Amend 0004 Attach 1 Salient Characteristics.pdf

PDF 712 KB Posted

Attached to
Uninterrupted Power Supply (UPS) Federal contract opportunity
Solicitation number
FA462024QA221
Issued by
Department of the Air Force Air Mobility Command

About this file

This document consists of the salient characteristics for uninterruptible power supplies (UPS) and related external batteries required under Solicitation FA462024QA221 issued by the Department of the Air Force Air Mobility Command. The 5kVA UPS must have an input voltage of 208V AC, 1-phase, 60Hz and provide 120V AC, 60Hz output power of at least 5,000VA with a minimum of 8 NEMA 5-15/5-20 receptacles. The UPS must be rack-mountable, support network management via SNMP, and provide at least 10 minutes of backup power at full load. The 1kVA UPS must have similar requirements but with a 120V AC, 60Hz input and output, at least 6 NEMA 5-15 receptacles, and 6.5 minutes of backup power at full load. Both the 5kVA and 1kVA UPS, as well as any required external batteries, must be TAA-compliant. The document provides detailed specifications for the salient characteristics of the required UPS systems and accessories.

View the file

Other files for this federal contract opportunity

Other files attached to Uninterrupted Power Supply (UPS), newest first.
File Type Posted
Amend 0004 Attach 1 Salient Characteristics.pdf PDF
Amend 0004 SF30.pdf PDF
Amend 0003 SF30.pdf PDF
Amend 0003 Attach 1 Salient Characteristics.pdf PDF
Amend 0002 SF30.pdf PDF
Amend 0002 Attach 1 Salient Characteristics.pdf PDF
Amend 0002 24QA221 Combo.pdf PDF
Amendment 0001.pdf PDF
Amend 0001 - 24QA221 Combo 3 Apr 2024.pdf PDF
Amend 0001 - 24QA221 Combo.pdf PDF
Attach. 1 - Salient Characteristics.pdf PDF
24QA221 Combo.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES

PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real‐time health monitoring remotely.

The UPS will have the following salient characteristics:

5K UPS:

Input Voltage 208V AC 1 Phase 60Hz

Input Plug Type NEMA L6‐30

Output voltage 120V AC 60HZ

Output Power 5.0k VA

Output receptacles at least 8 NEMA 5‐15/5‐20

Maximum Depth: 29”

Maximum Rack Height: 7U

Form Factor: Rack Mountable

Backup/Runtime (Full Load) without external batteries: 10 minutes

Hot Swappable: Yes

Replaceable Battery: Yes

External Battery capable: Yes

Network Management: SNMP capable or pre‐installed one.

Line Interactive

TAA Compliant

External Batteries:

Maximum Depth: 29”

Maximum Rack Height: 4U

Form Factor: Rack Mountable

Minimum Battery Life: 4 years

Compatible with selected 5K UPS

TAA Compliant

1K UPS:

Maximum Depth: 29 ”

Maximum Rack Height: 4U

Input Voltage 120V AC 60HZ

Input Plug Type NEMA L5‐15

Output Voltage 120V AC 60HZ

Output Power minimum 1.5k VA

Output receptacles at least 6 NEMA 5‐15

Form Factor: Rack Mountable

Replaceable Battery: Yes

Backup/Run Time (Full Load): 6.5 minutes

FA462024QA221

Attach. 1 - Salient Characteristics (Amend 0004)

Network Management: SNMP capable expansion port or pre‐installed one.

Line Interactive

TAA Compliant

Network Management Card:

Supports SNMP over TCP/IP

Compatible with selected 5K UPS

Only needed if model of 5K UPS does not have one pre‐installed

TAA Compliant

FA462024QA221

Attach. 1 - Salient Characteristics (Amend 0004)