16195-1 (072125) 2009 by FEI
SECTION 16195
ELECTRICAL IDENTIFICATION
PART 1 - GENERAL
1.1 SUMMARY
A. Extent of electrical identification is indicated by drawings and schedules.
B. See ‘Electrical Equipment Identification Schedule’ on drawings for extent of equipment to be labeled and label verbiage.
C. Types of electrical identification specified in this section include the following:
1. Buried cable warnings.
2. Electrical power, control and communication conductors.
3. Operational instructions and warnings.
4. Danger signs.
5. Equipment/system identification signs.
D. Refer to Division 1 General Requirements Section, Identification Systems, for equipment and system nameplates and performance data; not work of this section.
PART 2 - PRODUCTS
2.1 ELECTRICAL IDENTIFICATION MATERIALS
A. General: Except as otherwise indicated, provide manufacturer's standard products of categories and types required for each application. Where more than one (1) single type is specified for an application, selection is Installer's option, but provide single selection for each application.
B. Plasticized Tags:
1. General: Manufacturer's standard pre-printed or partially pre- printed accident-prevention and operational tags, of plasticized card stock with matte finish suitable for writing, approximately 3-1/4-inch x 5-5/8-inch, with brass grommets and wire fasteners, and with appropriate pre-printed wording including large-size primary working, e.g., DANGER, CAUTION, DO NOT OPERATE.
C. Self-Adhesive Plastic Signs:
1. General: Provide manufacturer's standard, self-adhesive or pressure-sensitive, pre-printed, flexible vinyl signs for operational instructions or warnings; of sizes suitable for application areas and adequate for visibility, with proper wording for each application, e.g., 208V, EXHAUST FAN, RECTIFIER.
a. Colors: Unless otherwise indicated or required by governing regulations, provide orange signs with black lettering.
16195-2
D. Baked Enamel Danger Signs:
1. General: Provide manufacturer's standard "DANGER" signs of baked enamel finish on 20-gage steel; of standard red, black and white graphics; 14-inch x 10-inch size except where 10-inches x 7-inches is the largest size which can be applied where needed, and except where larger size is needed for adequate vision; with recognized standard explanation wording, e.g., HIGH VOLTAGE, KEEP AWAY, BURIED CABLE, DO NOT
TOUCH SWITCH.
E. Engraved Plastic-Laminate Signs:
1. General: Provide engraving stock melamine plastic laminate, complying with FS L-P-387, in sizes and thicknesses indicated, engraved with engraver's standard letter style of sizes and wording indicated, black face and white core (letter color) except as otherwise indicated, punched for mechanical fastening except where adhesive mounting is necessary because of substrate.
a. Thickness: 1/16-inch, for units up to 20 sq. in. or 8-inch length; 1/8-inch for larger units.
b. Fasteners: Double sided tape, except contact-type permanent adhesive where tape will not adhere to surface.
c. Label size at ‘Load’ to be 2 1/2” x 4” label size at breaker to be 1” x 2 1/2”.
F. Color-Coded Conduit Markers:
1. General: Provide manufacturer's standard pre-printed, flexible or semi-rigid, permanent, plastic-sheet conduit markers, extending 360º degrees around conduits; designed for attachment to conduit by adhesive, adhesive lap joint of marker or matching adhesive plastic tape at each end of marker, or pretensioned snap-on. Except as otherwise indicated, provide lettering which indicates voltage of conductor(s) in conduit. Provide 8-inch minimum length for 2-inch and smaller conduit, 12-inch length for larger conduit.
a. Colors: Unless otherwise indicated or required by governing regulations, provide orange markers with black letters.
2.2 LETTERING AND GRAPHICS
A. General: Coordinate names, abbreviations and other designations used in electrical identification work, with corresponding designations shown, specified or scheduled. Provide numbers, lettering and wording as indicated or, if not otherwise indicated, as recommended by manufacturers or as required for proper identification and operation/maintenance of electrical systems and equipment. Comply with ANSI A13.1 pertaining to minimum sizes for letters and numbers.
PART 3 - EXECUTION
3.1 APPLICATION AND INSTALLATION
A. General Installation Requirements:
1. Install electrical identification products as indicated, in accordance with manufacturer's written instructions and requirements of NEC.
