GENERAL ELECTRICAL NOTES
1. BRANCH CIRCUIT WIRING FOR 20A/120V CIRCUITS LESS THAN 100' FROM PANEL TO FARTHEST DEVICE SHALL BE 2-#12s, #12 GND IN 3/4" C. AND 2-#10s, #10 GND IN 3/4" C. FOR CIRCUITS GREATER THAN 100' UNLESS NOTED OTHERWISE. WHERE CONDUCTOR AND RACEWAY SIZE ARE SHOWN AT HOMERUN, SUCH SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT. EXCEPTION: FINAL CONNECTION
TO DEVICES IN OUTLET BOXES IS NOT REQUIRED TO BE LARGER THAN #12.
2. EXPOSED RACEWAYS MAY BE USED IN UNFINISHED SPACES, WHERE EXPLICITLY NOTED ON PLANS AND WHERE APPROVED BY THE
ENGINEER. LAY OUT EXPOSED RACEWAYS TO MINIMIZE THE NUMBER OF VERTICAL RUNS.
3. BRANCH CIRCUIT ROUTING SHALL COMPLY WITH DETAILS ON DRAWINGS AND SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES BEFORE AND DURING CONSTRUCTION. BRANCH CIRCUITS SHALL BE ROUTED OVERHEAD UNLESS PRIOR APPROVAL HAS
BEEN GRANTED BY THE ARCHITECT AND ENGINEER.
4. A FIRESTOP SYSTEM SHALL BE USED TO SEAL ALL PENETRATIONS OF ELECTRICAL CONDUITS AND CABLES THROUGH FIRE-RATED PARTITIONS. THE FIRESTOP SYSTEM SHALL CONSIST OF A FIRE-RATED CAULK TYPE SUBSTANCE AND HIGH TEMPERATURE FIBER INSULATION BY STI OR APPROVED EQUAL. ONLY METAL CONDUIT SHALL BE USED TO PENETRATE FIRE-RATED PARTITIONS. SEE
ARCHITECTURAL DRAWINGS FOR ALL LOCATIONS OF FIRE-RATED WALLS.
5. THE USE OF MC CABLE IS NOT ALLOWED, UNLESS NOTED OTHERWISE.
6. WHEREVER THE WORD "PROVIDE" IS USED ON THE ELECTRICAL DRAWINGS, IT SHALL BE INFERRED TO MEAN "FURNISH AND
INSTALL", UNLESS NOTED OTHERWISE.
7. THE ARRANGEMENT, GROUPING, AND ROUTING OF BRANCH CIRCUITS SHALL BE PROVIDED AT THE CONTRACTOR'S DISCRETION IN
ACCORDANCE WITH GENERALLY ACCEPTED PRACTICE FOR ELECTRICAL WORK, THE NATIONAL ELECTRICAL CODE REQUIREMENTS, LOCAL ORDINANCES, AND THE FOLLOWING: 1 - A COMMON NEUTRAL MAY NOT BE INSTALLED IN A HOMERUN. 2 - MULTIPLE SINGLE- POLE BRANCH CIRCUITS (UP TO 3 HOTS, 3 NEUTRALS AND 1 GROUND) RATED FOR 30A OR LESS MAY BE PULLED INTO A SINGLE RACEWAY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING THE RACEWAYS AND DE-RATING CONDUCTORS PER NEC 310.15.
3 - A GROUND CONDUCTOR SHALL BE PROVIDED IN ALL RACEWAYS UNLESS NOTED OTHERWISE.
1. ALL EXISTING ELECTRICAL EQUIPMENT INDICATED FOR DEMOLITION SHALL BE PROPERLY DISPOSED OF BY THE CONTRACTOR.
GENERAL DEMOLITION NOTES
1. AREAS OF WORK EXIST FOR THIS PROJECT WHICH WERE NOT ACCESSIBLE OR HAD LIMITED ACCESS DURING DESIGN. AS SUCH, CONTRACTOR SHALL VERIFY ALL UTILITIES IN AREA OF WORK BEFORE DEMOLITION OF ANY SERVICE. ANY ELECTRICAL COMPONENTS NOT SHOWN SHALL BE IDENTIFIED AND THE ENGINEER SHALL BE NOTIFIED AS SOON AS POSSIBLE. NO ELECTRICAL REWORK SHALL BE COMMENCED WITHOUT COORDINATION WITH THE ENGINEER. WHERE INFORMATION SHOWN ON THESE DRAWINGS CONFLICTS WITH VERIFIED FIELD CONDITIONS, IT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A FIRESTOP SYSTEM IN ALL PENETRATIONS OF FIRE-RATED FLOORS AND WALLS CREATED BY THE REMOVAL OF EXISTING ELECTRICAL CONDUIT OR CABLES, AS WELL AS THOSE CREATED BY NEWLY
INSTALLED CONDUITS AND SLEEVES.
