Attach. 1 - Salient Characteristics.pdf

PDF 708 KB Posted

Attached to
Uninterrupted Power Supply (UPS)
Solicitation number
FA462024QA221
Issued by

About this file

The provided document is the Salient Characteristics for Uninterruptible Power Supply (UPS) systems required under Solicitation FA462024QA221. The key details are:

The 92nd Communications Squadron at Fairchild AFB has a requirement for 14 units of 5K UPS, 140 units of 1K UPS, 18 external batteries, and 5 network management cards. The 5K UPS units must have a maximum depth of 29", maximum height of 8.75", 5U rack height, maximum weight of 125 lbs, and provide 10 minutes of backup power at full load or 26 minutes at half load. The 1K UPS units must have a maximum depth of 29", maximum height of 3.5", 2U rack height, maximum weight of 70 lbs, and provide 6.5 minutes of backup power at full load. The network management cards must be SNMP-capable and compatible with the 5K UPS. All equipment must be rack-mountable. The external batteries must have a minimum 4-year lifespan and provide 192V DC output.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

FOR

Uninterrupted Power Supply (UPS)

January 2024

FA462024QA221

Attach. 1 - Salient Characteristics

SALIENT CHARACTERISTICS FOR UNINTERRUPTABLE POWER SUPPLIES

PURPOSE: Uninterruptable Power Supplies (UPS) are used to provide continuous, regulated power to network devices on Fairchild AFB during power outages. Network Cards are added into the UPS to provide real-time health monitoring remotely.

Item Quan�ty

5K UPS 14

External Batteries 18

1K UPS 140

Network Management Card 5

The UPS will have the following salient characteristics:

5K UPS:

• Maximum Depth: 29”

• Maximum Height: 8.75”

• Rack Height: 5U

• Maximum Weight: 125 lbs

• Form Factor: Rack Mountable

• Backup/Runtime (Full Load): 10 minutes

• Backup/Runtime (Half Load): 26 minutes

• DC System Voltage: 192V DC

• Hot Swappable: Yes

• Replaceable Battery: Yes

• Network Management: SNMP capable expansion port

External Batteries:

• Maximum Depth: 29”

• Maximum Height: 3.5”

• Rack Height: 2U

• Form Factor: Rack Mountable

• Minimum Battery Life: 4 years

• Output Voltage: 192 V DC

FA462024QA221

1K UPS:

• Maximum Depth: 29”

• Maximum Height: 3.5”

• Maximum Weight: 70 lbs

• Rack Height: 2U

• Form Factor: Rack Mountable

• Backup/Run Time (Full Load): 6.5 minutes

• Network Management: SNMP capable expansion port

Network Management Card:

• Supports SNMP over TCP/IP

• Compatible with selected 5K UPS

• Only needed if model of 5K UPS does not have one pre-installed

FA462024QA221

24QA221 Salient Characteristics.pdf
SALIENT CHARACTERISTICS final.pdf

File details come from the government source that posted it. Updated .