Attachment__10_Specification_Section_28_31_76_JB_CHS_INTERIOR_FIRE_ALARM_AND_MASS_NOTIFICATION_SYSTEM_Dated_15_Feb.pdf

PDF 789 KB Posted

Attached to
Add/Rpr IMC Fire Suppression System Federal contract opportunity
Solicitation number
FA4418-16-R-0028
Issued by
Department of the Air Force Air Mobility Command

About this file

Attachment #10 Specification Section 28 31 76 JB CHS INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM Dated 15 Feb for FA4418-17-R-0003-0007 Add-Rpr IMC Fire Suppression System

View the file

Other files for this federal contract opportunity

Other files attached to Add/Rpr IMC Fire Suppression System, newest first.
File Type Posted
Attachment__9_Addendum__2_dated_15_Feb_17..pdf PDF
Attachment__13_Specification_Section_26_42_15.00_10_CATHODIC_PROTECTION_SYSTEM_(STEEL_WATER_TANKS)_dated_15_Feb_17.pdf PDF
Attachment__11_Drawing_35_SB-101_Structural_Plan,_Elevations_and_Details_rev.01_Dated_13_Feb_17..pdf PDF
Attachment__12_Specification_Section_33_16_15_WATER_STORAGE_STEEL_TANKS_dated_15_Feb_17.pdf PDF
FA4418-17-R-0003-0007.pdf PDF
FA4418-17-R-0003-0006.pdf PDF
FA4418-17-R-0003-0005.pdf PDF
FA4418-17-R-0003-0004.pdf PDF
Attachment__8_-_FA4418-17-R-0003_Section_26_42_15.00_10_CATHODIC_PROTECTION_SYSTEM_(STEEL_WATER_TANKS).pdf PDF
Attachment__6_-_FA4418-17-R-0003_Davis_Bacon_Wage_Determination_dated_6_Jan_2017.pdf PDF
Attachment__7_-_FA4418-17-R-0003_Addendum__1_dated_12_Jan_17.pdf PDF
FA4418-17-R-0003-0003.pdf PDF
Pre-bid_QA_FA4418-17-R-0003_12_Jan.pdf PDF
Pre-bid_QA_FA4418-17-R-0003_11_Jan.pdf PDF
FA4418-17-R-0003-0002.pdf PDF
Pre-bid_QA_FA4418-17-R-0003_10_Jan_2017.pdf PDF
FA4418-17-R-0003-0001.pdf PDF
Site_Visit_Attendees_Sign-In_Sheet_-_Fire_Supp._Sys.pdf PDF
Site_Visit_Briefing_Slides_-_Fire_Supp._Sys.pdf PDF
Site_Visit_Minutes_-_Fire_Supp_Sys.pdf PDF
Attachment__1_-_FA4418-17-R-0003_Specifications,_IMC_Fire_Suppression_dated_Oct_2013.pdf PDF
Attachment__5_-_FA4418-17-R-0003_Green_Procurement_Form_dated_Dec_2016.pdf PDF
Attachment__4_-_FA4418-17-R-0003_FAA_Form_7460-2_dated_Oct_2013.pdf PDF
Attachment__3_-_FA4418-17-R-0003_FAA_Form_7460-1_dated_Fed_2012.pdf PDF
Attachment__2_-_FA4418-17-R-0003_Drawings,_AddRepair_IMC_Fire_Suppression_System.pdf PDF
FA4418-17-R-0003.pdf PDF
Attachment__6_-_FA4418-17-R-0003_Davis_Bacon_Wage_Determination_dated_Aug_2016.pdf PDF
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B Final Design Construction Documents

Section 28 31 76 JB CHS page 1

SECTION 28 31 76

(Modified specifically for use at JBC-ABW and JBC-NWS)

INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM

02/17

PART 1 GENERAL-LIFE SAFETY SYSTEM

This section establishes the requirements for an integrated Fire Alarm System (FAS). Each FAS shall include only new components meeting the requirements of NFPA, FM, UL, and ADA standards, all applicable local, state and federal regulations, manufacturer’s recommendations, and specifications identified in this section.

Each FAS shall be a complete, supervised, non-coded, analog-addressable system, installed in a class A configuration per NFPA 72. Each FAS shall provide point reporting to the FACP. The FACP shall in turn provide point reporting to the Monaco D-21 Central Receiving Station at the Joint Base Charleston (Air Base Wing) Fire Department and the Joint Base Charleston Naval Weapons Station (JBC-NWS) Fire Department. Point reporting, also known as point to point reporting, is the capability of the FACP to relay the individual status/condition/location of each addressable device as well as certain system components (such as SLCs) to the D-21 in real time. The FAS shall be tested and perform as a critical life-safety system. The FAS shall be compatible with and shall communicate seamlessly with the appropriate D-21 Central Receiving Station without impairing operational function or reliability of any existing FAS. Note that this SECTION is applicable to all facilities located at JBC-ABW and JBC-NWS.

1.1 RELATED SECTIONS

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS

1.2 REFERENCES

The publications listed below form a part of this section to the extent referenced within the text. The latest edition/revision of each publication available at the time of contract award shall apply unless otherwise noted.

ACOUSTICAL SOCIETY OF AMERICA (ASA)

ASA S3.2--Method for Measuring the Intelligibility of Speech Over Communication Systems (ASA 85)

AMERICAN DISABILITY ACT (ADA)

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ANSI/ASA S3.41-1990 Audible Emergency Evacuation Signal

AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

A17.1--Safety Code for Elevators and Escalators

DIRECTOR OF CENTRAL INTELLIGENCE DIRECTIVE (DCID)

UFC 4-010-05, Sensitive Compartmented Information Facilities Planning, Design, and Construction.

