
AutoCAD SHX Text 11'-10 "12"
AutoCAD SHX Text 14'-8"
AutoCAD SHX Text 12'-0"
AutoCAD SHX Text 20'-8"
AutoCAD SHX Text 24'-3 "12"
AutoCAD SHX Text 12'-10"
AutoCAD SHX Text 9'-9 "12"
AutoCAD SHX Text 4'-2 "78"
AutoCAD SHX Text 24'-3 "12"
AutoCAD SHX Text 22'-8"
AutoCAD SHX Text 10'-8"
AutoCAD SHX Text 13'-1 "12"
AutoCAD SHX Text 11'-3 "14"
AutoCAD SHX Text 11'-10 "12"
AutoCAD SHX Text 9'-1 "34"
AutoCAD SHX Text 27'-1"
AutoCAD SHX Text 18'-8"
AutoCAD SHX Text 12'-0"
AutoCAD SHX Text 15'-1 "34"
AutoCAD SHX Text 21'-1 "34"
AutoCAD SHX Text
ELEVATION VIEWS
AutoCAD SHX Text
AutoCAD SHX Text 24-035-S4X
AutoCAD SHX Text S4.0
AutoCAD SHX Text
ATTACHMENT:
AutoCAD SHX Text
FA4626-XX-X-XXXX
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
REVIEWED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PLATE
AutoCAD SHX Text
PAGE
AutoCAD SHX Text
OF
AutoCAD SHX Text
PROJECT NUMBERS
AutoCAD SHX Text
ACAD DRAWING NUMBER
AutoCAD SHX Text
RECORD FILE NUMBER
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
AutoCAD SHX Text
NZAS 23-0059
AutoCAD SHX Text
REPAIR BLDG 1840 ROOF
AutoCAD SHX Text 10/09/25
AutoCAD SHX Text
RRB
AutoCAD SHX Text
RRB
AutoCAD SHX Text
RLT
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text
15168 PE
AutoCAD SHX Text
BLAKE
AutoCAD SHX Text
RODNEY R.
Austin Callout Question to the government.
Are these downspouts and heat tape supposed to be extended to the next gutter?
Austin Callout Question to the government.
Are these downspouts locations that don't show on E1.2 suppose to get heat tape as well?
| E1.2 |
| S4.0 |
File details come from the government source that posted it. Updated .