The file is a Questions and Answers (Q&A) document for Solicitation FA4626-25-Q-0019, detailing requirements for HVAC chillers to be delivered to Malmstrom Air Force Base, Montana. The solicitation seeks four HVAC units: one 70-ton chiller with a cold start and dry cooler, one 90-ton chiller, one 40-ton chiller, and one 50-ton chiller, with specific technical specifications including 208V 3-phase 60 Hz power requirements, air-cooled outdoor units, and propylene glycol and water as process fluid.

Key details include delivery to 341 CES at Malmstrom AFB, no installation required, factory startup needed, and comfort cooling application. Technical specifications consistently cite 40-ton units with 93 gpm design flow, entering temperature of 54F, leaving temperature of 44F, and ambient temperature of 95F. No specific brand preference exists, but chillers must meet outlined specifications. The solicitation indicates considerations will be pursued if delivery deadlines are not met, and there is no formal submittal process for proposed chillers. Questions were due by April 27th, with the document intended to clarify specifications for the requirement.

View the file

Other files

File Type Posted
Amendment2 HVAC Chillers_Combo.pdf PDF
4100 HVAC_QA.xlsx XLSX spreadsheet
Amendment2 HVAC Chillers.pdf PDF
330 HVAC_QA.xlsx XLSX spreadsheet
640 HVAC_QA.xlsx XLSX spreadsheet
Amendment 001 HVAC Chillers_Combo.pdf PDF
Amendment 001 Ack.pdf PDF
Attch 1_Salient Characteristics_HVAC Chillers.pdf PDF
Attch 2_Clauses.pdf PDF
HVAC Chillers Combo.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