Attachment #10 FA4418-17-R-0003

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 2

ELECTRONIC INDUSTRIES ASSOCIATION (EIA)

ANSI/EIA/TIA-222-G-2005 Steel Antenna Tower & Antenna Supporting Structures

ENGINEERING TECHNICAL LETTER (ETL)

ETL 02-15-Fire Protection Engineering Criteria-New Aircraft Facilities

FACTORY MUTUAL ENGINEERING & RESEARCH CORPORATION (FM)

FM P7825a--Approval Guide For Fire Protection

FEDERAL STANDARDS (FED-STD)

FED-STD 595 (Rev B) Colors

INSTITUTE OF ELECTRICAL & ELECTRONICS ENGINEERS (IEEE)

C62.41.1-2002--Guide on the Surges Environment in Low-Voltage AC Power Circuits (1000 V and Less) C62.41.2-2002--Recommended Practice on Characterization of Surges in Low- Voltage AC Power Circuits (1000 V and Less)

INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)

60268-16--Sound System Equipment-Part 16

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA ICS 6 1993 (R2001, R2006) Enclosures for Industrial Control

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

01---Fire Code 70---National Electrical Code 72---National Fire Alarm Code 78---Lightning Protection Code 90A--STD for the Installation of AC and Ventilating Systems 101--Life Safety Code 170--Fire Safety Symbols 241--Safeguarding Construction, Alt, & Demolition Operations 1221-Installation Maint & Use of Fire Service Communication Systems

UNDERWRITERS LABORATORIES (UL)

006--Rigid Metal Conduit 228--Door Closers-Holders, With or W/O Integral Smoke Detectors 268--Standard for Smoke Detection for Fire Alarm Signaling Systems 268A- Smoke Detectors for Duct Application 464--Standard for Audible Signal Appliances 521--Heat Detectors for Fire Protective Signaling Systems 797--Steel Electrical Metallic Tubing 864--Control Units and Accessories for Fire Alarm Systems 1242-Electrical Intermediate Metal Conduit 1480-Standard for Safety Speakers for Fire Alarm, Emergency, and Commercial and Professional Use 1638-Visual Signaling Appliances Private Mode Emergency and General Utility Signaling 1971-Signaling Devices for the Hearing Impaired 2017-STDs for Safety for General Purpose Signaling Devices and Systems, UL---Electrical Construction Equipment Directory, UL---Fire Protection Equipment Directory

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 3

UNIFIED FACILITIES CRITERIA (UFC)

03-600-01—Fire Protection Engineering for Facilities 03-601-02-Operations and Maintenance: Inspection, Testing, and Maintenance of Fire Protection Systems 04-010-01—DoD Minimum Antiterrorism Standards for Buildings 04-021-01—Design and O&M For Building Mass Notification System

UNITED FACILITIES GUIDE SECTIONS (UFGS)

84 00-----------FIRESTOPPING

71 00-----------DOOR HARDWARE FOR DOOR RELEASE/DOOR UNLOCKING

14 24 00--------HYDRAULIC ELEVATORS

21 13 13.00 20--WET PIPE SPRINKLER SYSTERM, FIRE PROTECTION

21 13 18.00 10--PREACTION AND DELUGE SPRINKLER SYSTEMS, FIRE PROTECTION

21 13 19.00 20--DELUGE PREACTION FIRE SPRINKLER SYSTEMS

21 30 00--------FIRE PUMPS

23 00 00--------AIR SUPPLY, DISTRIBUTION, VENTILATION & EXHAUST SYSTEMS

US ARMY CORPS OF ENGINEERS

Engineering Manual (EM), EM 385-1-1, Safety and Health Requirements

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

47 CFR 15-------Radio Frequency Devices

OTHER ORGANIZATIONS

Central Intelligence Directive (DCID 6/9), Manual for Physical Security Standards for Sensitive Compartmented Information Facilities

1.3 DEFINITIONS

Equipment, devices and functions mentioned in this specification or on the drawings, as well as commonly used FAS equipment, are defined as follows:

a. Authority Having Jurisdiction (AHJ): The AHJ responsible for enforcing the requirements of applicable codes, standards, and for approving equipment, materials, installations, and procedures is the Joint Base Charleston Air Base Wing 628 Civil Engineer Squadron (628 CES/CEF), Fire Services Department.

b. Central Receiving Station: The central receiving station is an existing Factory Mutual approved Monaco Enterprises Inc. model D-21 Incident Management System transceiver located at the JBC-ABW Fire Department, transmitting and receiving encoded radio signals at 138.9250 MHz, for communicating with the FAS transceiver Fire Alarm Control Panel (FACP) at each building on JBC-ABW and, an identical D-21, located at the JBC-NWS Fire Department, transmitting and receiving signals at 143.5250 MHz for communicating with the FAS transceiver FACP at each building on JBC-NWS.

Hereafter the central receiving station at JBC-ABW and at JBC-NWS will each be identified merely as “D-21.”

c. Analog/Addressable System: A system where multiple signals are transmitted via the same conduction path to a remote fire alarm control unit and FACP, decoded and separated so that each signal will initiate the specified response.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 4

d. Hard Wired System: A system where alarm and supervisory initiating devices are directly connected, through individual dedicated conductors, to a central control panel without the use of analog/addressable circuits or devices.

e. Interface Unit (Monitor Module): An addressable device which is connected to a non-addressable device for the purpose of relaying the status/condition of the non-addressable device to the analog/addressable FACP.

f. Class A addressable system with point reporting: A Class A system as defined in NFPA 72 with each FAS device reporting individually to the FACP and the FACP continuously relaying the status of that device to the D-21. This system is also referred to as “device point reporting” or “point-to-point”. In device point reporting systems, the status of each device is reported back to the D-21 through the FACP. This is in contrast to a zone reporting system wherein s e v e r a l devices are lumped into a zone. In a Class A system, devices are connected by circuits configured such that an open circuit on one or both of the incoming or outgoing conductors at the same location does not prevent reporting of each device on the circuit.

g. Class B non-addressable system: Class B non-addressable circuits are 2 wire circuits which terminate in an end-of-line device as defined in NFPA

72. In Class B circuits, a single open (or break) in either conductor will disable any/all devices located between the open/break and the end of line device.

h. Notification Appliance Circuits (NACs): The FACP provides Class A NAC circuits to supply power to each o f s e v e r a l notification appliances.

