Attachment 6 - Asbestos Inspection.pdf
PDF 3 MB Posted
- Attached to
- CCTV - BLDG 241
- Solicitation number
- FA461325Q0015
About this file
This is an Asbestos Inspection Report for F.E. Warren Air Force Base Building #231 in Cheyenne, Wyoming, conducted by Asbestos & Technical Services, Inc. on May 10, 2021. The comprehensive inspection involved collecting 23 bulk samples across the basement, first floor, second floor, and attic levels to test for asbestos-containing materials (ACM) and lead-based paint.
The laboratory analysis by CA Labs revealed no asbestos detected in any of the samples, which included various materials such as drywall, plaster, popcorn texture, and brick mortar. For lead testing, one sample (L1 - off-white paint on red paint on brick in the basement northeast area) exhibited a strong color change, indicating the potential presence of lead-based paint. The report recommends that if suspect materials are discovered during future renovation or demolition, work should be stopped and the materials tested prior to proceeding.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos & Technical Services, Inc P.O. Box 2574
Cheyenne, WY 82003
307-214-0904
Asbestos Inspection Report
May 18, 2021
F.E. Warren A.F.B
Project: B241
Cheyenne, WY 82001
Dear F.E. Warren A.F.B., On May 10, 2021, ATS performed an asbestos inspection for the property listed above. The purpose of the survey is to identify asbestos containing material (ACM) using nondestructive sampling protocols.
Inspection, sampling and analytical procedures were performed in general accordance with the Environmental Protection
Agency’s (EPA) interpretations, and guidelines of the Asbestos Hazardous Emergency Response Act (AHERA).
Asbestos containing materials as defined by the Occupational Safety and Health Administration (OSHA), the Environmental
Protection Agency and the State of Wyoming are material with asbestos concentration greater than 1% (>1%) by volume.
However, OSHA governs asbestos exposures to employees above the Permissible Exposure Limit regardless of asbestos containing material concentration.
No inspection can eliminate the uncertainty regarding the presence of ACM. ATS’s level of diligence and investigative procedures are intended to reduce, but not eliminate potential uncertainty regarding the presence of ACM. The determinations in this report should not be constructed as a guarantee that all ACM present in the subject property has been included in this report.
The inspection was performed in a manner consistent with the level of care and expertise exercised by members of the asbestos inspection and assessment profession. Those entities and persons involved with the inspection and generation of this report do not imply or guarantee that all potential ACM on or in the building has been identified and sampled.
Historically, asbestos has been added as a component to over 3,000 materials and products produced in the United States.
The inspection was intended to identify those accessible materials that were reasonable suspect and that were most likely to contain asbestos in quantities subject to regulation, based on existing industry and regulatory standards.
If suspect material is discovered during renovation or demolition, work needs to be stopped and suspect material needs to be tested prior to proceeding.
Total samples taken: 23
FIELD NOTES AND SAMPLE LOCATIONS:
Sample #/Description Location:
Basement
• 051021-B241-1 Drywall on ceiling Northeast
• 051021-B241-2 Drywall on ceiling Northeast
• 051021-B241-3 Brick mortar for red brick wall Northeast
• 051021-B241-4 Plaster and skim coat East
• 051021-B241-5 Plaster and stucco texture East
• 051021-B241-6 Plaster ceiling Northwest
• 051021-B241-7 Plaster and troweled texture West
First Floor
• 051021-B241-8 Popcorn on plaster #108
• 051021-B241-9 Drywall and orange peel texture #108
• 051021-B241-10 Plaster and smooth texture, wall Bathroom
• 051021-B241-11 Plaster ceiling, smooth texture Bathroom
• 051021-B241-12 Texture on drywall Laundry Room
• 051021-B241-13 Popcorn on plaster Laundry Room
Second Floor
• 051021-B241-14 Texture on drywall Hall #208
• 051021-B241-15 Plaster (Attic)
• 051021-B241-16 Texture on drywall #212
• 051021-B241-17 Popcorn texture #212
• 051021-B241-18 Texture on drywall #212
• 051021-B241-19 Textured drywall #217
• 051021-B241-20 Popcorn on drywall #202
• 051021-B241-21 Textured drywall #202
First Floor
• 051021-B241-22 Popcorn on drywall ceiling Stairs
• 051021-B241-23 Textured drywall Stairs
FINDINGS:
None of the samples collected above were found to contain asbestos. Please refer to the attached CA Lab results and contact ATS if you have any questions.
