The provided document is the Salient Characteristics for Uninterruptible Power Supply (UPS) systems required under Solicitation FA462024QA221. The key details are:
The 92nd Communications Squadron at Fairchild AFB has a requirement for 14 units of 5K UPS, 140 units of 1K UPS, 18 external batteries, and 5 network management cards. The 5K UPS units must have a maximum depth of 29", maximum height of 8.75", 5U rack height, maximum weight of 125 lbs, and provide 10 minutes of backup power at full load or 26 minutes at half load. The 1K UPS units must have a maximum depth of 29", maximum height of 3.5", 2U rack height, maximum weight of 70 lbs, and provide 6.5 minutes of backup power at full load. The network management cards must be SNMP-capable and compatible with the 5K UPS. All equipment must be rack-mountable. The external batteries must have a minimum 4-year lifespan and provide 192V DC output.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amend 0004 Attach 1 Salient Characteristics.pdf | ||
| Amend 0004 Attach 1 Salient Characteristics.pdf | ||
| Amend 0004 SF30.pdf | ||
| Amend 0003 SF30.pdf | ||
| Amend 0003 Attach 1 Salient Characteristics.pdf | ||
| Amend 0002 SF30.pdf | ||
| Amend 0002 Attach 1 Salient Characteristics.pdf | ||
| Amend 0002 24QA221 Combo.pdf | ||
| Amend 0001 - 24QA221 Combo 3 Apr 2024.pdf | ||
| Amendment 0001.pdf | ||
| Amend 0001 - 24QA221 Combo.pdf | ||
| 24QA221 Combo.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
FOR
Uninterrupted Power Supply (UPS)
January 2024
FA462024QA221
Attach. 1 - Salient Characteristics
SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES
PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real-time health monitoring remotely.
Item Quan�ty
5K UPS 14
External Batteries 18
1K UPS 140
Network Management Card 5
The UPS will have the following salient characteristics:
5K UPS:
• Maximum Depth: 29”
• Maximum Height: 8.75”
• Rack Height: 5U
• Maximum Weight: 125 lbs
• Form Factor: Rack Mountable
• Backup/Runtime (Full Load): 10 minutes
• Backup/Runtime (Half Load): 26 minutes
• DC System Voltage: 192V DC
• Hot Swappable: Yes
• Replaceable Battery: Yes
• Network Management: SNMP capable expansion port
External Batteries:
• Maximum Depth: 29”
• Maximum Height: 3.5”
• Rack Height: 2U
• Form Factor: Rack Mountable
• Minimum Battery Life: 4 years
• Output Voltage: 192 V DC
FA462024QA221
1K UPS:
• Maximum Depth: 29”
• Maximum Height: 3.5”
• Maximum Weight: 70 lbs
• Rack Height: 2U
• Form Factor: Rack Mountable
• Backup/Run Time (Full Load): 6.5 minutes
• Network Management: SNMP capable expansion port
Network Management Card:
• Supports SNMP over TCP/IP
• Compatible with selected 5K UPS
• Only needed if model of 5K UPS does not have one pre-installed