DESIGN CONDITIONS
INDOOR:
OUTDOOR:
SUMMER
OUTDOOR:
WINTER
INDOOR:
95°F DB / 80°F WB
78°F DB / 45% RH
25°F DB
68°F DB
GENERAL HVAC NOTES
1. THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND LOCATION OF EQUIPMENT, DUCTWORK, PIPING, ETC. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE MECHANICAL INSTALLATION W/ THE STRUCTURE AND
OTHER TRADES AND SHALL PROVIDE ADDITIONAL OFFSETS AND FITTINGS AS NECESSARY.
2. COORDINATE WORK WITH GOVERNMENT AND OBTAIN ALL PERMITS AND INSPECTIONS.
3. PROVIDE GOVERNMENT WITH CERTIFICATES OF FINAL INSPECTION AND ACCEPTANCE.
4. THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS SHALL COMPLY WITH THE THE CODES LISTED ON THIS
SHEET AS WELL AS ALL GOVERNMENT UFC CODE OFFICIAL REQUIREMENTS. IN THE EVENT OF A CONFLICT BETWEEN
CODES, THE MOST STRINGENT SHALL ALWAYS GOVERN.
5. DUCT DIMENSIONS ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
6. THE CONTRACTOR SHALL CHECK AND VERIFY ALL CLEARANCES PRIOR TO FABRICATION OR INSTALLATION OF
EQUIPMENT, DUCTWORK, AND PIPING SYSTEMS. WHERE CONDITIONS REQUIRE A CHANGE IN DUCT OR PIPE ROUTING, NOTIFY THE GOVERNMENT AND ENGINEER FOR AN ACCEPTABLE ALTERNATIVE METHOD. AVOID ROUTING COMPONENTS DIRECTLY OVER LIGHT FIXTURES, DIFFUSERS, AND OTHER CEILING MTD. DEVICES. LOCATE ALL MECHANICAL EQUIPMENT SO THAT FILTERS AND COMPONENTS REQUIRING ACCESS (SERVICE AND MAINTENANCE) ARE FULLY ACCESSIBLE.
7. INSTALL ALL DUCT MOUNTED DEVICES (DAMPERS, ACCESS DOORS, ETC.) AND PIPING SPECIALTIES IN EASILY ACCESSIBLE LOCATIONS. ADVISE THE ENGINEER IN ADVANCE OF INSTALLATION IF ACCESS WILL BE HINDERED SO AN ALTERNATE
LOCATION CAN BE SELECTED.
8. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS WITH PRESCRIBED CLEARANCES FOR SERVICE AND MAINTENANCE. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IF RECOMMENDED CLEARANCES ARE NOT POSSIBLE BEFORE INSTALLING EQUIPMENT.
9. ALL ROTATING MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION. PROVIDE FLEXIBLE
NEOPRENE DUCT CONNECTORS BETWEEN DUCTWORK AND ISOLATED MECHANICAL EQUIPMENT.
10. SEISMIC PROTECTION OF EQUIPMENT, DUCTWORK, PIPING AND UTILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 16 OF THE INTERNATIONAL BUILDING CODE, 2015 EDITION. ALL SEISMIC RESTRAINT AND BRACING SHALL BE SUBSTANTIATED BY MANUFACTURER'S SUBMITTALS PER THE SPECIFICATIONS. FOR ADDITIONAL INFORMATION, SEE 'SEISMIC AND WIND REQUIREMENTS FOR MECHANICAL SYSTEMS' ON THIS SHEET. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING INSTALLATION OF SEISMIC BRACING DEVICES WITH THE OWNER'S SEISMIC SPECIAL INSPECTOR.
PROVIDE A MINIMUM OF SEVEN DAYS ADVANCE NOTICE OF INSTALLATION.
11. BALANCE ALL AIR DISTRIBUTION DEVICES, EXHAUST FANS, AND OUTSIDE AIR QUANTITIES AS SCHEDULED OR SHOWN ON THE DRAWINGS. PROVIDE MARKERS AT ALL DAMPER LOCATIONS SHOWING FULL OPEN/CLOSED POSITIONS AND DAMPER SETTING FOR REQUIRED AIRFLOW. PROVIDE FINAL TEST AND BALANCE REPORT ALONG W/ SCHEMATIC DRAWINGS SHOWING DIFFUSER LOCATION W/ DESIGN AND ACTUAL CFM. THE DIFFUSER TAGS ON THE DRAWINGS SHALL CORRESPOND TO THE DIFFUSER TAGS ON THE REPORT. THIS REPORT SHALL BE SUBMITTED BEFORE THE FINAL
INSPECTION IS PERFORMED. SEE SPECIFICATIONS FOR FURTHER INFORMATION.
12. ALL CONTROL WIRING, CONDUIT AND CONTROLS ACCESSORIES NECESSARY TO IMPLEMENT THE OUTLINED SEQUENCES
OF OPERATION SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR.
13. WIND LOAD PROTECTION OF ROOF MOUNTED EQUIPMENT AND DUCTWORK SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 16 OF THE INTERNATIONAL BUILDING CODE, 2015 EDITION. ALL WIND LOAD RESTRAINT AND BRACING SHALL BE
SUBSTANTIATED BY MANUFACTURER'S SUBMITTALS PER THE SPECIFICATIONS.
14. WHERE "APPROXIMATELY" IS USED TO DEFINE INSTALLATION LOCATIONS, CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES TO VERIFY THERE ARE NO CONFLICTS PRIOR TO INSTALLATION AT DIMENSION LISTED.