Each NAC is monitored and controlled by the FACP for fire events and by the MNS panel for MNS events.

i. Signal Line Circuit (SLC): A SLC is one of up to 8 circuits reporting to the FACP, configured for Class A operation, with each circuit having the capacity to support up to 99 addressable sensors (smoke or heat) and up to 99 addressable modules (control, monitor, NAC, and interface). Alarm, supervisory or trouble conditions are transmitted by the FACP radio transmitter to the D-21 reporting the status/location of each individual device. Equipment and/or device faults, including command faults, missing device, early warning, maintenance alert, communications loss, IDC, NAC, SLC, power and battery faults are also transmitted by the FACP to the D-21 instantaneously.

j. Notification Appliance Circuit (NAC) Extenders: In the event the quantity of notification appliances exceeds the capacity of the FAS, NAC extenders must be provided to power those extra appliances. NAC extenders are controlled from the FACP/NAC circuits by means of a synchronization module. Each NAC extender has the capacity to provide power for up to 4 Class A NACs. Each NAC extender has its own 120 Volt AC primary power, backed up with batteries and a battery charger. NAC extenders are enclosed in a steel panel, red in color, keyed the same as the FACP. Each NAC extender is monitored by the FACP for trouble conditions. All NACs, IDCs, and SLCs remain functional if the conductors between them are severed at any common point.

k. Initiating Device Circuits (IDCs): The FACP provides two Class A or four Class B IDCs. Each IDC system has an interconnected riser loop or network with Class A supervision for connection to FACP/MNS panels.

l. Remote Fire Alarm and Mass Notification Control Unit: A control panel, electronically remote from the fire alarm and mass notification control panel, that receives inputs from automatic and manual fire alarm devices; may

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 5 supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the FACP.

m. Fire Alarm and Mass Notification Control Panel (FACP/FMCP): A master control panel having the features of a fire alarm and mass notification control unit where fire alarm and mass notification control units are interconnected. The FACP/FMCP has central processing, memory, input and output terminals.

n. Riser Diagram: A riser diagram is a drawing showing the circuit connections to each of the FAS devices installed throughout the building, each sheet not less than 30” X 42,” including terminal cabinets, and junction boxes. A color code schedule shall be included for the wiring and a device legend listing the drawing symbols used for each device (per NFPA 170, Fire Safety Symbols). A table shall be included, listing the voltage, model number, catalog number, and manufacturer's name for each FAS component.

1.4 FIRE ALARM SYSTEM/MASS NOTIFICATION (FAS/MNS) DESCRIPTION

1.4.1 Scope

a. This work includes completion of design and providing a new, complete, analog/addressable FAS as described herein and on the contract drawings. Note that uninhabited buildings, are not required or recommended to have a Mass Notification System (per UFC 4-021-01, para. 2-6.2.1). Included in the F A S a r e wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, other accessories and miscellaneous items required for a complete F A S . Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with the required and advisory provisions of NFPA 72, ISO 7240-16, IEC 60268-16, except as modified herein.

The system layouts on the construction drawings show the intent of coverage and are shown in suggested locations. Final quantity, system layout, and coordination are the responsibility of the contractor.

b. The FAS shall be a Class A addressable system with point device point reporting. The JBC-ABW Fire Servic es Department (the AHJ) shall observe the final inspection/test. After having passed the JBC-ABW Fire Department inspection, the system will be officially accepted and placed in service. To minimize the effect of lightning or electrical surges from damaging the equipment, all FAS equipment connected to building 120 VAC power shall be provided with surge protection. UL and FM listing/approval of each FAS device/component verifies that surge testing has been successfully performed on each individual component.

c. Provide equipment, materials, installation, workmanship, inspection, and testing in accordance with the required and advisory provisions of NFPA 72, ISO 7240-16, and IEC 60268-16, except as modified herein. The Contractor is responsible to coordinate with the JBC-ABW Fire Ser vices Department to determine final system design and quantities/locations of each FAS device.

1.4.2 Technical Data and Computer Software-For Training Course

Technical data specifically identified in this section shall be provided to the government on a CD-ROM. Drawings shall be in AutoCAD (2009) and portable document file (PDF) format. Contractor shall identify the data provided by

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 6 reference to the particular paragraph of this section against which it is furnished. Data submitted shall include the complete FAS and all related devices and equipment. Technical data/descriptions shall verify how the equipment can operate as a system to meet the performance requirements of this section. The data package (as a minimum) shall include:

a. Programmable Features: Identification of all programmable portions of system equipment and capabilities.

b. Software Data for FAS: Provide software for all modes of programmable portions of the FAS and MNS system.

c. Description of Operation of FACP/MNS: Description of the operation of FAS/FACP and MNS.

d. Description of Operation of NACs/RDUs: Description of operation of notification appliance circuits (NACs) and remote display units (RDUs).

e. Operation and Maintenance (O&M) manual: An operating manual outlining step-by-step procedures required for system startup, operation, and shutdown shall be provided. The manual shall include the manufacturer's name, model number, service manual, parts list, and a complete description of each type of installed equipment and its operating features. The manual shall include a complete procedure for system revision and expansion, detailing both equipment and software requirements.

f. Database for FAS: A database shall be provided for the FAS, to handle not only current points installed, but to handle an additional 144 points without addition of hardware or modification to the software. In the event additional points must be added, the system topology and hardware configuration shall be such that it shall not require changes of computers, hard drives or any other electronic equipment.

g. Testing Reports/Drawings: The contractor shall provide (to the CAFB Fire Services Department) the NFPA Record of Completion and Inspection and Testing Reports, as-built drawings, including floor plans, wiring diagrams, point to point connection diagrams, programming information, installation and instructions.

