Questions 1.docx

DOCX document 13 KB Posted

Attached to
Remodel Dorm 740 Federal contract opportunity
Solicitation number
FA4626-10-R-0021
Issued by
Department of the Air Force Global Strike Command

About this file

Questions and Answers (1)

View the file

Other files for this federal contract opportunity

Other files attached to Remodel Dorm 740, newest first.
File Type Posted
Questioins and Answers 7.docx DOCX document
Questions and Answers 6.docx DOCX document
BIRD COVE DETAIL.pdf PDF
Questions and Answers 5.docx DOCX document
Questions and Answers 4.docx DOCX document
Amendment 0002.doc DOC document
085113-revised on Sept 9 2010.doc DOC document
TOC.Revise.9-9-2010doc.doc DOC document
Amendment 0001.doc DOC document
010100-Revised.9-9-2010.doc DOC document
Question and Answers 3.docx DOCX document
Questions 2.docx DOCX document
740 Site Visit.pdf PDF
Attach 1 Specifications.zip ZIP file
Attach 2 Material Submital.xlsx XLSX spreadsheet
Attch 3 Schedule of Drawings.DOC DOC document
Attach 5 Wage Determination Heavy.docx DOCX document
Attach 5 Wage Determination Building.docx DOCX document
Attch 4 Drawings.zip ZIP file
Solicitation.doc DOC document
Attch 6 Past Performance Questionnaire.docx DOCX document
Attch 7 - Subcontractor Consent Form - 10R0027.docx DOCX document
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Sheet A0.1, the first item in the legend states remove gyp. bd. from wall. West of suite 102 on grid line 2 and west of grid line d the western most wall shows the gyp. bd. being demoed. Sheet A1.1 shows that wall as a wall type E which states gyp. bd. to remain . Please CLARIFY what gyp. bd. gets demoed and stays between the demo sheets and the floor plan sheets. RESPONSE: Those walls have the sheet rock demoed and replaced. The description is wall type "E4" -note the "4" at the lower right corner of the triangle- which states to demo and replace.

2. Many of the sheet work notes on E1.1 call out for demolition of conducters and conduit in the rooms. Do these rooms have conduit in them, or romex, or a combination of both?

RESPONSE: Each typical/non-typical suite has a j-box in the ceiling space of the hallway between the sleeping rooms of each suite. There is conduit, as noted on plans, from this j-box back to corresponding panelboard. From each j-box, all of the branch circuits in each suite are romex. The work notes should not say to remove conduit in the suites as there is none.

3. Drawing E1.1, sheet work note 5 says day room fixtures are to remain, while being cleaned and re-lamped. There are some existing fixtures in the other rooms that are to remain. Are they to be cleaned and relamped also?

RESPONSE: Each existing fixture to remain in the building shall be cleaned and re-lamped.

4. Specification 260519 3.6 A.B.C. are for testing on conductors. What NETA section applies, and for which conductors?

RESPONSE: NETA Section 7.3.2 for all conductors being installed.

5. Demo sheets E1.1, E1.2 and E1.3. In the entry way to each dorm unit the symbol for a manual motor starter (Sm) is shown. Are we in fact removing a manual motor starter or is this supposed to be a regular switch (S)?

RESPONSE: This is light and solid which indicates that this manual motor starter is existing. There is no work to be done to this.

Clarification: The “Unique” closet layout for room 209, 211,309, and 311 are shown incorrectly on the plan layout sheets. Currently, it shows the “Unique” closet floor plan as being different from the “Typical”. The “Unique” layouts should be similar to the “Typical” plan layout and elevations; the exception will be in the dimensions of the cabinets and adjustment of the rod. The "Unique" closets will need to have the cabinets altered from approximately 2’-6” to 2’-0”-It is the contractors responsibility to verify all dimensions. ALL CLOSEST WILL NEED TO BE CUSTOM FITTED AND DIMENSIONS FIELD VERIFIED since the closets –both "Typical" and "Unique"- vary slightly in layout and dimension.

Clarification: The note on “Finishing’s” located on Sheet A5.1 under General Notes. This note applies only to the beds, tables, and chairs.