AUTOMATIC BALANCING CONTROL VALVE
HOSE BIBB
DIRECTION OF PIPING FLOW
PIPING SLOPE
PIPE CAP
DRAIN VALVE W/ HOSE CONNECTION
AUTOMATIC AIR VENT
BASKET STRAINER
RELIEF VALVE
RINSE VALVE
FLANGE CONNECTION
M
M
S
SOLENOID VALVE
SWING CHECK VALVE
PLUG VALVE
CIRCUIT SENSOR
BACKFLOW PREVENTER
PRESSURE REDUCING VALVE
UNION
ECCENTRIC REDUCER/INCREASER
CONCENTRIC REDUCER/INCREASER
MOTORIZED BALL VALVE
MOTORIZED BUTTERFLY VALVE
END SUCTION PUMP
DOUBLE SUCTION PUMP
PUMP CONNECTOR/FLEX CONNECTOR
GATE VALVE
PUMP SUCTION DIFFUSERPSD
CIRCUIT SETTER
EARTHQUAKE VALVE
BALL VALVE
HVAC PIPING SPECIALTIES SYMBOL LEGEND
CONNECTION TO EXISTING SYSTEM
X"x Y"
TURNING VANES
CONDENSING UNIT
DUCTWORK (X" = WIDTH, Y" = HEIGHT)
COMPONENT TO BE DEMOLISHED
EQUIPMENT CLEARANCE
HVAC SYMBOL LEGEND
DESCRIPTIONSYMBOL SYMBOL DESCRIPTION
DESCRIPTIONSYMBOL SYMBOL DESCRIPTION
WYE STRAINER W/BLOWDOWN BALL VALVE
WITH HOSE CONNECTION
31WAY CONTROL VALVE
WAFER CHECK VALVE
WYE STRAINER
FLANGED JOINT
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
ELBOW SIDE
TEE SIDE
BUTTERFLY VALVE
BALL VALVE
CIRCUIT SETTER/ BALANCING VALVE
PIPE WITH HEAT TRACING INSULATION AND
JACKET
M
MOTORIZED BUTTERFLY VALVE
HVAC PIPING SYMBOL LEGEND
DESCRIPTIONSYMBOL
A M
IL
I
L W
BA
D E N
I
A
I I
R
L L
DG
No.
TU
D S
IS
R
E T
E
AA
30241
RE
G E
ER
IN
E N
L
RCAH
ORP
SEF
OL
N
S IO
IN
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
M001
H
VA
C N
O
TE
S, S C H
ED
U
LE
S, L
EG
EN
DS
W D
B W
D B
M A
U
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08110306
MECHANICAL ABBREVIATIONS
ABBR DESCRIPTION
(E) EXISTING
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AIR HANDLER
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
BHP BRAKE HORSE POWER
BMS BUILDING MANAGMENT SYSTEM
BOD BASIS OF DESIGN
C DOMESTIC COLD WATER SUPPLY
CFM CUBIC FEET PER MINUTE
CHF CHEMICAL FEED
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CO CLEANOUT
CU CONDENSING UNIT
DB DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DIA DIAMETER
DRN DRAIN
DX DIRECT EXPANSION
EC ELECTRICAL CONDUCTOR
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
ESP EXTERNAL STATIC PRESSURE
FD FLOOR DRAIN
FPM FEET PER MINUTE
FRPM FAN ROTATIONS PER MINUTE
FT FEET
GPM GALLONS PER MINUTE
HP HORSEPOWER
IN INCHES
LAT LEAVING AIR TEMPERATURE
MBH THOUSANDS OF BTU'S PER HOUR
MC MECHANICAL CONTRACTOR
NC NOISE CRITERIA
NO NORMALLY OPEN
OA OUTSIDE AIR
PD PRESSURE DROP
PS PIPE SUPPORT
REFR REFRIGERANT
RPM ROTATIONS PER MINUTE
TYP TYPICAL
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
°F DEGREES FAHRENHEIT
MECHANICAL CODES & STANDARDS
CODE DESCRIPTION
IBC (2015) INTERNATIONAL BUILDING CODE
IECC (2015) INTERNATIONAL ENERGY CONSERVATION CODE
IMC (2015) INTERNATIONAL MECHANICAL CODE
NFPA 90A (2009) STANDARD FOR THE INSTALLATION AIR1CONDITIONING & VENTILATING SYSTEMS
SMACNA (2005) HVAC DUCT CONSTRUCTION STANDARDS MANUAL, THIRD EDITION
AIR COOLED CHILLER SCHEDULE
UNIT
I.D.
NOMINAL
CAPACITY
CHILLED WATER
AMBIENT
AIR IPLV
BASIS OF
DESIGN MODEL
DESIGN
FLOW RATE EWT LWT
MAX PRESSURE
DROP
CH11 60 TONS 106 GPM 56 °F 44 °F 8.60 ftH2O 95 14.6 TRANE CGAM 60
CHILLED WATER COOLING COIL SCHEDULE
UNIT
I.D.
AIR CAPACITY
CFM
TOTAL
MBH
SENS.
MBH
MAX FV
(FPM)
ENTERING AIR LEAVING AIR
GPM EWT °F LWT °F
AIR P.D. (IN
W.G.)
WATER P.D.
(FT W.G.)