1.4.3 Keys

Keys and locks for all FAS equipment panels shall be identical. Upon final acceptance of the FAS, contractor shall provide not less than six keys to the JBC-ABW or JBC-NWS Fire Department as appropriate.

1.5 SUBMITTALS

Documents designated as "G" require Government approval. Each fire alarm component and device shown on the drawings is identified by NFPA 170 Fire Safety Symbols. Provide three (3) copies of each submittal document. Government approval is required for submittals with a "G" designation.

SD-02 D O C U M E N T S - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - G D o c u m e n t s a r e to be provided to the government as a package not to exceed 45 days after final acceptance of the system.

AMPLIFIERS Amplifier data is provided for each circuit.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 7

DEVICE OPERATION Each device address and corresponding status message that appears on the FACP, MNS and the D-21 is provided, including each NAC and NAC extender. The drawings show each circuit.

FINAL AS BUILT DRAWINGS One set of full size as-built drawings and schematics for the FAS and for the MNS are provided. Three sets of CD-ROMs in AutoCAD (2009) and in pdf format of as-built drawings, wiring diagrams and schematics are provided. Final drawings are signed and stamped by a licensed Fire Protection Engineer with 4 years of documented experience.

RISER DIAGRAM A riser diagram includes circuit connections to each FAS and MNS device installed on each floor, including location, terminal cabinets, junction boxes, conduit, wire counts, wire size, wire in each conduit, device type, floor number and room number is provided. A color code schedule for clear identification of each device and each wire is provided. The voltage, model number, manufacturer's name, and catalog number is provided in table format, listing each FAS and MNS device and component.

WIRING DIAGRAMS A complete wiring diagram for both factory wired and field wired devices and components includes field connections and terminals used for each device, component, speaker panel, strobe, panel, FACP, RDU, IDC, MNS, switches, relays and wire terminals. The wiring diagram shows the entire installed system, including identification and exact location of each device, such as room number, floor number, location within the building, junction box, related equipment, conduit routing, wire counts, wire size, identification of wire in each conduit, circuit layout, battery and voltage drop calculations, deviations from the project specifications and shop drawings.

SHOP DRAWINGS: Include with shop data, annotated catalog, in table format, of the drawings, showing manufacturer's name, model, voltage, and catalog number for each installed device/equipment and all components.

SYSTEM LAYOUT: Plan view drawing of each floor of the building, showing floor number, room number, location within each room, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each conduit, and circuit layouts.

Drawings shall comply with the requirements of NFPA 170, Fire Safety Symbols.

SYSTEM OPERATION: List each device address and corresponding status message to appear on the FACP, MNS and the D-21.

NOTIFICATION APPLIANCES: Data from each Notification Appliance Circuit (NAC) Extender. Annotate data for each circuit on the drawings.

RISER DIAGRAMS: Drawings showing the circuit connections of each of the FAS devices installed on each floor of the building, each sheet not smaller than 30” X 42,” including terminal cabinets, junction boxes, conduit routing, wire counts, circuit identification in each conduit, circuit layout, type and location of each device identified by floor number, room number, location within each room. A color code schedule shall be included for the wiring and a device legend listing the drawing symbols used for each device (per NFPA 170, Fire Safety Symbols). A table shall be included, listing the voltage, model number, manufacturer's name and catalog number for each component.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 8

FULL SIZE DRAWINGS: Provide one set of full size paper as-built detailed drawings and schematics for the FAS and the MNS to the government. The drawings shall be prepared on uniform sized sheets not less than 30 inches by 42 inches with 8 inch by 4 inch title block. Furnish three sets of CD-ROM discs containing software back-up in AutoCAD (2009) and PDF format of as-built drawings and schematics. All final FAS drawings shall be signed and stamped by a registered Fire Protection Engineer with documented experience in fire alarm system design and codes.

FINAL AS BUILT DRAWINGS: At least one set of as-built (marked-up) drawings shall be provided prior to the final acceptance test.

OPERATION AND MAINTENANCE(O&M) Data/Instructions: Provide three (3) copies of O&M manuals, indexed and in spiral ring booklet form and on CD/DVD.

SD-03 PRODUCT DATA--------------------------------------------------------------G Provide copy of UL, FM or other nationally recognized testing laboratory approval for each of the following:

FAS and MNS firmware identification and/or revision; Fire Alarm Control Panel (FACP); FM certification; Mass Notification System (MNS) Panel; Transmitters (including housing); Battery chargers;

Smoke detectors/sensors; Thermal (heat) detectors/sensors; Wiring and cable;

Notification Appliance Circuit (NAC) Extenders; Addressable Monitor; Relay Control & Mini-Modules; Water flow detectors;

Tamper switches; Electromagnetic door holders;

SD-05 DESIGN DATA--------------------------------------------------------------G

Provide a complete description of the FAS and MNS system operation in matrix format on the drawings.

Battery power and load calculations SD-06 Test Reports-------------------------------------------------------------G Field Quality Control Testing Procedures Smoke sensor testing procedures

SD-07 CERTIFICATIONS------------------------------------------------------------G Installer, Electrician, and Test personnel

SD-09 MANUFACTURER’S FIELD REPORTS---------------------------------------------G

Fire Alarm Control Panel (FACP) Include the FACP panel, initiating devices, indicating devices, a unique identifier for each device, with a report of test results with signature of the factory trained technician for the FACP as well as the equipment installer. The contractor shall complete the NFPA 72 “Record of Completion” and “Inspection and Testing” form, along with the appropriate test reports/signatures.

