This document contains questions and responses related to a solicitation for repair work at an Air Force facility. The solicitation is for interior demolition and construction work on the first and second floors of an existing warehouse building, including new bathrooms, mechanical rooms, classrooms, and offices. Questions addressed specifications for door hardware, exit devices, locks, and cylinder requirements. Responses approved parallel arm door closers, separate alarm devices, new mortise locks and surface bolts, and clarified that cylinder cores would be contractor furnished.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOLICITATION NO. FA441720R0015

PROJECT: Repair Interior 505/705 TRS, Bldg 90021, No. CP1017959

QUESTIONS – ANSWERS – 60 through 64

Question 60: Hardware Set 5 calls for ANSI C03081 which is a top jamb hold open door closer.

Top Jamb configuration is not recommended for a 4070 door. Recommend Parallel arm mount.

Please confirm.

Answer 60: Concur with recommendation, provide parallel arm mount.

Question 61: Hardware Set 3 calls for “armed” exit device. Is this an alarm feature of an exit device? Alarmed option not available for wind rated rim type exit devices. Will a separate smaller type alarm device be acceptable for use?

Answer 61: Yes, a separate alarm device is acceptable.

Question 62: Drawing Sheet A‐115 calls to reuse a X‐09 lock. Many X‐09 parts are unavailable.

Several replacement parts are required to reuse an X‐09/X‐10 lock. Please Clarify if this X‐09 is part of a FF‐L‐2890B Type IV locking device. Due to the unavailability of parts for the X‐09 recommendation is to replace with new X‐10. Please confirm.

Answer 62: Concur with recommendation, provide new X‐10.

Question 63: Specification 08.71.00 subsection 2.3.6 says to notify the contracting officer 90 days prior to the required delivery of the cylinders. Will the government be furnishing the cylinder cores for this project?

Answer 63: No, the contractor furnishes the cylinder cores.

Question 64: Hardware Set 5 calls for a F86 function (cylindrical lockset function) and specification 08.71.00 subsection 2.3.3 calls for bored locks and latches. Wind rated Hollow metal door frames are required to have a mortise lock w/deadbolt (active) and Surface Bolts

(Inactive), vertical rod exit devices on each leaf or rim exit devices on each leaf and a mullion.

Will a mortise lock with deadbolt on the active leaf and surface bolts on the inactive leaf be acceptable?

Answer 64: Yes, a mortise lock with deadbolt on the active leaf and surface bolts on the inactive leaf is acceptable.