FA441721B0003 - Questions and Answers - Part 2.pdf
PDF 70 KB Posted
- Attached to
- Convert Bldg 91157 from Storage Warehouse to Testing Lab Federal contract opportunity
- Solicitation number
- FA441721B0003
About this file
This document contains answers to questions regarding federal contract opportunity FA441721B0003 to convert Building 91157 from a storage warehouse to a testing lab for the Department of the Air Force Special Operations Command. Surveying will be required to set the sewer piping, manholes, and lift station at the designed elevations, though specifications for surveying are not provided. The opportunity type is a solicitation seeking to convert the specified building to a testing lab as described in the attached documents.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 7 - Drawings - Revised (Addendum 1).pdf | ||
| Addendum 1 - Drawings Changes.pdf | ||
| Addendum 1 - Specs Changes.pdf | ||
| Solicitation Amendment 2 - FA441721B00030002 SF 30.pdf | ||
| Attachment 6 - Specifications - Revised (Addendum 1).pdf | ||
| CE Response - Site Visit Questions.pdf | ||
| Site Visit Sign In Sheet - 25 August 2021.pdf | ||
| Memo for Record - FA441721B0003 Pre-Proposal Conference_Site Visit - 25 August 2021.pdf | ||
| FA441721B0003 - Questions and Answers - Part 1.pdf | ||
| Solicitation Amendment 1 - FA441721B0003 SF 30.pdf | ||
| Attachment 4 - DBA Wage Determination FL20210217.pdf | ||
| Solicitation - FA441721B0003.pdf | ||
| Attachment 1 - Specifications.pdf | ||
| Attachment 5 - Financial Institution Reference Sheet.pdf | ||
| Attachment 3 - Working Time Analysis.pdf | ||
| Attachment 2 - Drawings.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA441721B0003 HF Convert B91157 - RFI # 2
Regarding the requirements for surveying in the specifications. Could you verify that this requirement is not needed, or if is needed, could you provide us with the Specs for it, please?
Answer: It is required to set the sewer piping, manholes and lift station at designed elevations which will require some kind of surveying to make sure they are at the correct elevations. There is not a specification for surveying.