SD-10 OPERATION & MAINTENANCE (O&M) Data/Instructions:------------------------G (Included in the “as built” package.)

1.6 QUALITY ASSURANCE

Compatibility with Existing Systems: All installed equipment and devices shall be compatible and operable with all existing FASs and shall not impair reliability or operational function of the D-21.

a. Advisory provisions mandatory: In NFPA publications referred to herein, consider advisory provisions to be mandatory, as though the word “shall” had been substituted for “should” wherever it appears.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 9

b. Manufacturer’s recommended practices mandatory: The recommended practices stated in the manufacturer’s literature or documentation for each device shall be considered as mandatory requirements.

c. Devices must be UL or FM listed: Unless otherwise noted, devices and equipment for FAS service shall be listed by UL Fire Prot Dir or approved 100% Design Construction Documents by FM P7825a. Devices and equipment connected together shall be UL or FM listed as acceptable to be connected together.

1.6.1 Qualifications

1.6.1.1 Design Services

Installation drawings/specifications/modifications of fire detection, FAS and fire suppression systems require certification/approval of a registered Professional Engineer (PE) who has passed the Fire Protection Engineering written examination administered by the National Council of Examiners for Engineering and Surveys (NCEES), plus a minimum of four years work experience (verified with documentation) in Fire Protection Engineering. Certifications shall be up to date, and a copy provided to the (AHJ) Fire Services Department.

1.6.1.2 Supervisor

On site supervision of FAS equipment installation shall be by a technician who has been factory trained by the manufacturer of the FACP/MNS panels in the installation, programming, adjustment, testing and operation of FAS, with a minimum of eight year’s experience (verified with documentation provided to the AHJ) installing FAS. Each Fire Alarm Supervisor’s qualifications shall include submission of a valid/current certification from the National Institute for Certification in Engineering Technologies (NICET-minimum Level III), in the subfield of Fire Protection Engineering Technology.

1.6.1.3 Technician/Installer/Test Personnel

All FAS components and systems shall be installed by Fire Alarm Technicians who have a minimum of two years of experience to assist in the installation of FAS devices, cabinets and panels, and have been factory trained in the installation, programming, adjustment, testing and operation of FAS.

Verification of each Fire Alarm Technician/ Installer/Test Personnel’s experience in performing this type of work shall include submission of a valid certification by the National Institute for Certification in Engineering Technologies (NICET-minimum Level II), in the subfield of Fire Protection Engineering Technology. A licensed electrician may be used to install FAS conduit, wire and cable.

1.6.1.4 Technician-in-training

A Fire Alarm Technician who has not yet completed the NICET II certification shall be allowed to assist in the installation under the direct supervision of a NICET II certified technician.

1.6.1.5 Manufacturer’s Representative

The FACP equipment manufacturer’s representative (an employee of the manufacturer with technical training on the system being installed) shall be present for the connection of wiring to the FACP.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 10

1.6.1.6 Manufacturer

MNS and FAS components shall be of current design and shall be in regular and current production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system and mass notification system, complete, conforming to NFPA 72, and as additionally specified herein.

1.6.2 Regulatory Requirements

All FAS equipment shall be listed for use under the applicable reference standards. If the software programming features cannot provide a listed interface control, interfacing of equipment listed by UL 864 shall be done in a laboratory listed configuration. For field modifications, such as adding equipment like relays, the contractor shall provide details of the modification for review and confirmation to the government.

1.6.2.1 Requirements for Fire Protection Service/Equipment

Equipment and material shall be UL listed in UL Fire Prot Dir or approved by FM. The FACP must be listed in FM P7825a. Where the terms “listed” or “approved” appear in this specification, they shall mean listed in UL Fire Prot Dir or FM P7825a. The omission of these terms under the description of any item of equipment described shall not be construed as waiving this requirement. Note that, while a particular fire alarm system device may be individually UL or FM approved, it must be UL or FM approved to be connected to the FACP. While connecting one manufacturer’s FAS device to another manufacturer’s FAS device may be a “field accepted practice,” that is not sufficient: connecting any FAS device to the FACP must be certified by UL or FM as approved for that use.

1.6.2.3 Testing Services or laboratories

FAS and fire detection equipment shall be constructed in accordance with UL Fire Protection Directory, UL Electrical Construction, or FM P7825a, and tested in accordance with NFPA 70 & 72, Class A Systems.

1.7 DELIVERY, STORAGE, AND HANDLING

While awaiting installation, all FAS and MNS equipment shall be protected from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.

1.8 OPERATION AND MAINTENANCE (O&M) FAS INSTRUCTIONS

Fire Alarm System Operation and Maintenance (O&M) Instructions provided to the CAFB Fire Department shall include:

a. Manufacturer Data Package as specified in Section 01 78 23 OPERATION AND

MAINTENANCE DATA.

b. Operating manual outlining step-by-step procedures required for system startup, operation, and shutdown. The manual shall include the manufacturer's name, model number, service manual, parts list, and a complete description

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 11 of each type of installed equipment and its operating features. The manual shall include a complete procedure for system revision and expansion, detailing both equipment and software requirements.

c. Maintenance Manual including a list of routine maintenance procedures, list of possible breakdown situations and repair for each, and a troubleshooting guide for each type of installed FAS component. The manual shall include conduit layout, equipment location/layout and simplified wiring, control and riser diagrams for the entire FAS as installed.

d. Software delivered for this project shall be provided on a CD/DVD.

e. Printouts of configuration settings for all devices.

f. Routine maintenance checklist. The routine maintenance checklist shall be arranged in a columnar format. The first column shall list all installed devices, the second column shall detail the type of maintenance required, the third column shall state the frequency of the maintenance activity, and the fourth column shall be provided for additional comments.