Lead Inspection
The purpose of this inspection is to identify and assess the lead-based (LBP) present on specified painted components at the subject property.
3M™ LeadCheck™ Swabs are EPA recognized when used by a certified renovator to determine if lead-based paint is present on wood and metal. When lead is detected, 3M™ LeadCheck™ Swabs and/or the surface being tested turns pink or red depending on the concentration of lead present. In the vast majority of test situations results are obtained in less than
30 seconds. When detecting low levels of lead, or lead chromate containing pigments, results may take longer to develop.
The results of swab testing are not quantitative.
Total samples taken on May 10, 2021: 9
Lead Analysis Location: Color Change:
• Sample # L1 – Off-white paint on red paint on brick Basement- Northeast YES
• Sample # L2 – Grey paint on wall Basement- East NO
• Sample # L3 – Tan paint on metal Basement- East NO
• Sample # L4 – Green paint on wall Basement- North NO
• Sample # L5 – Silver paint on brick Basement- North NO
• Sample # L6 – Tan paint on drywall First Floor- #108 NO
• Sample # L7 – Tan paint on drywall First Floor-Restroom NO
• Sample # L8 – Off-white paint on wood rafter (shiny) Attic NO
• Sample # L9 – Off-white paint on wood rafter Attic NO
Testing Method: 3M Lead Test (swab) Kits
Results:
After a 10-minute wait time, sample L1 (paint on brick)) exhibited a strong color change and should be assumed to be lead paint.
Background for Lead Test Kits:
On April 22, 2008, EPA published the Lead Renovation, Repair and Painting (RRP) rule, which, among other things, established performance recognition criteria for lead test kits for use as an option to determine if regulated lead-based paint is not present in target housing and child-occupied facilities. Currently, the EPA is reviewing the application and expansion of the RRP rule to include public and commercial buildings.
According to the EPA, the use of an EPA-recognized lead test kit, when used by a trained professional, can reliably determine that regulated lead-based paint is not present by virtue of a negative result. The EPA recognizes that when used by a Certified Renovator, the 3M™ LeadCheck™ lead test kit can reliably determine that regulated lead-based paint is not present on wood, ferrous metal (alloys that contain iron), or drywall and plaster surfaces. The results of swab testing are not quantitative. A positive result may indicate the presence of lead-based paint and should be dealt with by an EPA- RRP contractor or certified Lead Abatement firm.
Please feel free to contact me with any questions.
Sincerely, Nate Challenger
Asbestos Building Inspector
Asbestos & Technical Services, Inc
307-214-0904
Produced with a Trial Version of PDF Annotator - www.PDFAnnotator.com
Customer Project:
Reference #: Date: 05/14/21
Analysis and Method
Discussion
Qualifications
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Materials Characterization - Bulk Asbestos Analysis Laboratory Analysis Report - Polarized Light
Asbestos & Technical Services
P.O. Box 2574
Cheyenne, WY 82003 051021-241, FE Warren B241 Cheyenne, WY
CAL21054456AG
Summary of polarized light microscopy (PLM / Stereomicroscopy bulk asbestos analysis) using the methods described in 40CFR Part 763
Appendix E to Subpart E (Interim and EPA 600 / R-93 / 116 (Improved). The sample is first viewed with the aid of a stereomicroscope. Numerous liquid slide preparations are created for analysis under the polarized microscope where identifications and quantifications are preformed. Calibrated liquid refractive oils are used as liquid mouting medium. These oils are used for identification (dispersion staining). A calibrated visual estimation is reported, should any asbestiform mineral be present. Other techniques such as acid washing are used in conjugation with refractive oils for detection of smaller quantities of asbestos. All asbestos percentages are based on calibrated visual estimation traceable to NIST standards for regulated asbestos. Traceability to measurement and calibration is achieved by using known amounts and types of asbestos from standards where analyst and laboratory accuracy are measured. As little as 0.001% asbestos can be detected in favorable samples, while detection in unfavorable samples may approach the detection limit of 0.50% (well above the laboratory definition of trace).