HVAC Units/ FA4626-25-Q-0019
Questions and Answers
Question #QuestionAnswer
1
Air-cooled / Water-cooled?Air Cooled
2Indoor/Outdoor?Outdoor
3Chiller setpoint?45F
4Process return temperature?54F
5Is pumping and/or tank required?No
6Process fluid (water / propylene glycol)Propylene glycol and water
7How much power do you have to tie into these chillers? (If you need power we can bring in generators)Power is on site
8We would need to know your hose/cable runs.Awaiting question clarification.
9Can you please provide the complete specs required in the chillers?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
10Can you provide any model number for the reference?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
11Can you confirm that this is Buy American?N/A
12Please confirm the voltage?208V 3 PH 60 Hz
13Please confirm that these are air cooled chillers?Yes
14Is this existing equipment and if so can you please provide pics of the tags?Awaiting question clarification.
15What are the voltage requirements?208V 3 PH 60 Hz
16Are the chillers indoor or packaged outdoor units?Outdoor
17Are the units self-contained with pumps, tanks etc.?no
18Where would you need them to be delivered to?341 CES Malmstrom AFB Montana
19Will you require factory startups?Yes
20Could you please provide the complete specifications of the Chillers?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
21Incoming and Leaving Water Temperatures – Could you please provide the desired entering and leaving water
temperatures for each chiller unit?45F 55F
22Power Requirements – Please confirm the electrical specifications required for each unit (e.g., voltage, phase, frequency).208V 3 PH 60 Hz
23Installation Site Conditions – If available, any additional site-related data (e.g., ambient conditions, available space
for dry cooler) would also be helpful.Ready for unit and Drycooler
24Could you kindly send over specifications for each unit?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
25Please advise voltage needed, what options are needed, any specific capacity requirements -
flow rates, temperature requirements etc.208V 3 PH 60 Hz
26Would you happen to know the Pre-existing Unit info for the chillers that are being replaced?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
27Do you have any specs for this equipment?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
28Design winter ambient temps?55F
29Design voltage?208V 3 PH 60 Hz
30Design fluid temps?45F
31Specifically looking for info on:
•Chiller Voltage
•Tonnages listed are nominal or at specific performance criteria? Glycol %?
•Dry cooler capacity and change over temp for full capacity?
•No installation is required, but is offloading or any other site work necessary?280V 50% Glycol 100 Percent capacity 45 degree change over NO
32I need a bit more information regarding the electrical voltages as well as the glycol cooler. Could you please confirm if you require 480V 3-phase or 208-240V 3-phase? How many CFM on glycol cooler? How many gallons per minute needed for sufficient flow? What are the entering and leaving water temps?208V 3 PH 60 Hz
33I am currently seeking to submit a bid for the respective solicitation and would like to inquire if you can provide the detailed specifications for all four chillers.
40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
34
Are there any specifications such as the voltages and unit optimizations that can be provided?208V 3 PH 60 Hz
35
Are there any specifications such as the voltages and unit optimizations that can be provided?208V 3 PH 60 Hz
36Could you please confirm whether the chillers should be configured as single-circuit systems or dual-circuit systems for redundancy
and operational reliability?Either
37I am currently seeking to submit a bid for the respective solicitation and would like to inquire if you can provide the detailed
specifications for all four chillers40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
38Could you please clarify the voltage required for the HVAC Chillers Solicitation Notice ID FA4626-25-Q-0019
submitted on Sam.gov?208V 3 PH 60 Hz
39Could you please mention more specifications regarding this request?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
40What process will these chillers be serving? (Comfort Cooling or Manufacturing or other Process Coolin)?Comfort
41What voltage do the chillers need to be?208V 3 PH 60 Hz
42Footprint of chillers? I see the Salient Characteristic document, but want to more information with square footage of pad and thickness etc.PAD will be poured to unit
43To quote standard units we will need electrical power supply and certainly elevation and confirm ambient conditions.208V 3 PH 60 Hz
44Is the "cold start and dry cooler" only required for the 70 ton?Yes
45The solicitation states that no installation is required, but who is responsible for offloading the chillers from the truck when
they arrive on site?341 CES
46Was there a Brand preference?No specific brand preffered. Chiller must satisfy specifications.
47Are there any specifications such as the voltages and unit optimizations that can be provided?208V 3 PH 60 Hz
48Blueprints and Layout Drawings:
oScaled diagrams that detail the dimensions of the equipment and the pad.
oInclude placement, clearances, and any necessary anchoring points.
If there are any technical documents, specifications, or resources available, I would be grateful if you could share them.N/A
49Re the request for the (4) HVAC Chillers. Was there a Brand preference?
No specific brand preffered. Chiller must satisfy specifications.
50What process will these chillers be serving? (Comfort Cooling or Manufacturing or other Process Cooling)?Comfort
51What voltage do the chillers need to be?208V 3 PH 60 Hz
52Can you please provide a detailed item specification to the HVAC Chillers Solicitation Notice ID FA4626-25-Q-0019 posted on sam.gov?40Ton 208 V 3 PH 60 HZ Design flow 93 gpm entering temperature 54F leaving temperature 44F Ambient Temperature 95F
53Is the "cold start and dry cooler" only required for the 70 ton?Yes
54Upon review, it is evident that we need additional information, such as referenced brand, model numbers, product details such as equipment voltages, etc. in order to be able to put together a quotation.208V 3 PH 60 Hz
55Will there be a submittal and review process for the proposed chillers prior to, or after the date of contract? If so will the time in review be considered as part of the 90-days?There is not a submittal process.The product quoted must meet the specifications within the solicitation.
56Are there liquidated damages or other considerations if this deadline is not met?Considerations will be pursued if the delivery deadline is not met.
57Lead times on equipment can fluctuate. Do you want information of the current published lead times for the prosed chillers provided on the solicitation?No, as long as the product arrives within the delivery deadline.
58We are tracking SAM.GOV but still there is no addendum for the specifications of the chillers.
Could you please let us know how long it will take you to get it published on the website.This document is intended to clarify specifications needed for this requirement.
83
84
85
86
87
88
89

&"Times New Roman,Regular"&P of &N

Sheet2

remove draft stamp
topr may 4th 3 pm
questions due by the 27th of April