1.9 EXTRA MATERIALS

1.9.1 Repair Service/Replacement Parts

Repair services and replacement parts for the system shall be available for a period of 10 years after the date of final acceptance of this work. The contractor shall provide a warranty of the installed FAS (all components, wiring, etc.,) for one year after date of acceptance. In the event of a FAS component failure during the warranty period, government technicians will evaluate and determine the cause of failure. If the failure is caused by an act of nature or damaged by others, government technicians will make the repair.

If, however, it is determined by the government that the failure is as a result of a defect, or is the cause of the contractor, the contractor shall be notified of the problem, and shall have a technician on-site within 48 hours after notification, and, during the one year warranty period, all warranty service (trouble shooting, parts, labor, travel, etc.) shall be provided by the contractor at no charge to the government.

1.9.2 Interchangeable Parts

Spare parts furnished by the contractor shall be directly interchangeable and compatible with the corresponding components of the installed system. Spare parts shall be appropriately packaged and identified by tagging, or stamping.

Spare parts shall be delivered to the government on or before system acceptance. (If a listed spare part is of a type that is not being used in the specific installation, it may be omitted.)

1.9.3 Spare Parts

a Three (3) manual stations b Three (3) smoke detectors c Three (3) heat detectors d Three (3) speaker/strobes e Three (3) strobes

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 12 f Three (3) tamper switches g Three (3) horn/strobes h Three (3) sets of fuses

1.9.4 Special Tools

Contractor shall provide all software, tools, laptop computer, special connecting cables and any other proprietary equipment to the government necessary for the maintenance, testing, programming and reprogramming of the FAS equipment by government technicians after the warranty period.

PART 2.0 PRODUCTS

2.1 MONITOR MODULE The monitor module, or addressable interface unit, is powered and supervised by the FACP. It mounts in a standard electrical box, has the capacity to report the status of a non-addressable device to the FACP, and it contains an LED to indicate polling and alarm conditions. A monitor module provides either Class “A” or Class “B” supervised indicating device circuits (IDCs) to the FACP. Monitor modules have dry contacts and supervised output. A monitor module is not to be used to report to the D-21.

2.1.1 Mini-Monitor Module Manual pull stations are not addressable.

A mini-monitor module provides a means for the manual pull station to become addressable, so it can report to the FACP. An LED is not required for mini-monitor modules.

2.2 SMOKE DETECTOR Smoke detectors are installed 30 foot apart on smooth ceilings, have addressable sensors, are powered by the FACP, have an LED to indicate a fire event, and include a sensor head with separate twist lock base containing two (2) LED indicators that flash when being polled by the D-21. Each photoelectric type smoke detector operates on the light scattering principle. No other type of smoke detector is allowed at JB CHS. The sensor base has screw type terminals and an internal alarm signaling device. Each sensor address has a rotary or a manual “dual-in-line package” switch or “dip” type switch that requires no tools to operate, and clearly displays the address set for the unit without binary interpretation. Plug-in components or jumper arrangements are not acceptable. This specification requires one smoke detector to be installed on the ceiling above the FACP.

2.2.1 Duct Smoke Detector Duct smoke detectors have air sampling tubes running the full width of the duct, are addressable, powered by the FACP, are photoelectric, and installed inside an HVAC duct 2 feet width or larger having an air velocity between 100 and 4000 feet per minute. If a fire event occurs, the activated sensor reports to the FACP and the FACP shuts down the air handling unit (AHU). In those situations where the detector alarm or supervisory indicator cannot be easily seen, a remote alarm indicator and reset control, visible from the floor, will be provided. After resolution of the fire event, the duct smoke detector requires manual re-set.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 13

2.3 MANUAL PULL STATION Pull stations are non-addressable, single action, key lock, surface mounted, painted red, with operating instructions in raised, contrasting color letters, have an addressable mini-monitor module installed in the pull station back box, and are supervised by the FACP. Pull stations are mounted 48 inches above the finished floor (AFF), keyed the same as the FACP to allow ease of test and reset. Stations that require replacement parts (such as a breakable glass or plastic rod), or gravity or mercury switches are not acceptable.

2.4 HEAT DETECTOR Heat detectors or sensors are addressable, rated for 50' spacing on smooth ceilings. Fixed temperature and combination fixed temperature and rate of rise sensors are approved for use. Sensor assemblies include a sensor head utilizing a dual thermistor sensing circuit, twist lock base with two (2) LED indicators for polling and alarm. Screw type terminals are provided in the sensor base for wiring.

2.5 FIRE DOOR DEVICE Fire door devices are addressable and

are designed to hold fire doors open. Door holding devices have no moving parts, operate on 120 VAC and 3 watts of power, develop 35 pounds magnetic holding force and are listed and tested per UL 228. Either a fire event or a building power failure cuts power to the magnet, allowing the doors to close. Upon resolution of the fire event or power failure, each fire door must be manually re-opened.

2.6 SIGNAL LINE CIRCUIT (SLC) A SLC is configured Class “A,” one of up to 8 circuits reporting to the FACP, with each circuit having the capacity to support up to 99 addressable smoke or heat detectors and up to 99 control, monitor, NAC, and interface addressable modules. SLC alarm, supervisory, trouble conditions, device faults, command faults, missing device, early warning, maintenance alert, communication loss, IDC, NAC, SLC, power and battery fault are reported by the FACP to the D-21.