FINS /
INCH SIZE MANUFACTURER MODELD.B. °F W.B. °F D.B. °F W.B. °F
CCC11 10,000 385.2 275.6 481 FPM 80.0 °F 67.0 °F 55.0 °F 54.5 °F 64.0 GPM 56 °F 44 °F 0.65 in1wg 6.2 ftH2O 103 67"x45" TRANE DUWB45
CCC12 8,800 249.4 209.9 423 FPM 76.7 °F 63.8 °F 55.0 °F 54.5 °F 42.0 GPM 56 °F 44 °F 0.44 in1wg 2.8 ftH2O 84 67"x45" TRANE DUWB45
NOTES:
1. FIELD VERIFY DIMENSIONS OF COIL TO FIT IN EXISTING AIR HANDLER CABINET.
2. DELTA FLOW H FIN TYPE
3. ALUMINUM FINS, COPPER TUBES
4. AHRI ACHC 410 CERTIFIED
5. PROVIDE REPLACEMENT AIR HANDLER ENCLOSURE PANELS TO REPLACE EXISTING AROUND REPLACED COILS.
NOTES:
1. COORDINATE VOLTAGE WITH ELECTRICAL DRAWINGS.
2. INCLUDE INTEGRAL DUAL PUMPING PACKAGE, 60' HEAD PRESSURE. VFD'S SHALL BE PROVIDED BY THE CHILLER
MANUFACTURER TO CONTROL THE PUMPS.
3. INCLUDE WITH INTEGRAL 136 GALLON BUFFER TANK.
4. INCLUDE WITH INTEGRAL 5 GALLON EXPANSION TANK.
5. SUPER QUIET SOUND ATTENUATOR PACKAGE.
6. INCLUDE WITH DDC CONNECTION TO CONNECT TO EXISTING BASE EMCS.
7. INCLUDE WITH SINGLE POINT POWER, EXCEPT HEAT TRACE.
8. CONDENSER COIL SHALL BE FACTORY APPLIED WITH EPOXY COATING.
9. PROVIDE WITH INTEGRAL DISCONNECT.
10. PROVIDE WITH FACTORY INSTALLED HEAT TRACE, THIS REQUIRES A SEPARATE ELECTRICAL CONNECTION.
AIR SEPARATOR SCHEDULE
UNIT
I.D.
SYSTEM
CONNECTION
DESIGN FLOW
RATE
MAXIMUM DESIGN
PRESSURE DROP TYPE
BASIS OF
DESIGN MODEL
AS11 3" 106 GPM 1.0 ftH2O TANGENTIAL AIR SEPARATOR LESS STRAINER BELL & GOSSETT RL13FB
NOTES:
H = (FAN S.P.) + 1"3.
J"
ACCESSIBLE FOR CLEANING.
2. "RUNNING" TYPE TRAPS SHALL
BE UNACCEPTABLE.
1. LOCATE TRAPS SO AS TO BE
PIPE FULL SIZE
OF UNIT DRAIN
H"
UNIT CASING
SCREWED CAP
OPEN END (VENT)
J = H/2 (MIN.)4.
5 FT 6 8 10
32 2 1/21 1/21 1 1/4THRU 3/4
7 98
ADJUSTABLE CLEVIS HANGER
TYPE 43 1 SEE SPECIFICATIONS
WELD
SADDLE
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
THREADED HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF
SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
IN.
FT.
NOTES:
SEE SPECIFICATIONS
FOR DETAILED HANGER
REQUIREMENTS
MECHANICAL COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION
IBC�2015 /ASCE 7�10
SEISMIC AND WIND REQUIREMENTS
FOR MECHANICAL SYSTEMS
COMPONENT IMPORTANCE FACTOR (Ip)
Ip = 1.0 Ip = 1.5
RESTRAIN IF TOTAL WEIGHT OF
DUCTS ON TRAPEZE > 10 LBS/FT
44 RESTRAIN IF TOTAL WEIGHT OF
DUCTS ON TRAPEZE > 10 LBS/FT
MULTIPLE DUCTS ON TRAPEZE
51 6 SQ.FT. AND LARGER
RESTRAIN IF ANY PIPE ON TRAPEZE > 1"
RESTRAIN IF TOTAL WEIGHT OF PIPES ON
TRAPEZE > 10 LBS/FT
4 RESTRAIN ALL
RESTRAIN IF ANY PIPE ON
TRAPEZE > 3" RESTRAIN IF
TOTAL WEIGHT OF PIPES ON
TRAPEZE > 10 LBS/FT
RESTRAIN ALL
SUSPENDED PIPE ON TRAPEZE
SUSPENDED NON DUCTILE PIPING
(CAST IRON, PLASTIC, CERAMIC)
A. PER SECTION 301.15 OF THE 2012 EDITION OF THE INTERNATIONAL MECHANICAL CODE, MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS (INCLUDING ROOF CURBS & ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINT IS REQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURAL
DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY.
B. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR DESIGNATIONS.
C. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT.
D. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED BY A
REGISTERED DESIGN PROFESSIONAL. SUBMITTALS MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS.
E. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS
CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF THE
SEISMIC SUBMITTAL.
F. SEISMIC RESTRAINTS FOR PIPING AND DUCTWORK MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT
LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS.
NOTES
1.51.0
6REQUIRED6NOT REQUIRED
COMPONENT CERTIFICATION
(SEE NOTE 6)
6 SQ.FT. AND LARGERDUCTWORK
4>1"4>3"SUSPENDED DUCTILE PIPING
STEEL, ALUMINUM, COPPER, ETC.
1RESTRAIN ALL1RESTRAIN ALLNOT INLINE W/
DUCT/PIPE
3RESTRAIN IF >75 LBS
PROVIDE FLEX. CONN.
