Amend 0004 Attach 1 Salient Characteristics.pdf
PDF 725 KB Posted
- Attached to
- Uninterrupted Power Supply (UPS) Federal contract opportunity
- Solicitation number
- FA462024QA221
About this file
This document is the Salient Characteristics for Uninterruptable Power Supplies (UPS) required by the 92nd Communications Squadron at Fairchild Air Force Base. It specifies the technical requirements for two sizes of UPS systems - a 5kVA UPS and a 1.5kVA UPS - as well as compatible external battery packs and network management cards. Key details include:
The 5kVA UPS must have 208V AC input, 208V AC 60Hz output, at least 2 NEMA L6-30 output receptacles, a maximum depth of 29 inches, a maximum rack height of 7U, and a minimum runtime of 10 minutes on battery at full load without external batteries. It must be rack mountable, have hot-swappable and replaceable batteries, and be capable of external battery connection. The UPS and external batteries must be TAA compliant.
The 1.5kVA UPS must have 120V AC 60Hz input and output, at least 6 NEMA 5-15 output receptacles, a maximum depth of 29 inches, a maximum rack height of 4U, and a minimum runtime of 6.5 minutes on battery at full load. It must be rack mountable, have replaceable batteries, and be TAA compliant. A TAA compliant network management card is required if the UPS model does not have one pre-installed.
These salient characteristics are referenced in Solicitation Number FA462024QA221 for Uninterrupted Power Supply (UPS) systems and accessories issued by the 92nd Communications Squadron of the Department of the Air Force Air Mobility Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amend 0004 Attach 1 Salient Characteristics.pdf | ||
| Amend 0004 SF30.pdf | ||
| Amend 0003 SF30.pdf | ||
| Amend 0003 Attach 1 Salient Characteristics.pdf | ||
| Amend 0002 Attach 1 Salient Characteristics.pdf | ||
| Amend 0002 24QA221 Combo.pdf | ||
| Amend 0002 SF30.pdf | ||
| Amendment 0001.pdf | ||
| Amend 0001 - 24QA221 Combo 3 Apr 2024.pdf | ||
| Amend 0001 - 24QA221 Combo.pdf | ||
| Attach. 1 - Salient Characteristics.pdf | ||
| 24QA221 Combo.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES
PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real‐time health monitoring remotely.
The UPS will have the following salient characteristics:
5K UPS:
• Input Voltage 208V AC 1 Phase 60Hz
• Input Plug Type NEMA L6‐30
• Output voltage 208V AC 60HZ
• Output Power 5.0k VA
• Output receptacles at least 2 NEMA L6-30
• Maximum Depth: 29”
• Maximum Rack Height: 7U
• Form Factor: Rack Mountable
• Backup/Runtime (Full Load) without external batteries: 10 minutes
• Hot Swappable: Yes
• Replaceable Battery: Yes
• External Battery capable: Yes
• Network Management: SNMP capable or pre‐installed one.
• Line Interactive
• TAA Compliant
External Batteries:
Maximum Depth: 29”
Maximum Rack Height: 4U
Form Factor: Rack Mountable
Minimum Battery Life: 4 years
Compatible with selected 5K UPS
TAA Compliant
1K UPS:
Maximum Depth: 29 ”
Maximum Rack Height: 4U
Input Voltage 120V AC 60HZ
Input Plug Type NEMA L5‐15
Output Voltage 120V AC 60HZ
Output Power minimum 1.5k VA
Output receptacles at least 6 NEMA 5‐15
Form Factor: Rack Mountable
Replaceable Battery: Yes
Backup/Run Time (Full Load): 6.5 minutes
FA462024QA221
Attach. 1 - Salient Characteristics (Amend 0004)
Network Management: SNMP capable expansion port or pre‐installed one.
Line Interactive
TAA Compliant
Network Management Card:
Supports SNMP over TCP/IP
Compatible with selected 5K UPS
Only needed if model of 5K UPS does not have one pre‐installed
TAA Compliant
FA462024QA221
Attach. 1 - Salient Characteristics (Amend 0003)