2.7 INITIATING DEVICE CIRCUIT (IDC) The FACP provides two Class “A” or four Class “B” IDCs. Each IDC system has an interconnected riser loop or network with Class “A” supervision. Each IDC or SLC is powered and supervised so a signal from one IDC, SLC, addressable device or point does not prevent the FACP from receiving a signal from an addressable IDC or SLC.

2.8 REMOTE TRANSCEIVER A transceiver, remote from the FACP or MNS enclosure, receives inputs from addressable devices, provides power to detection devices, interface units or NACs, then forwards and receives the condition and status of addressable devices that are connected to the FACP. Each transceiver is fully supervised by the FACP. Audio NAC wiring, strobes, auxiliary expansion modules, power output circuit wiring, amplifier input voltage, low battery or remote microphone station is supervised for open and short conditions. A trouble signal is sent for any supervision loss, and annunciated locally with built-in audible alert and LED indicators. FACP and MNS transceivers transmit to the D-21.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 14

2.9 LOCAL OPERATING CONSOLE A local operating console includes a hand- held push to talk (PTT) microphone, with LEDs and pre-amplifier.

Live-voice messages, initiated from the D-21 will over-ride messages initiated by the PTT microphone. The PTT console is capable of initiating the MNS strobes, and includes controls to manually activate pre-recorded messages and tones from the FACP and MNS transceivers.

2.10 Sensitive Compartmented Information Facilities (SCIF) Speakers SCIF speakers will comply with UFC 4-010-05 Sensitive Compartmented Information Facilities Planning, Design, and Construction, Change 1.

2.11 FIRE ALARM CONTROL PANEL (FACP) Every addressable device or component reports as a “point” to the FACP. The FACP continuously transmits, in real time, the status and specific location of each device or “point” to the D-21. The FACP has a capacity of sixteen (16) addressable Signal Line Circuits (SLCs), expandable by the addition of plug-in circuit cards into existing ports and includes two (2) programmable on-board relays as well as software to support at least two

(2) SLCs. Each plug-in card supports up to 99 addressable smoke or heat devices and 99 addressable monitor or control modules. In addition, the FACP provides ports for four Class “B”, two (2) Class “A” conventional Initiating Device Circuits (IDCs) and four (4) NACs. The FACP will have a database capable of handling an additional 144 points, along with current installed points, without modification of hardware or software.

2.11.1 FACP Antenna Each FACP omnidirectional antenna is installed external to the facility, mounted in accordance with the manufacturers’ recommendations, made of non-corrosive material, designed to withstand 125 miles per hour wind velocity, located away from overhead power lines with a driving point impedance of 50 ohms. Antenna coaxial cables will be 50 ohm RF type, including PL, BNC, N type fittings or connectors.

2.11.2 Grounding Of Antenna Each antenna is grounded in accordance with NFPA 70, Article 810. Noncurrent carrying metallic parts associated with fire alarm equipment are connected to the building grounding electrode system with a total connection resistance not to exceed 1 ohm. Grounding conductors are 10 AWG solid copper or 8 AWG solid aluminum.

2.11.3 Lightning Protection All antennas will be provided with coaxial static lightning surge protection. Surge protectors will be of a type approved by the manufacturer and located as close as practicable to the grounding location. All antenna coax cables will be installed in conduit.

2.12 CENTRAL RECEIVING STATION (D-21) The central receiving station is a Monaco Enterprises Inc. Incident Management System Transceiver Model D-21. The primary JB CHS AB D-21 is located in the Base Defense Operations Center (BDOC) located in Security Forces Building #254, while the primary JB CHS NWS D-21 is located in the NWS BDOC. All repaired or new FAS or MNS will be compatible with the existing D-21s.

2.12.1 MNS Connect To FACP The MNS provides a minimum of eight relays for the purpose of connecting to the FACP. MNS and FACP transceivers provide a supervised RS-422 serial data communication port for interfacing the FACP. This interface allows the MNS and FAS transceivers to transmit

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 15 alarm, trouble, poll replies and status messages from the FACP to the D-

21. NOTE: A monitor module installed between the MNS and FACP and the D- 21 to provide point alarm and trouble status, is not permitted.

2.12.2 MNS And FACP Battery Each MNS and FACP battery is a spill-proof, sealed, gel-type, lead acid battery, requiring no addition of water or electrolyte, capable of supplying power requirements for all fire alarm system devices for 72 hours, then support a 100% alarm condition for 15 minutes, and still have the capacity to send a message at the end of the 72 hour, 15 minute time.

2.13 NOTIFICATION APPLIANCE CIRCUIT (NAC) Each NAC will be monitored and controlled by the FACP for reporting fire events and by the MNS for reporting MNS events. Power will be supplied to each NAC from a Class “A” circuit on the FACP, with battery backup. NAC programming will provide continuous monitoring of NACs and activation of all associated control outputs. The NAC network will comply with NFPA 72 and the requirements of UFC 4-021-01 Design and O&M MNSs, using combined or shared audible NAC and strobe appliances for FACP and MNS. NAC extender panels are to be wired for monitoring by the FACP

2.13.1 NAC Enclosure Each NAC enclosure will be red in color, with at least eight (8) 3/4 inch diameter knock-outs, (for example, 3 on each side and 2 in the bottom). Each enclosure conforms to NEMA ICS 6, standard 1 for indoor locations, and cannot be smaller than 8” by 8”. One enclosure will be provided at the base of each circuit riser, having the top of each enclosure 6 feet above the finished floor (AFF). Each enclosure will be of ample size and capacity for installation of wiring, lamps, circuits, labels, wire connections, meters, fuses, switches, with all internal components aligned vertically or horizontally. Each conductor termination will be labeled. Wires that are terminated, spliced, or interrupted within the enclosure will be clearly identified and secured to a terminal block with screw or pressure type fitting.