GENERAL EXISTING CONDITION NOTES
J
JUNCTION BOX (CEILING MOUNTED),
"X" INDICATES JUNCTION BOX TYPE
J
JUNCTION BOX (WALL MOUNTED), "X"
INDICATES JUNCTION BOX TYPE
J
JUNCTION BOX (MOUNTING TYPE NOTED ON
PLANS), "X" INDICATES JUNCTION BOX TYPE
X
X
X
DISCONNECT SWITCH (FUSIBLE OR
NON-FUSIBLE)
DISCONNECT SWITCH (ENCLOSED
CIRCUIT BREAKER)
C B
POWER AND TELECOMMUNICATIONS SYMBOL LEGEND
METERM
PANELBOARDTRANSFORMER
EQUIPMENT AND SIGNAL SYMBOL LEGEND
DESCRIPTIONSYMBOL SYMBOL DESCRIPTION
DESCRIPTIONSYMBOL SYMBOL DESCRIPTION
SD SMOKE DETECTOR (DUCT MOUNTED)CONTROL PANEL, "X" INDICATES TYPE
X
DEMOLISHED
EXISTING TO REMAIN
NEW WORK
DESCRIPTIONSYMBOL
LINE LEGEND
COMPONENT IMPORTANCE FACTOR (Ip)
COMPONENT
IDENTIFICATION
SEISMIC RESTRAINT
REQUIREMENT
NOTES SEISMIC RESTRAINT REQUIREMENT
ROOF MOUNTED RESTRAIN ALL RESTRAIN ALL
FLOOR MOUNTED RESTRAIN ALL RESTRAIN ALL
WALL MOUNTED RESTRAIN ALL RESTRAIN ALL
COMPONENT SUPPORTS RESTRAIN ALL RESTRAIN ALL
RESTRAIN ALL RESTRAIN ALL
SINGLE CONDUIT >3" >1"
CABLE TRAY/BUS DUCT
TRAPEZED CONDUIT
COMPONENT CERTIFICATION
(SEE NOTE 5) NOT REQUIRED REQUIRED
1.0 1.5
NOTES
NOTES:
1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED
DUCTWORK, PIPING AND CONDUIT.
2. RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4' OR LESS ABOVE A FLOOR AND HAS FLEXIBLE CONNECTIONS BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT.
3. ALL NON-DUCTILE PIPING (I.E. PLASTIC) MUST BE RESTRAINED.
4. RESTRAINT IS NOT REQUIRED IF SUSPENDED 12" OR LESS FROM THE STRUCTURE AND THE HANGERS ARE DETAILED TO AVOID SIGNIFICANT BENDING OF THE HANGERS AND THEIR ATTACHMENTS AND PROVISIONS ARE MADE FOR PIPING TO ACCOMMODATE EXPECTED
DEFLECTIONS.
5. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BY ENGINEER OF
RECORD.
6. THE RESTRAINT OF PENDANT, LAY-IN AND CAN LIGHTS IS GOVERNED BY "CISCA-04 FOR SEISMIC ZONES" (CEILINGS AND INTERIOR SYSTEMS
CONSTRUCTION ASSOCIATION).
SUSPENDED EQUIPMENT
PENDANT, LAY-IN AND CAN
LIGHTS
REQUIRED REQUIRED
PER IBC-2015/ASCE 7-10
SEISMIC REQUIREMENTS FOR ELECTRICAL SYSTEMS
EMERGENCY LIGHTS EXIT LIGHTSALL ASSOCIATED ELECTRICAL WORK UNLESS NOTED OTHERWISE
A. EQUIPMENT, APPLIANCES AND SUPPORTS (INCLUDING ROOF CURBS AND ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINT IS REQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY. SEE EQUIPMENT
SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR DESIGNATIONS.
B. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT.
C. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL. SUBMITTALS MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS.
D. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF
THE SEISMIC SUBMITTAL.
E. SEISMIC RESTRAINTS FOR CONDUIT, CABLE TRAY AND BUS DUCT MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC
RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS.