Vermiculite containing samples may contain trace amounts of actinolite/tremolite. When not detected by PLM, these samples should be analyzed using TEM methods and / or water separation techniques. Suspected actinolite/vermiculite presence will be indicated through the sample comment section of this report.
Fibrous talc containing samples may contain a regulated asbestos fiber known as anthophyllite. Under certain conditions the same fiber may actually contain both talc and anthophyllite (a phenomenon called intergrowth). Again, TEM detection methods are recommended. CA Labs PLM report comments will denote suspected amounts of asbestiform anthophyllite with talc, where further analysis is recommended.
Some samples (floor tiles, surfacings, etc.) may contain fibers too small to be detectable by PLM analysis and should be analyzed by TEM bulk protocols.
A "trace asbestos" will be reported if the analyst observes far less than 1% asbestos. CA Labs defines "trace asbestos" as a few fibers detected by the analyst in several preparations and will indicate as such under these circumstances.
Since allowable variation in quantification of samples close to 1% is high, <1% may be reported. Such results are ideal for point counting, and the technique is mandatory for friable samples (NESHAP, Nov. 1990 and clarification letter 8 May 1991) under 1% percent asbestos or "trace asbestos".
In order to make all initial PLM reports issued from CA Labs NESHAP compliant, all <1% asbestos results (except floor tiles) will be point counted at no additional charge.
CA Labs is accredited by the National Voluntary Accreditation Program (NVLAP) for selected test methods for airborne fiber analysis (TEM), and for bulk asbestos fiber analysis (PLM). CA Labs is also accredited by AIHA LAP, LLC. in the PLM asbestos field of testing for Industrial Hygiene. All analysts have completed college courses or hold a degree in a natural science (geology, biology, or environmental science). Recognition by a state professional board in one these disciplines is preferred, but not required. Extensive in-house training programs are used to augment the educational background of the analyst. The Laboratory Director and Quality Manager have received supplemental McCrone Research training for asbestos identification. Analysis performed at Crisp Analytical Labs, LLC 1929 Old Denton Road Carrollton, TX 75006
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929
Labs
A
C
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 1 of 7
Customer Project: 051021-241, FE Warren B241 Cheyenne, WY CA Labs Project #: CAL21054456AG
No Asbestos Detected.
Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Overview of Project Sample Material Containing Asbestos
Laboratory
Sample ID
Sample # Layer # Analysts Physical Description of
Subsample
Asbestos type / calibrated visual estimate percent
List of Affected
Building Material
Types
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 2 of 7
Customer Info: Attn: Customer Project:
Date:
Phone #
Fax #
Alec Treviño Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
CA Labs Project #:
Asbestos & Technical Services 051021-241, FE Warren B241
Cheyenne, WY
CAL21054456AG
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 5/14/2021
2 days Samples Rec'd: 5/12/21 2:30PM
307-214-0904 Date Of Sampling: 5/10/2021
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
44277
051021-241-
1 1-1
Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44277 1-2 white compound (beneath tape) y None Detected 100% qu,mi,ca
44277 1-3 white drywall with brown paper n None Detected 20% ce 80% qu,gy
44278
051021-241-
2 2-1
Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44278 5 2-2
20% ce 80% qu,gy white compound (beneath tape)
3-1
44278 2-3 white drywall with brown paper n None Detected
100% qu,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Mortar/ white surfaced tan plaster n None Detected44279
051021-241-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
10. TEM analysis suggested
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 3 of 7
Phone #
Fax #
Alec Treviño Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
CA Labs Project #:
Asbestos & Technical Services 051021-241, FE Warren B241
