Delta Controls DCU-050 RFI Answered

Q 1:

ADP boards will be associated with the eBX-04's, eBCON's, and the eBMGR's to replace the existing DCU- 050/ORCAs. Where should the cost of these additional components be placed when breaking out the

CLIN?

A 1: IN THE CLIN FOR THE PANEL, THIS SHOULD BE ALL INCLUSIVE OF HARDWARE BEING USED.

Q 2:

Statement: CLIN 0004 lists a total quantity of 15 for the eBM-X's. Each eBCON and eBX-04 will have four eBM's associated with each of them. So according to CLIN 0002 and CLIN 0003 that would make the total eBM quantity 120. The four styles of eBM's are as follows: eBM-440, eBM-404, eBM-800, eBM-000

Q2a: Can we get a new CLIN that shows a total of quantity 120 for CLIN 0004?

Q2b: Do you want the total eBM-X quantity lumped together or broken out by their four types as shown above?

A2a: IN THE CLIN FOR THE PANEL, THIS SHOULD BE ALL INCLUSIVE OF HARDWARE BEING USED.

A2b: IN THE CLIN FOR THE PANEL, THIS SHOULD BE ALL INCLUSIVE OF HARDWARE BEING USED.

Q3:

Newly installed control panel enclosures had a UL label inside the enclosure. Do the control panels within the upgrade scope of work need to be UL listed?

A3:YES