2.13.2 Enclosure Drawing A plastic laminated outline circuit drawing will be installed inside each enclosure, identifying all wires, circuits, and interconnections. The drawing will have bold lines, and use minimum 12 point font.

2.13.3 NAC Extenders If the number of NACs exceed the capacity of the FAS and MNS panel, NAC extenders (monitored and controlled by the FACP), will be provided. Each NAC extender will provide power for up to four (4) Class “A” NACs, with its own 120 Volt AC primary power backed up with batteries, a battery charger, enclosed in a red steel panel, and keyed the same as the FACP and all other fire alarm enclosures in the facility. Each addressable NAC, IDC, and SLC will remain functional, even if the conductors between them are severed.

2.13.4 NAC Strobes NAC strobes will be suitable for the climatic and environmental conditions of this facility. Strobes will utilize a xenon flash tube using white light at a flash rate of 1 flash per second.

NAC strobes will have visibility and synchronization features per NFPA 72, the Uniform Federal Accessibility Standards (UFAS) and the Americans with Disabilities Act Accessibility Guidelines ADA). Note that NAC strobe bodies will be white with amber lens and marked with the word “ALERT” to provide a signal for the hearing impaired, while FAS strobes will be red

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 16 with white and clear strobes, marked with the word “FIRE”.

2.13.5 NAC Speakers NAC speakers will be located to provide

interior notification of occupants throughout the facility, particularly near entrances, exits, and commonly used areas. NAC speakers will alert occupants and provide voice instructions. Fire and MNS messages will be broadcast over the same shared speaker network. NAC speakers will be listed and approved for the purpose intended, suitable for installation in applications with consideration of electrically hazardous locations and for the climatic and environmental conditions of this facility.

2.13.6 NAC Speaker Intelligibility NAC Speaker Intelligibility is measured using a Common Intelligibility Scale (CIS) per NFPA 72 and IEC 60268-16. In areas where building personnel commonly occupy, it is required that a CIS score greater than 0.70 (verified by instrumentation) be maintained.

2.13.7 NAC Speaker Intensity The speaker system will be designed to provide effective voice communication throughout the facility and in areas commonly occupied by personnel. This will be accomplished by installation of several speakers having lower decibel intensity while still meeting the minimum decibel level required by NFPA 72. The speakers will be rated at two watts of power or less and will be provided with multiple tap settings to provide adjustment for output power. For large areas and areas having high ambient noise levels, speakers will be rated at eight watts of power and provided with multiple tap settings in increments of two watts.

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 17

PART 3.0 EXECUTION

3.1 SYSTEM, DEVICE AND COMPONENT INSTALLATION All system components, wiring, cabling, and terminals will be clearly identified with zone and circuit labels. The FAS and MNS transceivers will be compatible with the D-21, Factory Mutual (FM) and Underwriter’s Laboratory (UL) approved, and will employ Frequency Shift Keyed (FSK) message encoding. The MNS panel will have an integrated FSK, FAS, MNS transceiver for the purpose of sending local live-voice and prerecorded voice, tone, emergency messages.

Monitoring circuitry will be provided to detect and shut down a FSK transmitter. If the transmitter stays in a “transmit” condition for more than 30 seconds, the connected FSK transceiver will initiate a transmitter disconnect circuit, automatically disconnect the transmitter, and a “transmitter disconnected” LED will flash. A “transmitter reset” button is provided to reconnect the transmitter.

3.1.1 Deviation From Specifications Devices will be installed in accordance with NFPA 72 and 101, except, in the event of deviations from NFPA, then the final decision will be made by the JB CHS Emergency Services Department.

3.1.2 Pull Stations Pull stations will be installed near each exit per NFPA 72 and ADA.

3.1.3 Notification Appliance Devices Notification appliance devices will be installed 80 inches above the finished floor (AFF).

3.1.4 Smoke & Heat Sensors Smoke and heat detectors will be installed per NFPA 72.

3.1.5 Remote Indicator If the indicator light on an installed device is not readily visible, a remote indicator light will be provided in an easily visible location.

3.1.6 Water Flow Detectors and Tamper Switches Each water flow detector and tamper switch shall have a companion monitor module installed, that reports its status and location to the FACP.

3.1.7 Enclosures Each enclosure will be labeled, and the location of the power panel noted on the enclosure. Each terminal cabinet, FMCP, and remote FMCP shall contain a laminated drawing that indicates each conductor, its label, circuit, and terminal. The laminated drawing shall be neat, using 12 point lettering minimum size, and mounted within each cabinet, panel, or unit so that it does not interfere with the wiring or terminals. Maintain existing color code scheme where connecting to existing equipment. The panel that provides power to the enclosure will have the breaker clearly identified and will have a RED breaker lock.

3.1.8 Conduit In finished areas, conduit will be concealed. Conduit cannot be mounted on drop ceiling framework or the bottom of metal roof decking.

3.1.8.1 Conduit Penetrations Conduit penetrations through fire-rated walls will be fire-stopped per the International Building Code. Wall and ceiling conduit penetrations will be provided with escutcheons that snugly

Repair/Add IMC Fire Suppression System DKFX 11-1005 A/B

Section 28 31 76 JB CHS page 18 fit the conduit, completely cover the opening and painted to match the adjacent wall or ceiling. Each escutcheon will be secured to the wall or ceiling. Exterior wall or roof conduit penetrations will be sealed weather-tight.

3.1.8.2 Conduit Painting All exposed fire alarm conduit and raceway is to be painted bright red.

3.1.9 Wire Installation Installed wiring will conform to NFPA 70, be color coded the same throughout the entire facility, and be clearly identified with printed shrink-tube labels where connected to fire alarm equipment.

3.1.9.1 Enclosure Internal Wiring Wiring will be installed parallel to the side, bottom and back of each enclosure and connected to a clearly identified screw-type terminal.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .