4100 HVAC_QA.xlsx

XLSX spreadsheet 24 KB Posted

Attached to
HVAC Chillers
Solicitation number
FA4626-25-Q-0019
Issued by

About this file

This document is a Questions and Answers (Q&A) spreadsheet for Solicitation FA4626-25-Q-0019, detailing specifications for HVAC chillers to be procured by the Department of the Air Force Global Strike Command. The solicitation requires four HVAC chillers with specific configurations: one 70-ton unit with cold start and dry cooler, one 90-ton, one 40-ton, and one 50-ton chiller, to be delivered to Malmstrom Air Force Base in Montana. Key technical specifications include air-cooled outdoor units, 208V 3-phase 60 Hz power, propylene glycol and water fluid, 45°F chiller setpoint, 55°F process return temperature, and no installation required.

The Q&A document provides extensive technical details, confirming voltage requirements, ambient temperature conditions, and specific performance criteria such as entering/leaving water temperatures and fluid flow rates. Notable points include no brand preference, comfort cooling application, on-site power availability, and a delivery deadline with potential consequences for missed timelines. Potential vendors must ensure their proposed chillers meet the detailed specifications, with no formal submittal review process planned. The solicitation indicates questions were due by April 27th, with an emphasis on precise technical compliance for the HVAC unit procurement.

View the file

Other files

File Type Posted
640 HVAC_QA.xlsx XLSX spreadsheet
Amendment2 HVAC Chillers.pdf PDF
Amendment2 HVAC Chillers_Combo.pdf PDF
40T HVAC_QA.xlsx XLSX spreadsheet
330 HVAC_QA.xlsx XLSX spreadsheet
Amendment 001 Ack.pdf PDF
Amendment 001 HVAC Chillers_Combo.pdf PDF
HVAC Chillers Combo.pdf PDF
Attch 1_Salient Characteristics_HVAC Chillers.pdf PDF
Attch 2_Clauses.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

HVAC Units/ FA4626-25-Q-0019
Questions and Answers
Question #QuestionAnswer
1
Air-cooled / Water-cooled?Air Cooled
2Indoor/Outdoor?Outdoor
3Chiller setpoint?45F
4Process return temperature?55F
5Is pumping and/or tank required?No
6Process fluid (water / propylene glycol)Propylene glycol and water
7How much power do you have to tie into these chillers? (If you need power we can bring in generators)Power is on site
8We would need to know your hose/cable runs.Awaiting clarification for this question.
9Can you please provide the complete specs required in the chillers?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
10Can you provide any model number for the reference?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
11Can you confirm that this is Buy American?N/A
12Please confirm the voltage?208V 3 PH 60 Hz
13Please confirm that these are air cooled chillers?Yes
14Is this existing equipment and if so can you please provide pics of the tags?Awaiting clarification for this question.
15What are the voltage requirements?208V 3 PH 60 Hz
16Are the chillers indoor or packaged outdoor units?Outdoor
17Are the units self-contained with pumps, tanks etc.?no
18Where would you need them to be delivered to?341 CES Malmstrom AFB Montana
19Will you require factory startups?Yes
20Could you please provide the complete specifications of the Chillers?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
21Incoming and Leaving Water Temperatures – Could you please provide the desired entering and leaving water
temperatures for each chiller unit?45F 55F
22Power Requirements – Please confirm the electrical specifications required for each unit (e.g., voltage, phase, frequency).208V 3 PH 60 Hz
23Installation Site Conditions – If available, any additional site-related data (e.g., ambient conditions, available space
for dry cooler) would also be helpful.Ready for unit and Drycooler
24Could you kindly send over specifications for each unit?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
25Please advise voltage needed, what options are needed, any specific capacity requirements -
flow rates, temperature requirements etc.208V 3 PH 60 Hz
26Would you happen to know the Pre-existing Unit info for the chillers that are being replaced?Model = AGZ004F 51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
27Do you have any specs for this equipment?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
28Design winter ambient temps?55F
29Design voltage?208V 3 PH 60 Hz
30Design fluid temps?45F
31Specifically looking for info on:
•Chiller Voltage
•Tonnages listed are nominal or at specific performance criteria? Glycol %?
•Dry cooler capacity and change over temp for full capacity?
•No installation is required, but is offloading or any other site work necessary?280V 50% Glycol 100 Percent capacity 45 degree change over NO
32I need a bit more information regarding the electrical voltages as well as the glycol cooler. Could you please confirm if you require 480V 3-phase or 208-240V 3-phase? How many CFM on glycol cooler? How many gallons per minute needed for sufficient flow? What are the entering and leaving water temps?208V 3 PH 60 Hz
33I am currently seeking to submit a bid for the respective solicitation and would like to inquire if you can provide the detailed specifications for all four chillers.
51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
34
Are there any specifications such as the voltages and unit optimizations that can be provided?208V 3 PH 60 Hz
35
Are there any specifications such as the voltages and unit optimizations that can be provided?208V 3 PH 60 Hz
36Could you please confirm whether the chillers should be configured as single-circuit systems or dual-circuit systems for redundancy
and operational reliability?Either
37I am currently seeking to submit a bid for the respective solicitation and would like to inquire if you can provide the detailed
specifications for all four chillers51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
38Could you please clarify the voltage required for the HVAC Chillers Solicitation Notice ID FA4626-25-Q-0019
submitted on Sam.gov?208V 3 PH 60 Hz
39Could you please mention more specifications regarding this request?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature 95F Altitude 3600FT
40What process will these chillers be serving? (Comfort Cooling or Manufacturing or other Process Coolin)?Comfort
41What voltage do the chillers need to be?208V 3 PH 60 Hz
42Footprint of chillers? I see the Salient Characteristic document, but want to more information with square footage of pad and thickness etc.PAD will be poured to unit size after delivery of unit
43To quote standard units we will need electrical power supply and certainly elevation and confirm ambient conditions.208V 3 PH 60 Hz
44Is the "cold start and dry cooler" only required for the 70 ton?Yes
45The solicitation states that no installation is required, but who is responsible for offloading the chillers from the truck when
they arrive on site?341 CES
46Was there a Brand preference?No specific brand preffered. Chiller must satisfy specifications.
47Are there any specifications such as the voltages and unit optimizations that can be provided?208V 3 PH 60 Hz
48Blueprints and Layout Drawings:
oScaled diagrams that detail the dimensions of the equipment and the pad.
oInclude placement, clearances, and any necessary anchoring points.
If there are any technical documents, specifications, or resources available, I would be grateful if you could share them.N/A
49Re the request for the (4) HVAC Chillers. Was there a Brand preference?
No specific brand preffered. Chiller must satisfy specifications.
50What process will these chillers be serving? (Comfort Cooling or Manufacturing or other Process Cooling)?Comfort
51What voltage do the chillers need to be?208V 3 PH 60 Hz
52Can you please provide a detailed item specification to the HVAC Chillers Solicitation Notice ID FA4626-25-Q-0019 posted on sam.gov?51.66 Ton 208V 3 PH 60 HZ Air cooled scroll compressor Entering temperature 54F leaving temperature 44F Fluid flow 135.7 Ambient temperature

95F Altitude 3600FT

53Is the "cold start and dry cooler" only required for the 70 ton?Yes
54Upon review, it is evident that we need additional information, such as referenced brand, model numbers, product details such as equipment voltages, etc. in order to be able to put together a quotation.208V 3 PH 60 Hz
Will there be a submittal and review process for the proposed chillers prior to, or after the date of contract? If so will the time in review be considered as part of the 90-days?There is not a submittal process.The product quoted must meet the specifications within the solicitation.
Are there liquidated damages or other considerations if this deadline is not met?Considerations will be pursued if the delivery deadline is not met.
Lead times on equipment can fluctuate. Do you want information of the current published lead times for the prosed chillers provided on the solicitation?No, as long as the product arrives within the delivery deadline.
We are tracking SAM.GOV but still there is no addendum for the specifications of the chillers.
Could you please let us know how long it will take you to get it published on the website.This document is intended to clarify specifications needed for this requirement.
83
84
85
86
87
88
89

&"Times New Roman,Regular"&P of &N

Sheet2

remove draft stamp
topr may 4th 3 pm
questions due by the 27th of April