F. REFER TO ASCE 7-10 FOR SEISMIC INSTALLATION GUIDELINES.
RESTRAIN IF ANY CONDUIT ON
TRAPEZE > 1"
RESTRAIN IF TOTAL WEIGHT OF
SUPPORTED COMPONENT > 10 LBS/FT
1,2
3,4
1,2
1,2
3,4
ELECTRICAL COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION
Ip = 1.0 Ip = 1.5
SEISMIC DESIGN CATEGORIES D,E,F
RESTRAIN IF ANY CONDUIT
ON TRAPEZE > 3"
RESTRAIN IF TOTAL WEIGHT
OF SUSPENDEDCOMPONENT
> 10 LBS/FT
No.
TU
S A
29529
RCAH OL INN
E E
D
R
P
F ESS IO O
E C
S N
E I L R
L A
G I
E N
N
I
A
S W
D LA
D
I L
J R
V
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
E001
EL
EC
TR
IC
AL
N
O
TE
S, A B B
RE
VI
AT
IO
N S, LE
GE
N
DS
M A
R M
A R
D A
W
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08-10306
CONDUIT COLOR SCHEDULE
COMMUNICATION SYSTEM BLACK
FIRE ALARM SYSTEM RED
HVAC CONTROLS BLUE
NORMAL POWER SILVER
ELECTRICAL CODES AND STANDARDS
CODE DESCRIPTION
IBC (2015) INTERNATIONAL BUILDING CODE
IECC (2009) INTERNATIONAL ENERGY CONSERVATION CODE
IFC (2015) INTERNATIONAL FIRE CODE
NFPA 70 (2014) NATIONAL ELECTRICAL CODE
NFPA 72 (2013) NATIONAL FIRE ALARM AND SIGNALING CODE
UFC 3-501-01 (OCT 6, 2015) ELECTRICAL ENGINEERING
UFC 3-520-01 (OCT 6, 2015) INTERIOR ELECTRICAL SYSTEMS
UFC 3-550-01 (OCT 6, 2015) EXTERIOR ELECTRICAL POWER DISTRIBUTION
ELECTRICAL ABBREVIATIONS
ABBR DESCRIPTION
(E) EXISTING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
BAS BUILDING AUTOMATION SYSTEM
BFG BELOW FINISHED GRADE
BOD BOTTOM OF DEVICE
cd CANDELA
FACP FIRE ALARM CONTROL PANEL
FDS FUSED DISCONNECT SWITCH
GFCI GROUND-FAULT CIRCUIT-INTERRUPTING
GFI GROUND-FAULT INTERRUPTING
GP GENERAL PURPOSE
J-BOX JUNCTION BOX
KW KILOWATTS
NEC NATIONAL ELECTRICAL CODE
NFDS NON-FUSED DISCONNECT SWITCH
OC ON CENTER
SPD SURGE PROTECTION DEVICE
UNO UNLESS NOTED OTHERWISE
W/ WITH
WP WEATHERPROOF
XFMR TRANSFORMER
CONTROL
PANELS
DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
JUNCTION
BOX/SWITCH
DESCRIPTION
HT HEAT TRACE
EQUIPMENT CONNECTION SCHEDULE
UNIT I.D. VOLTS # OF POLES LOAD (VA) BRANCH CIRCUIT WIRING DISCONNECT / STARTER NOTES
AIR COOLED CHILLERS
CH-1 480 V 3 117059 3 #1/0, #6(G) IN 1-1/2"C DISCONNECT FURNISHED WITH EQUIPMENT
EXISTING
UTILITY
TRANSFORMER
EXISTING
XFMR
'(E)TXL1'
M
EXISTING
SWITCHBOARD
'(E)MDP'
800A MCB
S.E. RATED
EXISTING
PANEL
'(E)XL1'
MAIN
ELECTRICAL
ROOM
FIRST FLOOR
BUILDING EXTERIOR
EXISTING
SPD
EXISTING UTILITY
METER/CT CABINET
EXISTING
CONDUCTORS
AND CONDUIT
EXISTIN
G XFMR
'(E)TL1'
EXISTING
PANEL
'(E)L1'
EXISTING
CONDUCTORS
AND CONDUIT
EXISTING
'(E)ATS'
EXISTING
PANEL
'(E)XDP'
EXISTING
PANEL
'(E)XH1'
EXISTING
CONDUCTORS
AND CONDUIT
EXISTING CONDUCTORS
AND CONDUIT
EXISTING
PANEL
'(E)H1'
EXISTING CONDUCTORS
AND CONDUIT
EXISTING CONDUCTORS
AND CONDUIT
EXISTING CONDUCTORS
AND CONDUIT
GENERAL NOTE:
ONE-LINE DIAGRAM PROVIDED FOR REFERENCE ONLY.