16195-3
2. Coordination: Where identification is to be applied to surfaces, which require finish, install identification after completion of painting.
3. Regulations: Comply with governing regulations and requests of governing authorities for identification of electrical work.
B. Operational Identification and Warnings:
1. General: Wherever reasonably required to ensure safe and efficient operation and maintenance of electrical systems, and electrically connected mechanical systems and general systems and equipment, including prevention of misuse of electrical facilities by unauthorized personnel, install self-adhesive plastic signs or similar equivalent identification, instruction or warnings on switches, outlets and other controls, devices and covers of electrical enclosures. Where detailed instructions or explanations are needed, provide plasticized tags with clearly written messages adequate for intended purposes.
C. Danger Signs:
1. General: In addition to installation of danger signs required by Governing regulations and authorities, install appropriate danger signs at locations indicated and at locations subsequently identified by Installer of electrical work as constituting similar dangers for persons in or about Project.
a. High Voltage: Install danger signs wherever it is possible, under any circumstances, for persons to come into contact with electrical power of voltages higher than 250-volts.
b. Critical Switches/Controls: Install danger signs on switches and similar controls, regardless of whether concealed or locked up, where untimely or inadvertent operation (by anyone) could result in significant danger to persons, or damage to or loss of property where instructed by Architect.
D. Equipment/System Identification:
1. General: Install engraved plastic-laminate sign on each major unit of electrical equipment in building; including central or master unit of each electrical system including communication/control/signal systems, unless unit is specified with its own self-explanatory identification or signal system. Signs for disconnect switches, motor starters, contactors and similar equipment shall indicate the load served. Except as otherwise indicated, provide single line of text, 1/2-inch high lettering on 1-1/2-inch high sign (2-inch high where two (2) lines are required), white lettering in black field. Lettering for emergency power system components shall be white lettering in red field. Provide text matching terminology and numbering of the Contract Documents and shop drawings. Provide signs for each unit of the following categories of electrical work.
a. Panelboards, electrical cabinets and enclosures.
b. Access panel/doors to electrical facilities.
c. Major electrical switchgear.
d. Disconnect switches.
e. Motor control centers.
f. Motor starters.
g. Contactors.
16195-4
h. Power transfer equipment.
i. Transformers.
2. Install signs at locations indicated or, where not otherwise indicated, at location for best convenience of viewing without interference with operation and maintenance of equipment. Secure to substrate with fasteners, except use adhesive where fasteners should not or cannot penetrate substrate.
E. Cable/Conductor Identification:
1. General: Apply cable/conductor identification in each box/enclosure/cabinet, except where another form of identification (such as color-coded conductors) is provided. Match identification with marking system used in distribution switchboards, shop drawings, contract documents, and similar previously established identification for project electrical work.
END OF SECTION
16195-5 (072125) 0108 P1
BJ/1J Electrical Equipment Label Schedule
LABEL
INSTALLED
BY
LOCATION
LABEL AT LOAD
LABEL AT BREAKER
CKT
NO.
Contractor Sub BJ
15 kV SW Switch BJ
Fed from SAC 4B
Contractor Transformer Sub BJ
1000 KVA
Contractor Distribution Swbd. BJ
Distr. Switchboard BJ Fed from Sub BJ
Main Fed from Sub BJ
MBJ
Tie Fed from Panel 1J
BJ/1J
Contractor
MCC BJ
Fed from Dist. Swbd. BJ
MCC BJ
Room BJ15
BJ1
Contractor BJ UPS Input
Fed from Dist. Swbd. BJ BJ UPS Input Room BJ17
BJ2
Contractor Panel UDP1
Fed from Dist. Swbd. BJ Panel UDP1 Room BJ17
BJ4
Contractor UPS BJ/1J Bypass Swbd.
Fed from Dist. Swbd. BJ UPS BJ/1J bypass
Distr. Swbd.
BJ5
Contractor Transformer TMDP
Fed from Dist. Swbd. BJ Transformer MDP
Room BJ19
BJ3
Contractor Spare BJ6
Govt. Panel MDP Panel MDP
Fed from Dist. Swbd. BJ Transformer TMDP
Govt. Panel MDP-A Panel MDP-A
Fed from BJ Panel MDP
Govt. Panel PB2 Panel PB2
Govt. Panel PB1 Panel PB1
Govt. Panel LB3 Panel LB3
Govt. Panel LB2 Panel LB2
Govt. Panel BBP Panel BBP
Govt. Panel LB1 Panel LB1
Govt.
