Amend 0003 Attach 1 Salient Characteristics.pdf

PDF 729 KB Posted

Attached to
Uninterrupted Power Supply (UPS)
Solicitation number
FA462024QA221
Issued by

About this file

This document outlines the salient characteristics for Uninterruptible Power Supply (UPS) systems required under Solicitation Number FA462024QA221 issued by the Department of the Air Force Air Mobility Command. The solicitation seeks 5KVA and 1KVA UPS systems and related accessories to provide continuous, regulated power to network devices at Fairchild Air Force Base during power outages.

The 5KVA UPS must have an input voltage of 208V AC, 1 phase, 60Hz and a NEMA L630 plug type. It shall provide 120V AC, 60Hz output power of at least 5.0kVA, with a minimum of 8 NEMA 515/520 receptacles. The UPS must be rack mountable, have a maximum depth of 29 inches, and a maximum height of 7U. It shall provide at least 10 minutes of backup runtime at full load without external batteries, with hot-swappable and replaceable batteries, and external battery capability. The UPS must be SNMP capable and Line Interactive. Compatible rack-mountable 4U external batteries with a minimum 4-year life are also required. The 1KVA UPS has similar requirements but a 120V AC, 60Hz input with a NEMA L515 plug, 1.5kVA output, 6 NEMA 515 receptacles, and a minimum 6.5 minutes of backup at full load. An optional SNMP-capable network management card is required if not pre-installed.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES

PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real‐time health monitoring remotely.

The UPS will have the following salient characteristics:

5K UPS:

Input Voltage 208V AC 1 Phase 60Hz

Input Plug Type NEMA L6‐30

Output voltage 120V AC 60HZ

Output Power 5.0k VA

Output receptacles at least 8 NEMA 5‐15/5‐20

Maximum Depth: 29”

Maximum Rack Height: 7U

Form Factor: Rack Mountable

Backup/Runtime (Full Load) without external batteries: 10 minutes

Hot Swappable: Yes

Replaceable Battery: Yes

External Battery capable: Yes

Network Management: SNMP capable or pre‐installed one.

Line Interactive

TAA Compliant

External Batteries:

Maximum Depth: 29”

Maximum Rack Height: 4U

Form Factor: Rack Mountable

Minimum Battery Life: 4 years

Compatible with selected 5K UPS

TAA Compliant

1K UPS:

Maximum Depth: 29 ”

Maximum Rack Height: 4U

Input Voltage 120V AC 60HZ

Input Plug Type NEMA L5‐15

Output Voltage 120V AC 60HZ

Output Power minimum 1.5k VA

Output receptacles at least 6 NEMA 5‐15

Form Factor: Rack Mountable

Replaceable Battery: Yes

Backup/Run Time (Full Load): 6.5 minutes

FA462024QA221

Attach. 1 - Salient Characteristics (Amend 0003)

Network Management: SNMP capable expansion port or pre‐installed one.

Line Interactive

TAA Compliant

Network Management Card:

Supports SNMP over TCP/IP

Compatible with selected 5K UPS

Only needed if model of 5K UPS does not have one pre‐installed

TAA Compliant

FA462024QA221

Attach. 1 - Salient Characteristics (Amend 0003)

File details come from the government source that posted it. Updated .