TYPICAL TRANSFORMER
(SEPARATELY DERIVED
SYSTEM)
WHERE APPLICABLE TYPICAL
SECONDARY
PANEL
TYPICAL
PANEL
NEUT GRD
E G
C
EGC
SBJ
SIZE AS SECONDARY GEC
NEUT GRD
NEUTRAL
GECG
E
C
TRANSFORMER
NEUTRAL LUG
GROUND
METAL OUTLET BOX
GREEN HEX HEAD
GROUNDING SCREW
[250.126]
PROVIDE SELF-GROUNDING
RECEPTACLE, OR BOND BOX
USING LISTED CLIP OR
GROUNDING SCREW, DO NOT
USE SHEET METAL SCREW
[250.8] [250.146]
EGC
SIZE
NEUTRALS TO
MATCH PHASE
EGC
SIZE
NEUTRALS TO
MATCH PHASE
GROUNDING NOTES:
1. NUMBERS IN BRACKETS REFER TO SPECIFIC SECTIONS OF THE NATIONAL ELECTRICAL CODE.
2. ALL UNDERGROUND OR OTHERWISE INACCESSIBLE GROUND CONNECTIONS AND SPLICES SHALL BE
EXOTHERMICALLY WELDED [250.68].
3. GROUND ELECTRODE FOR SEPARATELY DERIVED SYSTEMS SHALL BE THE NEAREST METAL WATER PIPE OR
STRUCTURAL METAL. IF EITHER IS NOT AVAILABLE, PROVIDE GROUNDING CONDUCTOR BACK TO MAIN GROUND BUS
AT SERVICE ENTRANCE.
4. PROVIDE A GROUND WIRE IN ALL CONDUITS.
5. EARTH SHALL NOT BE USED AS THE SOLE GROUND RETURN PATH FOR ANY EQUIPMENT POWERED UNDER THIS
PROJECT. OTHERWISE OVERCURRENT PROTECTION MIGHT NOT WORK, OR IT MIGHT CAUSE POWER QUALITY
PROBLEMS.
6. NO ALUMINUM SHALL BE USED FOR GROUNDING WORK WITHOUT THE SPECIFIC WRITTEN PERMISSION OF THE ENGINEER. EXCEPTION: ALUMINUM BUILDING STRUCTURAL MATERIALS SHALL BE BONDED WITH LISTED ALUMINUM
EQUIPMENT WITH ALUMINUM TO COPPER CONNECTORS FOR ROUTING COPPER EGC'S.
7. ALL METAL ENCLOSURES AND RACEWAYS SHALL BE BONDED TO GROUND [250.86]. FOR CIRCUITS OVER 250V PROVIDE
BOND PER [250.97], STANDARD LOCKNUTS ARE NOT ACCEPTABLE.
8. PROVIDE EGC CONNECTED TO ANY JUNCTION BOX WHERE SPLICE IS MADE [250.148].
9. PROVIDE BOND TO EXPOSED METAL ON ALL MOTORS, PUMPS, AND LIGHTING FIXTURES PER [250.112].
GROUNDING LEGEND
ABBR. DESCRIPTION SIZE
SBJ SYSTEM BONDING JUMPER *
GEC GROUNDING ELECTRODE CONDUCTOR ***
EGC EQUIPMENT GROUNDING CONDUCTOR **
* SIZE PER TABLE 250.66 OF THE NEC OR
12.5% OF CONDUCTOR SIZE [250.28].
** SIZE PER TABLE 250.122.
*** SIZE PER ONE-LINE DIAGRAM.
No.