RESTRAIN IF >75 LBS
PROVIDE FLEX. CONN.
INLINE W/ DUCTSUSPENDED
EQUIPMENT
1RESTRAIN ALL1RESTRAIN ALLCOMPONENT SUPPORTS
1RESTRAIN ALL1, 2RESTRAIN ALLWALL MOUNTED
1RESTRAIN ALL1, 2RESTRAIN ALLFLOOR MOUNTED
1RESTRAIN ALL1RESTRAIN ALLROOF MOUNTED
SEISMIC RESTRAINT
REQUIREMENT
NOTES
SEISMIC RESTRAINT
REQUIREMENT
COMPONENT IDENTIFICATION
SEISMIC DESIGN CATEGORIES D,E,F
ALL HVAC COMPONENTS EXCEPT AS NOTED IN Ip=1.5
NOTES:
1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED
DUCTWORK, PIPING, AND CONDUIT.
2. RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4FT. OR LESS ABOVE A FLOOR, AND HAS FLEXIBLE CONNECTIONS BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
3. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY.
4. RESTRAINT IS NOT REQUIRED IF THE PIPING / DUCTWORK IS SUPPORTED BY HANGERS AND EACH HANGER IN THE PIPING RUN IS 12 IN. OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE SUPPORTED BY HANGERS HAVING A LENGTH OF 12 IN. OR LESS. WHERE ROD HANGERS ARE USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENT BENDING IN THE ROD.
5. ALL DUCTWORK , REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES OR USED FOR SMOKE
CONTROL MUST BE RESTRAINED.
6. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BY
ENGINEER OF RECORD.
TYPE 40 PROTECTION SHIELD
HIGH DENSITY
INSULATION
SEE SPECIFICATIONS
TYPE 46 ADJUSTABLE
PIPE ROLL & BASE
3'10"
3"
ASPHALT SEAL
6" STEEL PIPE
GRADE
2'10"±
W 6 X 15
3/16"
CENTERLINE OF SUPPORT
4 1 No.4 BARS
AT
3" O.C.3'10"∅ CONCRETE
FOOTING
4 1 No.4 BARS AT 6" O.C.
CHILLED WATER PIPE
INTEGRAL 1" 14 GAUGE
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
PIPE CLAMP.
SIZE AS
REQUIRED
REFER TO PLANS
FOR QUANTITY &
SIZE OF PIPES
GALVANIZED THREADED
ROD, (TYP)
UV1INHIBITED RUBBER BLOCK,
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER &
LOCKNUT
A M
IL
I
L W
BA
D E N
I
A
I I
R
L L
DG
No.
TU
D S
IS
R
E T
E
AA
30241
RE
G E
ER
IN
E N
L
RCAH
ORP
SEF
OL
N
S IO
IN
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
M002
H
VA
C N
O
TE
S D
ET
AI
LS
W D
B W
D B
M A
U
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08110306
NOT TO SCALEM002
3 CONDENSATE DRAIN TRAP INSTALLATION DETAIL
NOT TO SCALEM002
1 SUSPENDED PIPE SUPPORT DETAIL
NOT TO SCALEM002
2 GROUND PIPE SUPPORT DETAIL
NOT TO SCALEM002
4 CONDENSATE PIPING SUPPORT DETAIL
1"x 1" CHAMFER
TO PROVIDE BOND
ROUGH UP FLOOR
EACH WAY
No. 4 @ 6"O.C.
TROWEL
FINISH
FIN FLR
ALL AROUND
NOTE:
CONCRETE HOUSEKEEPING PAD SHALL BE
DELEGATED DESIGN BY SEISMIC ENGINEER.
STRUCTURAL REINFORCEMENT OF CONCRETE SHALL
BE VERIFIED BASED UPON SEISMIC REQUIREMENTS
AND ASSOCIATED EQUIPMENT(S) WEIGHTS,
DIMENSIONS AND OPERATING CHARACTERISTICS.
DRAIN VALVE
TO DDC CONTROLLER
CHILLED
WATER COIL
AIR VENT
REDUCERS AS REQ'D (TYPICAL)
ISOLATION VALVE
(TYP.)
MOTORIZED MODULATING
CONTROL VALVE (BY
CONTROLS CONTRACTOR)
CIRCUIT SETTER
FITTING WITH PRESSURE/
TEMPERATURE TEST PLUG
(TYPICAL)
STRAINER
W/BLOWDOWN
VALVE & CAP
PROVIDE
BYPASS LINE
WITH VALVE
FOR
FLUSHING
SYSTEM.
NOTE:
INSTALL AN ISOLATION
VALVE AT EACH
CONNECTION TO COIL FOR
MULTIPLE COIL
CONNECTIONS
NOTES:
1. CHEMICAL SHOT FEEDER SHALL BE 2'10" AFF MIN.
2. SEE SPECIFICATIONS FOR FURTHER
INFORMATION. COORDINATE WITH CHEMICAL
TREATMENT PROVIDER.
3/4" PIPING ROUTED TO
WATER LOOP. CONNECT TO
DISCHARGE SIDE OF PUMPS.
3/4" PIPING ROUTED TO
WATER LOOP. CONNECT
TO SUCTION SIDE OF
PUMPS UPSTREAM OF AIR
SEPERATOR.
CHECK VALVE
BALL VALVE
(TYP.)
1/2" DRAIN
VALVE
FINISHED FLOOR
HOSE CONNECTION
51GALLON CHEMICAL
SHOT FEEDER
MANUFACTURER'S
STANDARD SUPPORT
LEG, BOLTED DOWN TO
FLOOR (TYPICAL 3X)
NOTE:
STRAINER
ELASTOMERIC
VIBRATION
ELIMINATOR
PRESSURE/TEMPERATURE
TEST PLUG (TYPICAL)
BUTTERFLY VALVE
UNION
3/4"
DRAIN
VALVE
EVAPORATOR
AIR VENT
AIR VENT
PRESSURE GAUGE
BUTTERFLY VALVE
PRESSURE
GAUGE
PRESSURE /
TEMPERATURE
TEST PLUG
(TYPICAL)
UNION
ELASTOMERIC
VIBRATION
ELIMINATOR
3/4"
DRAIN
VALVE
1. ALL EXTERIOR CHILLED WATER LINES SHALL BE
WRAPPED WITH HEAT TAPE, INSULATION AND METAL
JACKETS.
2. CHILLER MANUFACTURER SHALL PROVIDE
ARCHITECTURAL LOUVERED PANELS TO COVER THE
SERVICE AREA (CONDENSING COIL) AROUND THE
CHILLER.
3. FLOW SWITCH SHALL BE INSTALLED PER
MANUFACTURERS RECOMMENDATIONS WITH THE
ADEQUATE PIPE DIAMETERS OF STRAIGHT PIPE.
SECURE CHILLER TO
CONCRETE
HOUSEKEEPING PAD
PER SEISMIC
RECOMMENDATIONS
PRESSURE REDUCING VALVE 1 SET AT 4 PSIG HIGHER
THAN THE PRESSURE AT THE HIGH POINT IN THE
SYSTEM
TO DRAIN
BLOWDOWN AND
DRAIN VALVE WITH
HOSE CONNECTION
PRESSURE GAUGE
W/ NEEDLE VALVE
BALL VALVE
REDUCED PRESSURE
BACKFLOW PREVENTER
WITH OPEN AIR GAP
REDUCER (WHERE
REQ'D.)
TO PUMP
SUCTION
RELIEF VALVE 1
PIPED TO FLOOR
DRAIN.
BRACKET SUPPORTS
WITH OVERHEAD
SUPPORTS
BUTTERFLY VALVES
FLANGE / UNION
CENTRIFUGAL AIR
SEPARATOR
HIGH
CAPACITY
AIR VENT
FROM SYSTEM
PIPE ALL DRAINS
TO EXISTING
FLOOR DRAINS
(TYPICAL)
A M
IL
I
L W
BA
D E N
I
A
I I
R
L L
DG
No.
TU
D S
IS
R
E T
E
AA
30241
RE
G E
ER
IN
E N
L
RCAH
ORP
SEF
OL
N
S IO
IN
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
M003
H
VA
C D
ET
AI
LS
W D
B W
D B
M A
U
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08110306
NOT TO SCALEM003
1 CONCRETE HOUSEKEEPING PAD DETAIL
NOT TO SCALEM003
5 CHILLED WATER COIL PIPING DETAIL
NOT TO SCALEM003
2 CHEMICAL TREATMENT INSTALLATION DETAIL
NOT TO SCALEM003
4 CHILLER PIPING DETAIL
NOT TO SCALEM003
3 CHILLED WATER AIR SEPARATOR AND PIPING DETAIL
CHWS
CHWRM
T
AHU POINTS LIST
LEGEND
RETURN
AHU
AIR
NEW
CHILLED
WATER
COIL
MIXING
BOX
M
M
FILTER
NEW
VFD
FANC
NEW TRACER AHU
CONTROLLER
OUTSIDE
P
M
SUPPLY
AHU
VAV AHU 1 EXISTING JCI
VAV CONTROLLERS
SPACE
T
ENERGY MANAGEMENT CONTROL SYSTEM UNIT CONTROLLER
MOTORIZED ACTUATOR
EMCS
M
TEMPERATURE SENSOR
CURRENT SWITCHC
T
T
EXTG
VAV
VARIABLE FREQUENCY DRIVEVFD
T
LOCATE 2/3 OF THE WAY
DOWN THE LENGTH OF
DUCT.
EXISTING FIRE
ALARM PANEL
PRESSURE SENSORPDI11 AHU FAN STATUS (CURRENT)
AI12 DISCHARGE AIR TEMP
AI13 DUCT STATIC PRESSURE
DI12 FIRE ALARM PANEL CONTACT
AI11 MIXED AIR TEMP
AO15 VARIABLE FREQUENCY DRIVE
DO11 START/STOP AHU
AO11 DISCHARGE STATIC PRESSURE SETPOINT
AO12 SUPPLY AIR TEMP SETPOINT
AO13 OA MOTORIZED DAMPER
AO14 RA MOTORIZED DAMPER
AI14 OUTDOOR AIRFLOW
MEASURING STATION
EXTG AHU
T
VAV AIR HANDLING UNIT NOTES:
THE GENERAL INTENT IS TO REPLACE THE CHILLED
WATER COIL, THE CONTROL DAMPERS, THE
SUPPLY FAN VFD, AND THE SENSORS OF THE AIR
HANDLER.
NEW CHILLED WATER CONTROL VALVE SHALL BE
PROVIDED TO THE NEW CHILLED WATER COIL.
A NEW TRACER SC CONTROLLER COMPATIBLE
WITH THE BASE DDC SYSTEM AND NEW AHU
CONTROLLERS SHALL BE PROVIDED.
THE EXISTING JCI VAV CONTROLLERS AND WALL
MOUNTED ZONE CONTROLLERS SHALL REMAIN TO
PROVIDE CONTROL TO ZONE VAV UNITS.
