This document is the Salient Characteristics for Uninterruptable Power Supplies (UPS) required by the 92nd Communications Squadron at Fairchild Air Force Base. It specifies the technical requirements for two sizes of UPS systems - a 5kVA UPS and a 1.5kVA UPS - as well as compatible external battery packs and network management cards. Key details include:

The 5kVA UPS must have 208V AC input, 208V AC 60Hz output, at least 2 NEMA L6-30 output receptacles, a maximum depth of 29 inches, a maximum rack height of 7U, and a minimum runtime of 10 minutes on battery at full load without external batteries. It must be rack mountable, have hot-swappable and replaceable batteries, and be capable of external battery connection. The UPS and external batteries must be TAA compliant.

The 1.5kVA UPS must have 120V AC 60Hz input and output, at least 6 NEMA 5-15 output receptacles, a maximum depth of 29 inches, a maximum rack height of 4U, and a minimum runtime of 6.5 minutes on battery at full load. It must be rack mountable, have replaceable batteries, and be TAA compliant. A TAA compliant network management card is required if the UPS model does not have one pre-installed.

These salient characteristics are referenced in Solicitation Number FA462024QA221 for Uninterrupted Power Supply (UPS) systems and accessories issued by the 92nd Communications Squadron of the Department of the Air Force Air Mobility Command.

View the file

Other files for this federal contract opportunity

Other files attached to Uninterrupted Power Supply (UPS), newest first.
File Type Posted
Amend 0004 Attach 1 Salient Characteristics.pdf PDF
Amend 0004 SF30.pdf PDF
Amend 0003 SF30.pdf PDF
Amend 0003 Attach 1 Salient Characteristics.pdf PDF
Amend 0002 Attach 1 Salient Characteristics.pdf PDF
Amend 0002 24QA221 Combo.pdf PDF
Amend 0002 SF30.pdf PDF
Amendment 0001.pdf PDF
Amend 0001 - 24QA221 Combo 3 Apr 2024.pdf PDF
Amend 0001 - 24QA221 Combo.pdf PDF
Attach. 1 - Salient Characteristics.pdf PDF
24QA221 Combo.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES

PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real‐time health monitoring remotely.

The UPS will have the following salient characteristics:

5K UPS:

• Input Voltage 208V AC 1 Phase 60Hz

• Input Plug Type NEMA L6‐30

• Output voltage 208V AC 60HZ

• Output Power 5.0k VA

• Output receptacles at least 2 NEMA L6-30

• Maximum Depth: 29”

• Maximum Rack Height: 7U

• Form Factor: Rack Mountable

• Backup/Runtime (Full Load) without external batteries: 10 minutes

• Hot Swappable: Yes

• Replaceable Battery: Yes

• External Battery capable: Yes

• Network Management: SNMP capable or pre‐installed one.

• Line Interactive

• TAA Compliant

External Batteries:

Maximum Depth: 29”

Maximum Rack Height: 4U

Form Factor: Rack Mountable

Minimum Battery Life: 4 years

Compatible with selected 5K UPS

TAA Compliant

1K UPS:

Maximum Depth: 29 ”

Maximum Rack Height: 4U

Input Voltage 120V AC 60HZ

Input Plug Type NEMA L5‐15

Output Voltage 120V AC 60HZ

Output Power minimum 1.5k VA

Output receptacles at least 6 NEMA 5‐15

Form Factor: Rack Mountable

Replaceable Battery: Yes

Backup/Run Time (Full Load): 6.5 minutes

FA462024QA221

Attach. 1 - Salient Characteristics (Amend 0004)

Network Management: SNMP capable expansion port or pre‐installed one.

Line Interactive

TAA Compliant

Network Management Card:

Supports SNMP over TCP/IP

Compatible with selected 5K UPS

Only needed if model of 5K UPS does not have one pre‐installed

TAA Compliant