Cheyenne, WY
CAL21054456AG
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 5/14/2021
2 days Samples Rec'd: 5/12/21 2:30PM
307-214-0904 Date Of Sampling: 5/10/2021
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
44280
051021-241-
4 4-1
Plaster/ off-white surfaced off-white finishing compound n None Detected 100% qu,mi,bi,ca
44280 4-2 tan plaster y None Detected 100% qu,ca
44281
051021-241-
5 5-1
Plaster/ off-white surfaced off-white finishing compound n None Detected 100% qu,mi,bi,ca
44281 5-2 tan plaster y None Detected 100% qu,ca
44282
051021-241-
6 6-1
100% qu,bi,ca
Plaster/ off-white surfaced tan plaster n None Detected
8-1
100% qu,bi,ca
44283
051021-241-
7 7-1
Plaster/ off-white surfaced tan plaster n None Detected
96% qu,mi,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Popcorn/ white textured surfacing y None Detected 2% ce
2% wo44284
051021-241-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 4 of 7
Phone #
Fax #
Alec Treviño Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
CA Labs Project #:
Asbestos & Technical Services 051021-241, FE Warren B241
Cheyenne, WY
CAL21054456AG
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 5/14/2021
2 days Samples Rec'd: 5/12/21 2:30PM
307-214-0904 Date Of Sampling: 5/10/2021
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
44285
051021-241-
9 9-1
Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44286
051021-241-
10 10-1
Plaster/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44286 10-2 tan plaster y None Detected 100% qu,ca
44287
051021-241-
11 11-1
Plaster/ white surfaced white finishing plaster n None Detected 2% wo
98% qu,bi,ca
44287 11-2
100% qu,mi,bi,ca tan plaster y None Detected
12-2
100% qu,ca
44288
051021-241-
12 12-1
Drywall/ white surfaced white compound n None Detected
100% qu,mi,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
white compound (beneath tape) y None Detected44288
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 5 of 7
Phone #
Fax #
Alec Treviño Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
CA Labs Project #:
Asbestos & Technical Services 051021-241, FE Warren B241
Cheyenne, WY
CAL21054456AG
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 5/14/2021
2 days Samples Rec'd: 5/12/21 2:30PM
307-214-0904 Date Of Sampling: 5/10/2021
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
44289
051021-241-
13 13-1
Popcorn/ white textured surfacing y None Detected 2% ce
2% wo
96% qu,pe,bi,ca
44290
051021-241-
14 14-1
Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44291
051021-241-
15 15-1
Plaster/ off-white surfaced white finishing compound n None Detected 20% ta
98% qu,bi,ca
44291 15-2 tan plaster y None Detected 100% qu,ca
44292
051021-241-
16 16-1
3% ta
97% qu,mi,bi,ca
Drywall/ white surfaced white compound n None Detected
18-1
100% qu,mi,bi,ca
44293
051021-241-
17 17-1
Popcorn/ white textured surfacing y None Detected
100% qu,mi,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Drywall/ white surfaced white compound n None Detected44294
051021-241-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 6 of 7
Phone #
Fax #
Alec Treviño Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
CA Labs Project #:
Asbestos & Technical Services 051021-241, FE Warren B241
Cheyenne, WY
CAL21054456AG
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 5/14/2021
2 days Samples Rec'd: 5/12/21 2:30PM
307-214-0904 Date Of Sampling: 5/10/2021
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
44295
051021-241-
19 19-1
Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44295 19-2 white drywall with brown paper n None Detected 20% ce 80% qu,gy
44296
051021-241-
20 20-1
Drywall/ white textured surfacing y None Detected 2% ce
2% ta
96% qu,mi,bi,ca
44297
051021-241-
21 21-1
Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca
44297 5 21-2
2% ta
2% ce
96% qu,mi,bi,ca white drywall with brown paper
23-1
44298
051021-241-
22 22-1
Popcorn/ white textured surfacing y None Detected
100% qu,mi,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Drywall/ white surfaced white compound n None Detected44299
051021-241-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 7 of 7
File details come from the government source that posted it. Updated .