This document contains questions and answers regarding solicitation number FA302220R0002 for a project to repair the roof at Building B160 on Columbus Air Force Base in Mississippi. The questions and answers provide clarification on the scope of work, specifying that three ventilation fans and one heater vent mentioned in photos are exhaust fans for the space below, and that while disconnected the contractor must provide drum-type fans of at least 18,000 CFM located and directed as required by the contracting officer. No further questions will be accepted prior to award. The project is to be undertaken for the Department of the Air Force Air Education and Training Command.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA302220R0002, BX Roof Repair B160
Questions and Answers (2 of 2)
31 Mar 2020
*No further questions will be accepted prior to award*
8. Refer to the Statement of Work - Chapter 2 - Paragraph 2.2 ROOFTOP EQUIPMENT TABLE- There is no scope of work addressing the three (3) vents in the attached photos. Please provide required directions for these vents. This is an exhaust fan for the space below. While this fan is disconnected, Contractor must provide two each drum-type 18,000 cfm (min) fans located and directed per CO.
11. Attached is a photo of a heater vent that is not addressed in the SOW - Chapter 2-Paragraph 2.2
ROOFTOP EQUIPMENT TABLE. Please provide directions for this vent.
This is an exhaust fan for the space below. While this fan is disconnected, Contractor must provide one drum-type 18,000 cfm (min) fan located and directed per CO.