Questions 1.docx
DOCX document 13 KB Posted
- Attached to
- Remodel Dorm 740 Federal contract opportunity
- Solicitation number
- FA4626-10-R-0021
About this file
Questions and Answers (1)
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questioins and Answers 7.docx | DOCX document | |
| Questions and Answers 6.docx | DOCX document | |
| BIRD COVE DETAIL.pdf | ||
| Questions and Answers 5.docx | DOCX document | |
| Questions and Answers 4.docx | DOCX document | |
| Amendment 0002.doc | DOC document | |
| 085113-revised on Sept 9 2010.doc | DOC document | |
| TOC.Revise.9-9-2010doc.doc | DOC document | |
| Amendment 0001.doc | DOC document | |
| 010100-Revised.9-9-2010.doc | DOC document | |
| Question and Answers 3.docx | DOCX document | |
| Questions 2.docx | DOCX document | |
| 740 Site Visit.pdf | ||
| Attach 1 Specifications.zip | ZIP file | |
| Attach 2 Material Submital.xlsx | XLSX spreadsheet | |
| Attch 3 Schedule of Drawings.DOC | DOC document | |
| Attach 5 Wage Determination Heavy.docx | DOCX document | |
| Attach 5 Wage Determination Building.docx | DOCX document | |
| Attch 4 Drawings.zip | ZIP file | |
| Solicitation.doc | DOC document | |
| Attch 6 Past Performance Questionnaire.docx | DOCX document | |
| Attch 7 - Subcontractor Consent Form - 10R0027.docx | DOCX document |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Sheet A0.1, the first item in the legend states remove gyp. bd. from wall. West of suite 102 on grid line 2 and west of grid line d the western most wall shows the gyp. bd. being demoed. Sheet A1.1 shows that wall as a wall type E which states gyp. bd. to remain . Please CLARIFY what gyp. bd. gets demoed and stays between the demo sheets and the floor plan sheets. RESPONSE: Those walls have the sheet rock demoed and replaced. The description is wall type "E4" -note the "4" at the lower right corner of the triangle- which states to demo and replace.
2. Many of the sheet work notes on E1.1 call out for demolition of conducters and conduit in the rooms. Do these rooms have conduit in them, or romex, or a combination of both?
RESPONSE: Each typical/non-typical suite has a j-box in the ceiling space of the hallway between the sleeping rooms of each suite. There is conduit, as noted on plans, from this j-box back to corresponding panelboard. From each j-box, all of the branch circuits in each suite are romex. The work notes should not say to remove conduit in the suites as there is none.
3. Drawing E1.1, sheet work note 5 says day room fixtures are to remain, while being cleaned and re-lamped. There are some existing fixtures in the other rooms that are to remain. Are they to be cleaned and relamped also?
RESPONSE: Each existing fixture to remain in the building shall be cleaned and re-lamped.
4. Specification 260519 3.6 A.B.C. are for testing on conductors. What NETA section applies, and for which conductors?
RESPONSE: NETA Section 7.3.2 for all conductors being installed.
5. Demo sheets E1.1, E1.2 and E1.3. In the entry way to each dorm unit the symbol for a manual motor starter (Sm) is shown. Are we in fact removing a manual motor starter or is this supposed to be a regular switch (S)?
RESPONSE: This is light and solid which indicates that this manual motor starter is existing. There is no work to be done to this.
Clarification: The “Unique” closet layout for room 209, 211,309, and 311 are shown incorrectly on the plan layout sheets. Currently, it shows the “Unique” closet floor plan as being different from the “Typical”. The “Unique” layouts should be similar to the “Typical” plan layout and elevations; the exception will be in the dimensions of the cabinets and adjustment of the rod. The "Unique" closets will need to have the cabinets altered from approximately 2’-6” to 2’-0”-It is the contractors responsibility to verify all dimensions. ALL CLOSEST WILL NEED TO BE CUSTOM FITTED AND DIMENSIONS FIELD VERIFIED since the closets –both "Typical" and "Unique"- vary slightly in layout and dimension.
Clarification: The note on “Finishing’s” located on Sheet A5.1 under General Notes. This note applies only to the beds, tables, and chairs.