THE CONTROL DAMPERS SHALL BE PROVIDED AND
INSTALLED BY THE MECHANICAL CONTRACTOR.
THE NEW DAMPER ACTUATORS SHALL BE
PROVIDED AND INSTALLED BY CONTROLS
CONTRACTOR.
VFD SHALL BE PROVIDED AND STARTED BY
CONTROLS CONTRACTOR. MECHANICAL
CONTRACTOR SHALL INSTALL VFD. ELECTRICAL
CONTRACTOR SHALL WIRE VFD.
NEW AIRFLOW MEASURING STATION TO BE
PROVIDED AND INSTALLED BY CONTROLS
CONTRACTOR.
THE TWO EXISTING EMCS EQUIPMENT ENCLOSURE
PANELS MAY BE RE1USED FOR NEW CONTROL
EQUIPMENT.
THE EXISTING EMCS CONTROLS WIRES TO BE
EVALUATED AND REUSED IF DEEMED TO BE IN
GOOD CONDITION BY THE CONTROLS
CONTRACTOR.
F
FREEZESTATF
EXTG TRANE FIELD
CONTROLLER
TO TRANE TRACER
BASEWIDE FRONT
END
NEW TRANE SC
CONTROLLER
NEW BACNET
CHILLER
CONTROLLER
NEW COMM
CONNECTION FROM
COMM ROOM TO
MECHANICAL ROOM
COMM ROOM
NEW DAMPERS
INSTALLED BY
MECHANICAL
CONTRACTOR (TYP 2)
NEW CONTROL VALVE
H
NEW GLOBAL
OUTDOOR
TEMPERATURE
AND HUMIDITY
SENSOR.
MOUNT IN
SHADE IN
EXTERIOR
WALL OF
BUILDING
DI13 DUCT STATIC PRESSURE SWITCH
DI14 VFD ALARM
AO16 CHILLED WATER VALVE
DI15 FREEZE STAT ALARM
FILTER STATUSFL
BACNET MSTP ON VFDB
DUCT STATIC HIGH LIMIT SWITCHDS
DS
B
FL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
EXISTING VAV BOX
CONTROLS AND ROOM
SENSORS TO REMAIN
WITH NO CHANGE
DI16 EMERGENCY PUSHBUTTON
AIR
MONITORING
STATION
E
EMERGENCY SHUTDOWN SWITCHE
CHWS
CHWRM
T
AHU POINTS LIST
LEGEND
RETURN
AHU
AIR
NEW
CHILLED
WATER
COIL
MIXING
BOX
M
M
FILTER
NEW
VFD
FANC
NEW TRACER AHU
CONTROLLER
OUTSIDE
SUPPLY
AHU
ENERGY MANAGEMENT CONTROL SYSTEM UNIT CONTROLLER
MOTORIZED ACTUATOR
EMCS
M
TEMPERATURE SENSOR
CURRENT SWITCHC
T
T
VARIABLE FREQUENCY DRIVEVFD
T
EXISTING FIRE
ALARM PANEL
PRESSURE SENSORP
DI11 AHU FAN STATUS (CURRENT)
AI12 DISCHARGE AIR TEMP
AI13 DUCT STATIC PRESSURE
DI12 FIRE ALARM PANEL CONTACT
AI11 MIXED AIR TEMP
AO15 VARIABLE FREQUENCY DRIVE
DO11 START/STOP AHU
AO11 DISCHARGE STATIC PRESSURE SETPOINT
AO12 SUPPLY AIR TEMP SETPOINT
AO13 OA MOTORIZED DAMPER
AO14 RA MOTORIZED DAMPER
AI14 OA MEASURING STATION
EXISTING AHU
T
CV AIR HANDLING UNIT NOTES:
THE GENERAL INTENT IS TO REPLACE THE
CHILLED WATER COIL, THE CONTROL
DAMPERS, AND THE SENSORS OF THE AIR
HANDLER.
NEW CHILLED WATER CONTROL VALVE
SHALL BE PROVIDED TO THE NEW
CHILLED WATER COIL.
A NEW TRACER SC CONTROLLER
COMPATIBLE WITH THE BASE DDC
SYSTEM AND NEW AHU CONTROLLERS
SHALL BE PROVIDED.
THE CONTROL DAMPERS SHALL BE
PROVIDED AND INSTALLED BY THE
MECHANICAL CONTRACTOR.
THE NEW DAMPER ACTUATORS SHALL BE
PROVIDED AND INSTALLED BY CONTROLS
CONTRACTOR.
VFD SHALL BE PROVIDED AND STARTED
BY CONTROLS CONTRACTOR.
MECHANICAL CONTRACTOR SHALL
INSTALL VFD. ELECTRICAL CONTRACTOR
SHALL WIRE VFD.
NEW AIRFLOW MEASURING STATION TO
BE PROVIDED AND INSTALLED BY
CONTROLS CONTRACTOR.
THE TWO EXISTING EMCS EQUIPMENT
ENCLOSURE PANELS MAY BE RE1USED
FOR NEW CONTROL EQUIPMENT.
THE EXISTING EMCS CONTROLS WIRES TO
BE EVALUATED AND REUSED IF DEEMED
TO BE IN GOOD CONDITION BY THE
CONTROLS CONTRACTOR.
THE CONTROLS CONTRACTOR SHALL
REPLACE THE EXISTING SPACE
TEMPERATURE AND HUMIDITY SENSORS.