Panel EM1
Fed from MCC BJ Panel EM1 BJ Corridor
Transformer
TEM1
Transformer TEM1 Fed from MCC
BJ Feeds Panel EM1
16195-6 (072125) 0108 P1 2009 by FEI
BJ/1J Electrical Equipment Label Schedule
INSTALLED
BY
LOCATION
LABEL AT LOAD
LABEL AT BREAKER
CKT
NO.
Contractor Sub 1J
15 kV SW Switch 1J
Fed from SAC 4A
Sub 1J
Swbd. 1J
Dist. Switchboard 1J Fed From Sub 1J
Fed from Sub 1J
M1J
Fed from Panel BJ
1J/BJ
MCC 1J
Room 1J11
1J1
Contractor
1J UPS
Fed from Dist. Swbd 1J Input 1J UPS Input Room BJ17
1J2
Spare 1J3
Contractor MCC 1J
MCC 1J
Fed from Dist. Swbd. 1J
Panel 1LA
Fed from MCC 1J Panel 1LA Room 1J8
Panel 1LB
Fed from MCC 1J Panel 1LB Room 1J8
Contractor Panel 1LB1 Panel 1LB1
Fed from 1J Panel 1LB
T1LA
Transformer T1LA Fed from MCC1J Feeds Panel 1LA
T1LB
Transformer T1LB Fed from MCC1J Feeds Panel 1LB
BJ/1J UPS
Bypass Dist.
Swbd.
(future connection) Maintenance Bypass Panel 1JA
(future connection)
Maintenance Bypass Panel BJA
UPS 1J Rm 1J12 Bypass
UPS BJ Bypass Rm BJ17
16195-7
2J/3J ELEC. EQUIPMENT IDENTIFICATION SCHEDULE
INSTALLED
BY
LOCATION LABEL AT LOAD LABEL AT
BREAKER CKT. NO
Contractor Sub 2J
15 kV SW Switch 2J
Fed from SAC 4B
Sub 2J
Swbd 2J
Distr. Switchboard 2J Fed from Sub 2J
M2J
Fed from Sub 3J
2J/3J
Contractor
MCC 2J
Fed from Dist. Swbd 2J
MCC 2J
Room 2J11 2J2
Contractor 2J UPS Input
Fed from Dist. Swbd 2J 2J UPS Input 2J5
Contractor Panel MS1
Fed From Dist. Swbd 2J Panel MS1 2J3
Spare 2J6
Contractor CAC16 CAC16 Rm. 2J15 Fed from Sub 2J
2J1
Contractor TUP1 TUP1 Rm. 3J2 2J4
Contractor Sub 3J
15 kV SW Switch 3J
Fed from SAC 4A
Sub 3J
Swbd 3J
Distribution Swbd 3J
M3J
3J/2J
Contractor
MCC 3J
Fed from Sub 3J
MCC 3J
Room 3J11 3J1
Contractor 3J UPS Input
Fed from Dist.
Swbd 3J
3J UPS Input Room 3J15
3J5
Contractor UPS 2J/3J Bypass Swbd
Fed from Dist.
Swbd. 3J
UPS 2J/3J Bypass Swbd. Rm. 2J12
3J4
Contractor
XFMR HA/Pnl 2HA/Pnl
3HA
Fed from Dist. Swbd.
Panel 3J
Panels 2HA/3HA Rooms 2J4/3J4
3J3
16195-8
2J/3J ELEC. EQUIPMENT IDENTIFICATION SCHEDULE
INSTALLED
BY
LOCATION LABEL AT LOAD LABEL AT
BREAKER CKT. NO
Spare 3J2
Govt.
Transformer
T2LA
Transformer T2LA Fed from Panel 2HA Feeds
Panel 2LA
Govt. Panel 2LA Panel 2LA
Fed from 3J Panel 2HA
UPS 2J/3J
Bypass Dist. Swbd.
Space Future
UPS 2J Bypass
UPS 3J Bypass
UPS 2JA
Maint. Bypass
UPS 3JA
Maint. Bypass