Amend 0002 Attach 1 Salient Characteristics.pdf

PDF 659 KB Posted

Attached to
Uninterrupted Power Supply (UPS) Federal contract opportunity
Solicitation number
FA462024QA221
Issued by
Department of the Air Force Air Mobility Command

About this file

This document contains the salient characteristics for uninterruptible power supply (UPS) systems and accessories required under Solicitation FA462024QA221 issued by the Department of the Air Force Air Mobility Command. The solicitation seeks 5kVA and 1kVA UPS systems with specific technical requirements, including input voltage, output voltage and receptacles, form factor, runtime, battery capabilities, and network management features. The 5kVA UPS must have a 10-minute backup time at full load without external batteries, while the 1kVA UPS must have a 6.5-minute backup time. Both UPS systems must be rack-mountable with a maximum depth of 29 inches. The solicitation also requires compatible rack-mountable line interactive external battery systems. The document provides detailed salient characteristics for the required UPS and battery systems.

View the file

Other files for this federal contract opportunity

Other files attached to Uninterrupted Power Supply (UPS), newest first.
File Type Posted
Amend 0004 Attach 1 Salient Characteristics.pdf PDF
Amend 0004 Attach 1 Salient Characteristics.pdf PDF
Amend 0004 SF30.pdf PDF
Amend 0003 SF30.pdf PDF
Amend 0003 Attach 1 Salient Characteristics.pdf PDF
Amend 0002 SF30.pdf PDF
Amend 0002 24QA221 Combo.pdf PDF
Amendment 0001.pdf PDF
Amend 0001 - 24QA221 Combo 3 Apr 2024.pdf PDF
Amend 0001 - 24QA221 Combo.pdf PDF
Attach. 1 - Salient Characteristics.pdf PDF
24QA221 Combo.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES

PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real-time health monitoring remotely.

The UPS will have the following salient characteristics:

5K UPS:

• Input Voltage 208V AC 3 Phase 60Hz

• Input Plug Type NEMA L6-30

• Output voltage 120V AC 60HZ

• Output Power 5.0k VA

• Output receptacles at least 8 NEMA 5-15/5-20

• Maximum Depth: 29”

• Maximum Rack Height: 7U

• Form Factor: Rack Mountable

• Backup/Runtime (Full Load) without external batteries: 10 minutes

• Hot Swappable: Yes

• Replaceable Battery: Yes

• External Battery capable: Yes

• Network Management: SNMP capable or pre-installed one.

• Line Interactive

External Batteries:

• Maximum Depth: 29”

• Maximum Rack Height: 4U

• Form Factor: Rack Mountable

• Minimum Battery Life: 4 years

• Compatible with selected 5K UPS

1K UPS:

• Maximum Depth: 29 ”

• Maximum Rack Height: 4U

• Input Voltage 120V AC 60HZ

• Input Plug Type NEMA L5-15

• Output Voltage 120 V AC 60HZ

• Output Power minimum 1.5k VA

• Output receptacles at least 6 NEMA 5-15

• Form Factor: Rack Mountable

• Replaceable Battery: Yes

• Backup/Run Time (Full Load): 6.5 minutes

FA462024QA221

Attach 1. Salient Characteristics (Amend 0002)

• Network Management: SNMP capable expansion port or pre-installed one.

• Line Interactive

Network Management Card:

• Supports SNMP over TCP/IP

• Compatible with selected 5K UPS

• Only needed if model of 5K UPS does not have one pre-installed

FA462024QA221

Attach 1. Salient Characteristics (Amend 0002)