F
FREEZESTATF
EXTG TRANE FIELD
CONTROLLER
TO TRANE TRACER
BASEWIDE FRONT
END
NEW TRANE SC
CONTROLLER
NEW BACNET
CHILLER
CONTROLLER
NEW COMM
CONNECTION FROM
COMM ROOM TO
MECHANICAL ROOM
COMM ROOM
NEW DAMPERS
INSTALLED BY
MECHANICAL
CONTRACTOR (TYP 2)
NEW CONTROL VALVE
H
NEW GLOBAL
OUTDOOR
TEMPERATURE
AND HUMIDITY
SENSOR.
MOUNT IN
SHADE IN
EXTERIOR
WALL OF
BUILDING
DI13 DUCT STATIC PRESSURE SWITCH
DI14 VFD ALARM
AO16 CHILLED WATER VALVE
DI15 FREEZE STAT ALARM
FILTER STATUSFL
BACNET MSTP ON VFDB
DUCT STATIC HIGH LIMIT SWITCHDS
DS
B
FL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
DO12 DUCT ELECTRIC HEAT STAGE 1
DO13 DUCT ELECTRIC HEAT STAGE 2
(E)
HEAT
STRIP
AI15 OUTDOOR AIR TEMPERATURE
AI16 OUTDOOR AIR HUMIDITY
T H
SPACE
T
EXISTING
ELECTRIC
DUCT HEATER
AIR
MONITORING
STATION
E
EMERGENCY SHUTDOWN SWITCHE
WALL MOUNTED HUMIDITY SENSORH
A M
IL
I
L W
BA
D E N
I
A
I I
R
L L
DG
No.
TU
D S
IS
R
E T
E
AA
30241
RE
G E
ER
IN
E N
L
RCAH
ORP
SEF
OL
N
S IO
IN
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
M004
H
VA
C C
O N
TR
O
LS
D
ET
AI
LS
W D
B W
D B
M A
U
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08110306
NOT TO SCALEM004
1 AHU11 VAV AHU SCHEMATIC DIAGRAM AND SEQUENCE OF OPERATION
NOT TO SCALEM004
2 AHU12 CONSTANT VOLUME SCHEMATIC DIAGRAM AND SEQUENCE OF OPERATION
3" CHWS
3" CHWR
CH11
AHU11
AHU12
NOTES:
ISOLATION VALVES, BALANCING
VALVES, CONTROL VALVES AND
OTHER PIPE FITTINGS AND
DEVICES ARE NOT SHOWN FOR
CLARITY. REFER TO DETAILS AND
DRAWINGS FOR ADDITIONAL
INFORMATION.
A M
IL
I
L W
BA
D E N
I
A
I I
R
L L
DG
No.
TU
D S
IS
R
E T
E
AA
30241
RE
G E
ER
IN
E N
L
RCAH
ORP
SEF
OL
N
S IO
IN
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
M010
M
EC
H
AN
IC
AL
I
SO
M
ET
RI
C
W D
B W
D B
M A
U
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08110306
NOT TO SCALEM010
1 MECHANICAL ISOMETRIC
MECHANICAL
YARD
MECHANICAL
ROOM
ELECTRICAL
ROOM
3" CHWS
3" CHWR
2 1/2" CHWS
2 1/2" CHWR
C H
W R
C H
W S
CH11
CCC12
CCC11
53" CHWS
3" CHWR
8 9
AS11
E15
AHU11
AHU12
MECHANICAL
YARD
MECHANICAL
ROOM
ELECTRICAL
ROOM
TRANSFORMER
PAD
CU PAD
FLAT
CONCRETE
PAD
6" HIGH
CONCRETE PAD
RAISED TANK
ENCLOSURE
AHU11
AHU12
AC12
AC11 A
M
IL
I
L W
BA
D E N
I
A
I I
R
L L
DG
No.
TU
D S
IS
R
E T
E
AA
30241
RE
G E
ER
IN
E N
L
RCAH
ORP
SEF
OL
N
S IO
IN
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
M101
M
EC
H
AN
IC
AL
P
LA
N
W D
B W
D B
M A
U
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08110306
SCALE: 1/8" = 1'10"M101
2 MECHANICAL RENOVATION PLAN
PROVIDE NEW CONCRETE PAD 6" LARGER THAN THE CHILLER IN ALL DIRECTIONS.
PROVIDE PENETRATION THROUGH BRICK WALL ADJACENT TO EXISTING REFRIGERANT LINE PENETRATIONS. SEAL PENETRATION
WEATHER TIGHT.
EXTERIOR CHILLED WATER LINES SHALL BE INSULATED WITH CELLULAR GLASS INSULATION, AND PROVIDED WITH AN ALUMINUM JACKET.
PROVIDE VERTICAL RISER CLAMPS WHERE CHILLED WATER LINES RISE UP WALL TO ABOVE HEAD HEIGHT.
INTERIOR CHILLED WATER LINES SHALL BE INSULATED WITH CELLULAR GLASS INSULATION WITH ALL SERVICE JACKET.
INSTALL NEW CHILLED WATER COIL IN EXISTING AIR HANDLER CABINET IN PLACE OF REMOVED REFRIGERANT COIL. COORDINATE WITH AHU MANUFACTURER (TRANE) FOR SPECIFIC INSTRUCTIONS INCLUDING HOW TO SECURE THE COIL WITHIN THE UNIT. ANY DAMAGE TO
THE EXISTING UNIT DUE TO THE COIL REPLACEMENT SHALL BE REPAIRED.
