Amend 0004 Attach 1 Salient Characteristics.pdf
PDF 712 KB Posted
- Attached to
- Uninterrupted Power Supply (UPS) Federal contract opportunity
- Solicitation number
- FA462024QA221
About this file
This document consists of the salient characteristics for uninterruptible power supplies (UPS) and related external batteries required under Solicitation FA462024QA221 issued by the Department of the Air Force Air Mobility Command. The 5kVA UPS must have an input voltage of 208V AC, 1-phase, 60Hz and provide 120V AC, 60Hz output power of at least 5,000VA with a minimum of 8 NEMA 5-15/5-20 receptacles. The UPS must be rack-mountable, support network management via SNMP, and provide at least 10 minutes of backup power at full load. The 1kVA UPS must have similar requirements but with a 120V AC, 60Hz input and output, at least 6 NEMA 5-15 receptacles, and 6.5 minutes of backup power at full load. Both the 5kVA and 1kVA UPS, as well as any required external batteries, must be TAA-compliant. The document provides detailed specifications for the salient characteristics of the required UPS systems and accessories.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amend 0004 Attach 1 Salient Characteristics.pdf | ||
| Amend 0004 SF30.pdf | ||
| Amend 0003 SF30.pdf | ||
| Amend 0003 Attach 1 Salient Characteristics.pdf | ||
| Amend 0002 SF30.pdf | ||
| Amend 0002 Attach 1 Salient Characteristics.pdf | ||
| Amend 0002 24QA221 Combo.pdf | ||
| Amendment 0001.pdf | ||
| Amend 0001 - 24QA221 Combo 3 Apr 2024.pdf | ||
| Amend 0001 - 24QA221 Combo.pdf | ||
| Attach. 1 - Salient Characteristics.pdf | ||
| 24QA221 Combo.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES
PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real‐time health monitoring remotely.
The UPS will have the following salient characteristics:
5K UPS:
Input Voltage 208V AC 1 Phase 60Hz
Input Plug Type NEMA L6‐30
Output voltage 120V AC 60HZ
Output Power 5.0k VA
Output receptacles at least 8 NEMA 5‐15/5‐20
Maximum Depth: 29”
Maximum Rack Height: 7U
Form Factor: Rack Mountable
Backup/Runtime (Full Load) without external batteries: 10 minutes
Hot Swappable: Yes
Replaceable Battery: Yes
External Battery capable: Yes
Network Management: SNMP capable or pre‐installed one.
Line Interactive
TAA Compliant
External Batteries:
Maximum Depth: 29”
Maximum Rack Height: 4U
Form Factor: Rack Mountable
Minimum Battery Life: 4 years
Compatible with selected 5K UPS
TAA Compliant
1K UPS:
Maximum Depth: 29 ”
Maximum Rack Height: 4U
Input Voltage 120V AC 60HZ
Input Plug Type NEMA L5‐15
Output Voltage 120V AC 60HZ
Output Power minimum 1.5k VA
Output receptacles at least 6 NEMA 5‐15
Form Factor: Rack Mountable
Replaceable Battery: Yes
Backup/Run Time (Full Load): 6.5 minutes
FA462024QA221
Attach. 1 - Salient Characteristics (Amend 0004)
Network Management: SNMP capable expansion port or pre‐installed one.
Line Interactive
TAA Compliant
Network Management Card:
Supports SNMP over TCP/IP
Compatible with selected 5K UPS
Only needed if model of 5K UPS does not have one pre‐installed
TAA Compliant
FA462024QA221
Attach. 1 - Salient Characteristics (Amend 0004)
File details come from the government source that posted it. Updated .