TU
S A
29529
RCAH OL INN
E E
D
R
P
F ESS IO O
E C
S N
E I L R
L A
G I
E N
N
I
A
S W
D LA
D
I L
J R
V
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
E010
EL
EC
TR
IC
AL
O
N E-
LI
N E
DI
AG
RA
M
M A
R M
A R
D A
W
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08-10306
5NOT TO SCALEE010
2 EXISTING PARTIAL ONE-LINE DIAGRAM
Notes:
TOTAL ADDITIONAL CURRENT: 141 A
TOTAL ADDITIONAL LOAD: 117060 VA
PANEL TOTALS
TOTAL PHASE CURRENT: 141 A 141 A 141 A
TOTAL PHASE LOAD: 39020 VA 39020 39020
41 0 VA / 0 VA 42
39 0 VA / 0 VA 40
37 0 VA / 0 VA
3 30 A EXISTING
35 36 33 34 31 32
29 0 VA / 0 VA 30
27 0 VA / 0 VA 28
EXISTING TRANSFER SWITCH (E)ATS 150 A 3
0 VA / 0 VA 26
23 0 VA / 39020 VA 24
21 0 VA / 39020 VA 22
EXISTING 150 A 3
0 VA / 39020 VA
3 150 A * CHILLER CH-1
17 0 VA / 0 VA 18
15 0 VA / 0 VA 16
** AC-2 70 A 3
0 VA / 0 VA
3 15 A EXISTING
11 0 VA / 0 VA 12
9 0 VA / 0 VA 10
** AC-1 90 A 3
0 VA / 0 VA
3 80 A EXISTING XFMR (E)TL2
5 0 VA / 0 VA 6
3 0 VA / 0 VA 4
PANEL (E)H1 20 A 3
0 VA / 0 VA
3 70 A EXISTING XFMR (E)TL1
CKT
NO.
CIRCUIT DESIGNATION TRIP POLES A B C POLES TRIP CIRCUIT DESIGNATION CKT
NO.
Mounting: SURFACE Enclosure: Type 1 SERVICE ENTRANCE RATED Supply From: Wires: 4 Mains Type: MAIN CIRCUIT BREAKER
Location: ELECTRICAL ROOM 132 Phases: 3 Mains Rating: 800 A Panel Name: (E)MDP Volts: 480/277 Wye A.I.C. Rating: EXISTING
REVISED PANELBOARD SCHEDULE
* PROVIDE NEW CIRCUIT BREAKER, IN EXISTING SPACE, MANUFACTURED AND UL LISTED FOR INSTALLATION IN EXISTING GE SPECTRA SERIES PANELBOARD.
** EXISTING CIRCUIT BREAKER SHALL BE ABANDONED AND BECOME A SPARE WHEN EQUIPMENT IS REMOVED.
***"TOTAL ADDITIONAL CURRENT" INDICATED IS ONLY THE NEW LOADS ADDED TO THE EXISTING PANEL. IT DOES NOT INCLUDE EXISTING LOADS THAT REMAIN
OR EXISTING LOADS THAT WERE REMOVED.
REVISE CIRCUIT LABELS AND PANEL SCHEDULES AT CONCLUSION OF WORK TO BE AN ACCURATE REPRESENTATIVE OF CIRCUITS.
UTILTY XFMR
NOT TO SCALEE010
1 GROUNDING DETAIL
J
J
AHU-1
AHU-2
CH-1
MECHANICAL
ROOM
MECHANICAL
YARD
ELECTRICAL
ROOM
132MEN'S
SUPPLY &
STORAGE
BREAK ROOM
(E)L1
(E)H1
(E)XH1
(E)FACP
(E)TL1
(E)MDP
(E)ATS
(E)XDP
(E)XL1
(E)XTL1
(E)MDP: 20,22,24
UTILITY XFMR
E101
(E)L1: 1
NEW FENCE, SEE FENCE
DETAILS AND SPECIFICATIONS
FOR ADDITIONAL
INFORMATION
(E)L1: 2
(E)L1: 3
WP
AHU-1
AHU-2
MECHANICAL
ROOM
MECHANICAL
YARD
ELECTRICAL
ROOM
MEN'S
SUPPLY &
STORAGE
BREAK ROOM
(E)L1
(E)H1
(E)XH1
(E)FACP
(E)TL1
(E)MDP
(E)ATS
(E)XDP
(E)XL1
(E)XTL1
UTILITY XFMR
AC-1
AC-2
AC-1
AC-2
EXISTING
PANEL (E)MDP
3/4" AND 1-1/2" CONDUIT
CHILLER
3/4" CONDUIT TO
CHILLER HEAT TRACE
3/4" CONDUIT TO
CHILLER HEAT TRACE
No.