PROVIDE 1.5" COPPER CONDENSATE DRAIN LINES TO EXISTING FLOOR DRAIN.
PROVIDE NEW TRACER CONTROL PANEL THAT INTERFACES WITH EXISTING TRANE BUILDING CONTROLS, EXISTING METASYS VAV CONTROLLERS, NEW CHILLER, NEW COOLING COIL, EXISTING AIR HANDLERS, AND EXISTING BASE WIDE EMCS.
CHEMICAL TREATMENT POT FEEDER, SEE DETAIL.
PROVIDE HEAT TRACE TO EXTERIOR CHILLED WATER PIPING.
PROVIDE FREEZE STAT TEMPERATURE SENSOR THAT UPON SENSING AIR LOWER THAN 40°F (ADJ.) SHALL INITIATE THE FOLLOWING SEQUENCE: SHUT DOWN AIR HANDLER FAN, CLOSE OUTSIDE AIR DAMPER, OPEN UP CHILLED WATER VALVE 100%, SHUT DOWN CHILLER COMPRESSOR, TURN ON PUMP TO FULL SPEED, NOTIFY THE DDC SYSTEM OF AN ALARM CONDITION.
PROVIDE 8' HIGH VINYL COATED CHAIN LINK FENCE TO CONNECT EXISTING FENCE TO BUILDING TO PROVIDE MECHANICAL ENCLOSURE.
SEE FENCE DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GROUND PIPE SUPPORT, SEE DETAIL FOR ADDITIONAL INFORMATION.
CONNECT TO EXISTING DOMESTIC WATER PIPING IN THIS APPROXIMATE LOCATION, DOWNSTREAM OF THE BACKFLOW PREVENTER.
ROUTE MAKE1UP WATER ASSEMBLY TO AIR SEPARATOR, SEE DETAIL FOR ADDITIONAL INFORMATION.
PROVIDE EMERGENCY HVAC SHUTDOWN SWITCH.
AS PART OF TEST AND BALANCE PORTION OF WORK, BALANCE FAN MOTOR BY ADJUSTING THE VFD AND PROVIDING AN AIR TRAVERSE IN THE EXISTING SUPPLY DUCTWORK. AIRFLOW SHALL BE BALANCED TO THE AIRFLOWS INDICATED IN THE COOLING COIL SCHEDULE.
PROVIDE AIR BALANCE INFORMATION AND VFD HZ SETTING AS PART OF BALANCING REPORT.
RENOVATION KEYED NOTES
SCALE: 1/8" = 1'10"M101
1 MECHANICAL DEMOLITION PLAN
DEMOLISH AND REMOVE CONDENSING UNIT AND
ASSOCIATED REFRIGERANT LINES, INSULATION, AND
SUPPORTS. REFRIGERANT SHALL BE RECOVERED AND
TURNED OVER TO THE OWNER.
DEMOLISH AND REMOVE DIRECT EXPANSION (DX)
COOLING COILS. AIR HANDLER SHALL REMAIN IN USE
FOLLOWING RENOVATION; THEREFORE ANY DAMAGE
TO THE AIR HANDLER THAT OCCURS DURING COIL
REPLACEMENT SHALL BE REPAIRED AT NO ADDITIONAL
COST TO THE OWNER.
CUT CONDUITS, REBARS, SCREWS AND UNISTRUT THAT
ARE PROTRUCING UP THROUGH SLAB. CONDUITS
SHALL BE FILLED TO PREVENT FURTHER WATER
INTRUSION.
DEMOLITION KEYED NOTES
PHASING DESCRIPTION:
EXISTING DX UNITS SHALL REMAIN OPERATIONAL AS
LONG AS POSSIBLE, AND PROVISIONS SHALL BE
IMPLEMENTED TO REDUCE HVAC SYSTEM DOWNTIME
AS MUCH AS POSSIBLE. BEFORE DEMOLITION OF SPLIT
SYSTEMS AND DX COOLING COILS OCCURS, THE
FOLLOWING SHALL BE COMPLETE:
1. CONCRETE PAD AND CHILLER SHALL BE SET.
2. CHILLER SHALL BE POWERED PER
REQUIREMENTS ON ELECTRICAL DRAWINGS.
3. CHILLED WATER LINES SHALL BE INSTALLED,
SUPPORTED, PRESSURE TESTED, AND
INSULATED ADJACENT TO EXISTING
REFRIGERANT LINES TO THE AIR HANDLERS.
4. REPLACEMENT CHILLED WATER COILS SHALL BE
ON SITE AND READY FOR INSTALLATION ONCE DX
COILS HAVE BEEN REMOVED.
5. CHILLED WATER COIL CONNECTIONS WITH
FITTINGS AND DEVICES PER DETAIL SHALL BE
PRE1FABRICATED TO ALLOW QUICK
INSTALLATION ONCE COILS HAVE BEEN
REPLACED.
6. DDC CONTROLS PANEL SHALL BE SET, POWERED,
PROVIDED WITH DATA, CONDUIT RUN,
CONDUCTORS PULLED. SEQUENCES SHALL BE
PRE1INSTALLED ON CONTROL PANEL TO MINIMIZE
IN1FIELD PROGRAMMING REQUIREMENTS.
| Sheets |
| M001 - HVAC NOTES, SCHEDULES, & LEGENDS |
| M002 - HVAC NOTES & DETAILS |
| M003 - HVAC DETAILS |
| M004 - HVAC CONTROLS DETAILS |
| M010 - MECHANICAL ISOMETRIC |
| M101 - MECHANICAL PLAN |