16170 Final Circuit and Motor Disconnects.pdf

PDF 38 KB Posted

Attached to
RECOVERY - SGBP970107 - Repair J-Wing Elec, Strat
Solicitation number
FA4600-09-B-0006
Issued by

About this file

Attachment 1 Specs

View the file

Other files

File Type Posted
QA 2 Repair J Wing Electrical RFI.doc DOC document
QA RECOVERY Repair J Wing Electrical RFI.doc DOC document
OFF-B-6073 Sheet 02 - Amendment 1 - May 09.dwf DWF file
OFF-B-6073 Sheet 04 - Amendment 1 - May 09.dwf DWF file
FA4600-09-B-0006-0003.pdf PDF
OFF-B-6074 Sheet 03 - Amendment 1 - May 09.dwf DWF file
OFF-B-6073 Sheet 05 - Amendment 1 - May 09.dwf DWF file
OFF-B-6074 Sheet 01 - Amendment 1 - May 09.dwf DWF file
OFF-B-6073 Sheet 06 - Amendment 1 - May 09.dwf DWF file
OFF-B-6073 Sheet 01 - Amendment 1 - May 09.dwf DWF file
amend 0002.doc DOC document
Site Visit Sign in.pdf PDF
Amendment 1.doc DOC document
08100.pdf PDF
Section 1A J-WING BJ-1J.pdf PDF
Sheet 05-5.dwf DWF file
09650.pdf PDF
Section 1C J-WING BJ-1J.pdf PDF
16010 Final General Electrical.pdf PDF
Sheet 04-4.dwf DWF file
09000.pdf PDF
Sheet 06-6.dwf DWF file
Sheet 07-7.dwf DWF file
02110.pdf PDF
Sheet 05-5.dwf DWF file
16452 Final Grounding.pdf PDF
16135 Final Electrical Boxes and Fittings.pdf PDF
Sheet 02-2.dwf DWF file
09900.pdf PDF
Sheet 09-Layout.dwf DWF file
16361 Final Secondary Unit Substations.pdf PDF
09250.pdf PDF
16470 Final Panelboards.pdf PDF
Section 1B J-WING BJ-1J.pdf PDF
Sheet 07-7.dwf DWF file
16120 Final Wires and Cables.pdf PDF
Section 1 AF66 J-WING bj-1j.xls XLS spreadsheet
16190 Final Supporting Devices.pdf PDF
Sheet 03-3.dwf DWF file
Sheet 01-01.dwf DWF file
16482 Final Motor Control Centers.pdf PDF
06300.pdf PDF
Sheet 04-4.dwf DWF file
16110 Final Raceways.pdf PDF
Sheet 06-6.dwf DWF file
16124 Final Medium Voltage Cables.pdf PDF
Atch 4 General Decision Number.doc DOC document
07200.pdf PDF
Atch 5 offeror checklist.doc DOC document
TOC - Repair Electrical J-Wing Stratcom Floors BJ 1J.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

16170-1 (072125) 2009 by FEI

SECTION 16170

CIRCUIT AND MOTOR DISCONNECTS

PART 1 - GENERAL

1.1 SUMMARY

A. Extent of circuit and motor disconnect switch work is indicated on drawings and schedules.

B. Types of circuit and motor disconnect switches in this section include the following:

1. Equipment disconnects.

2. Appliance disconnects.

3. Motor-circuit disconnects.

C. Wires/cables, raceways and electrical boxes and fittings required in connection with circuit and motor disconnect work are specified in other Division 16 Sections.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Manufacturer: Subject to compliance with requirements, provide circuit and motor disconnects of one (1) of the following:

1. General Electric Co.

2. Siemens.

3. Square D Company.

4. Cutler-Hammer.

2.2 DISCONNECT SWITCHES

A. General-Duty Disconnect Switches: For switches rated less than 100-amps provide surface-mounted, general-duty type, sheet-steel enclosed switches, of types, sizes and electrical characteristics indicated; rated for system voltage, 60 Hz, with required number of poles and solid neutral incorporating spring assisted, quick-make, quick-break switches. Equip with operating handle which is integral part of enclosure base and whose operating position is easily recognizable and is capable of being padlocked in OFF position. Construct current carrying parts of high-conductivity copper, with silver-tungsten type switch contacts and positive pressure type reinforced fuse clips where fusing is required. The enclosure shall be NEMA rated to suit the atmospheric conditions of the equipment surroundings and of the manufacturer's standard finish.

When used as service disconnect, provide with UL markings indicating "suitable for use as service equipment".

B. Heavy-Duty Disconnect Switches: For switches rated 100-amps or greater provide surface-mounted, heavy-duty type, sheet-steel enclosed switches, of types, sizes and electrical characteristics indicated; rated for system voltage 60 Hz, with required number of poles and solid neutral incorporating quick-make, quick-break type switches. Equip with operating handle which is integral part of enclosure base and whose position is easily recognizable, and is padlockable in OFF position; construct current carrying parts of high-conductivity copper, with silver-tungsten type switch contacts, and positive pressure type reinforced fuse clips where fusing is required.

The enclosure shall be NEMA rated to suit the atmospheric conditions of the equipment

16170-2 (072125) 2009 by FEI surroundings and of the manufacturer's standard finish. When used as service disconnect, provide with UL markings indicating "suitable for use as service equipment".

C. Motor-circuit disconnect switches must be HP rated.

D. Fuses: Provide fuses for disconnect switches, as recommended by switch manufacturer, of classes, types and ratings needed to fulfill electrical requirements for service indicated.

PART 3 - EXECUTION

3.1 INSTALLATION OF MOTOR AND CIRCUIT DISCONNECT SWITCHES

A. Install circuit and motor disconnect switches where indicated, complying with manufacturer's written instructions, applicable requirements of NEC, NEMA and NECA's "Standard of Installation" and in accordance with recognized industry practices.

B. Coordinate motor and circuit disconnect switch installation work with electrical raceway work, location of equipment and as necessary for proper interface. Provide U-channel supports from floor and/or structure where required to mount disconnects at free-standing equipment.

C. Install disconnect switches used with motor-driven appliances, and motors and controllers within sight of controller position for motors greater than 1/8 HP.

3.2 GROUNDING

A. Provide equipment grounding connections, sufficiently tight to assure a permanent and effective ground as required by NEC and in Grounding Section of Division 16.

3.3 FIELD QUALITY CONTROL

A. Subsequent to completion of installation of electrical disconnect switches, energize circuitry and demonstrate capability and compliance with requirements. Where possible, correct malfunctioning units at Project Site, then retest to demonstrate compliance; otherwise remove and replace with new units and retest.

END OF SECTION