TU
S A
29529
RCAH OL INN
E E
D
R
P
F ESS IO O
E C
S N
E I L R
L A
G I
E N
N
I
A
S W
D LA
D
I L
J R
V
O
I
R A
D
M A
N
COM
MO
IT Y
B I L
A/E SEAL
A
B
C
D
A
B
C
D
4 5321
21 3 4 5
IF SHEET IS LESS THAN 22"x34" (ANSI D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
RECORD DRAWING DATE
DRAWING SIZE:
PROJECT NO.
OFSHEET
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D
D A T E
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
D R A W
IN
G
R E V
IS
IO
N S
D A T E
P R E P
B Y
A P P R 'D
RECORD DRAWING DATE
ANSI D (22"x34")DRAWING SIZE:
PROJECT NO.
OFSHEET
D E
P A
R
TM
E N
T O
F
TH
E A
IR
F
O R
C E
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D R E V
D A
TE
D E S C R
IP
T
IO
N
D R A W
IN
G
R E V
IS
IO
N S
C H K
B Y
D R A W N
B Y
D S G N
B Y
I
R A
D
M A
N
COM
MO
IT Y
B I L
A P P R O V E D
B Y
F O R
J O
IN
T
B A S E
C H A R L E S T O N
D A T E
G
E W
B
A IR AS
I N 62 8T H
D W
G C
O N
S U
LT
IN
G E
N G
IN
E
E R
S , I
N C
A
N N
A K
N A
P P
B
LV
D
S U
IT
E
M T
. P
LE
A S
A N
T , S
C
JO
IN
T B
AS
E
C H
AR
LE
S
TO
N
C H A R L E S T O N S C
E101
EL
EC
TR
IC
AL
P
LA
N S
M A
R M
A R
D A
W
/0
2/
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
JB
C
AB
B ld g Ae ri al D el iv er y
Fa ci lit y
Fa ci lit y
Fa ci lit y
Fa ci lit y
DKFX 08-10306
SCALE: 1/8" = 1'-0"E101
2 ELECTRICAL RENOVATION PLAN
SCALE: 1/8" = 1'-0"E101
1 ELECTRICAL DEMOLITION PLAN
DEMOLITION KEYNOTES:
1 DISCONNECT EQUIPMENT AND REMOVE MOTOR STARTER
AND/OR DISCONNECT SWITCH. REMOVE WIRING TO
EXISTING MAIN DISTRIBUTION PANEL (E)MDP. REMOVE
CONDUIT ABOVE GRADE. CONDUIT BELOW GRADE SHALL
BE CUT AT GRADE AND SEALED WATERTIGHT.
REMOVE ALL EXPOSED CONTROL CONDUIT TO AC-1 & AC-2.
WHERE CONDUIT PENETRATES WALLS, FLOORS, OR
ASPHALT; CUT CAP AND SEAL TO BE WATERTIGHT.
RENOVATION KEYNOTES:
PROVIDE COVER PLATES ON EXISTING "LB'S" FOR PRIMARY
SERVICE CONDUCTORS.
ROUTE CONDUIT OVERHEAD TO AVOID BEING A TRIP
HAZZARD. ATTACH TO EXISTING WALL AND CHILLER FRAMING
FOR SUPPORT. SEE DETAIL. WHERE CONDUIT PENETRATES
EXTERIOR WALL. SEAL PENETRATION TO BE WATERTIGHT.
ATTACH CONDUIT TO CHILLER FRAME AND CONNECT TO
CONTROL PANEL. SEE DETAIL.
CONNECTION TO HEAT TRACE FOR CHILLED WATER PIPING.
CONNECTION TO HEAT TRACE PROVIDED WITH CHILLER.
COORDINATE EXACT REQUIREMENTS WITH CHILLER
SUPPLIER.
PROVIDE NEW 20A-1P CIRCUIT BREAKER MANUFACTURED
AND UL LISTED FOR INSTALLATION IN EXISTING GE "A" SERIES
CIRCUIT BREAKER PANELBOARD.
SCALE: 1/2" = 1'-0"E101
3 CHILLER POWER SECTION
GENERAL NOTES:
1. SCOPE OF WORK IS GENERALLY LIMITED TO MECHANICAL
ROOM 131, ELECTRICAL ROOM 132 AND MECHANICAL YARD
133; EXCEPT FOR WHAT'S REQUIRED FOR HVAC CONTROLS
WORK.
| Sheets |
| E001 - ELECTRICAL NOTES, ABBREVIATIONS, & LEGENDS |
| E010 - ELECTRICAL ONE-LINE DIAGRAM |
| E101 - ELECTRICAL PLANS |