Delta Controls EnteliBUS line of Managers & Controllers to replace the current Delta Controls DCU -050 line of controllers
Solicitation number
FA2543-22-Q-AS01
Issued by

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(e)

AC

ACU

AD

AFMS

AHU

AI

ALM

AO

ATD

BI

BLR

BO

BOPD

BOPR

BOTD

BOTR

CAV

CFM

CHLR

CHW

CHWR

CHWS

CO

CO2

COND

CP

CS

CT

CU

CUH

CV

CW

CWR

CWS

D

DA

DM

DPS

DPT

EF

EP

ES

EVC

FACP

FLT

FM

FPB

FS

FT

G

GND

Existing

Air Compressor

Air Conditioning Unit

Air Dryer

Air Flow Monitoring Station

Air Handling Unit

Analog Input

Alarm / Safety Input (suffix)

Analog Output

Auto Tank Drain

Binary Input

Boiler

Binary Output

Break on Pressure Drop

Break on Pressure Rise

Break on Temperature Drop

Break on Temperature Rise

Constant Air Volume

Cubic Ft/Minute volume

Chiller

Chilled Water

Chilled Water Return

Chilled Water Supply

Carbon Monoxide

Carbon Dioxide Sensor

Condenser

Control Panel

Current Switch

Current Transformer

Remote Condensing Unit

Cabinet Unit Heater

Control Valve

Condenser Water

Condenser Water Return

Condenser Water Supply

Damper

Damper Actuator (Pneumatic)

Damper Motor (Electric )

Differential Pressure Switch

Differential Pressure Transmitter

Exhaust Fan

Electric Pneumatic Switch

End Switch

Evaporative Cooling

Fire Alarm Control Panel

Filter

Flow Meter

Fan Powered Box

Flow Switch

Flow Transmitter

Gauge

Ground

Hot (Hot/Line)- voltage

Hand-Off-Auto Switch

Humidity Transmitter

Heating Ventilation Unit

Hot Water

Hot Water Return Temp

Hot Water Supply Temp

Heat Exchanger

Current to Pneumatic Transducer

Indoor Air Quality

Light

Line Filter

Liquid Level Switch

Liquid Level Transmitter

Lighting Control

Low Temperature Switch

Mixed Air

Magnetic Starter

Makeup Air Unit

Motor Control Center

Make on Pressure Drop

Make on Pressure Rise

Make on Temperature Drop

Make on Temperature Rise

Neutral (Line)- voltage

Normally Closed

Normally Open

Outside Air

Overload

Operator Work Station

Pump

Push Button

Pressure Electric Switch

Proximity Switch

Pressure Regulating Valve

Power Supply

Pressure Switch

Relay

Return Air

Receiver Controller

Restrictor

Return Fan

Humidity

Network Repeater

Relief Valve

Supply Air

Smoke Detector

Supply Fan

Surge Protector

Solenoid Valve

Selector Switch

H

HOA

HT

HV

HW

HWR

HWS

HX

I/P

IAQ

L

LF

LLS

LLT

LTG

LTS

MA

MAG

MAU

MCC

MOPD

MOPR

MOTD

MOTR

N

NC

NO

OA

OL

OWS

P

PB

PE

PROX

PRV

PS

PSW

R

RA

RC

RES

RF

RH

RPT

RV

SA

SD

SF

SRG

SV

SW

T

TB

TC

TDR

TF

THT

TP

TR

TRM

TS

TSP

TT

UH

UPS

UV

V

VA

VAC

VAV

VDC

VF

VFD

VSW

W

Thermostat

Terminal Block

Time Clock

Time Delay Relay

Transfer Fan

Temperature Humidity Transmitter

Twisted Pair

Transformer

End of Line Terminator

Temperature Sensor

Twisted Shielded Pair

Temperature Transmitter

Unit Heater

Uninterruptible Power Supply

Unit Ventilator

Valve

Volt/Amps

Volts Alternate Current

Variable Air Volume box

Volts Direct Current

Ventilation Fan

Variable Frequency Drive

Vibration Switch

Thermowell

Firmware Version# 3.33

REVISED 28 January 2014

Ethernet Hub #1

1234 756 8

OR

i n c h e s

25 inches

9.5"

Since 1983

10K OHM THERMISTER

18TP

TEMPERATURE SENSOR

DETAIL 1

INPUT JUMPER

SWITCH

CURRENT

OUT

INPUT JUMPER

CURRENT SWITCH

COM

18TP

DETAIL 2

DETAIL 5

DIGITAL INPUT

18TP

DETAIL 3

INPUT JUMPER

DIFFERENTIAL PRESSURE SWITCH

N.C

C

N.O.

18TP

DETAIL 4

INPUT JUMPER

PS()

FIELD DEVICE

18TP

LOOP POWERED 4-20mA

INPUT JUMPER

DPM065-51

O

A

H

DPM065-51

O

H

A

18TP

A2

A1

MODULAR RELAY 10VDC COIL

DETAIL 10

DPM065-51

O

H

A

DPM065-51

O

H

A

DPM065-51

O

H

A

DETAIL 8

X1

X2

DETAIL 9

X1

X2

DETAIL 11

MOUNT @ STARTER

WHT/YLW

TB2

WHT/BLU

TB2 12

ORNG

YLW

R1BU1C

R3

RELAY IN BOX 10VDC COIL

GND

DPM065-51

O

H

A

DPM065-51

O

H

A

DPM065-51

O

H

A

DPM065-51

O

H

A

DPM065-51

O

H

A

POT

DPM065-52

A

O

H

BLUE

GREEN

BROWN

VAC

24VAC

TB1

GND FILTER1

G

N

N

L

L

TB1

100VA

TB2

TB2

X2

X2

X1

X1

H

N

N

H

TB2

TB2

TB2

TB2

120VAC PWR

BY DIV. 16

BAC.92600.BI08

120VAC

OUTLET

CB1

N

TB2

TB2

NO NCCOM

NO NCCOM

R1BU1C

R1/AHU1 SMK

TB1

TB1

TB2

TB2

TB2

TB2

TB2

TB2

TB1

TB1

R2/AHU1 FRZ

BAC.92600.BI09

BAC.92600.AO05

MEM

SIG LOSS HOLD

PWM SIGNAL

MEM

NO

STATUS

5V

MA

OFF

POWER

SIGNAL

PWM

COM

SIG

I-V

I-V TZ 15V

FALLBACK

RES-1 (NEW)

RESIST

24VAC

OUTPUT POT

RB BW R W

PWM OZ 10V

X

X

X

X

X

X

X

ON

X

TB2

TB2

135 OHM

TB2

TB2

TB1

TB1

X1 X2

TB2

TB2

TB2

TB2

TB2

X3

X4

General:

The system consists of a horizontal draw-thru type make-up air handling unit. The fan control circuit shall include safety controls.

Safety Controls:

On detection of smoke the supply fan shall stop. The EMCS shall prevent the supply fan from starting until the damper is fully open. The low limit cutoff shall stop the fan at temperatures below its setpoint.

Sequence:

With AHU-1 Hand-Off-Auto switch in the "auto" position and all safety controls closed. Intake damper shall open.

End switch ES-1 closes when the damper is fully opened, and AHU-1 starts.

Discharge Temperature Control:

The discharge air temperature shall be maintained by the EMCS modulating the chilled water and glycol control valves through transducers EL1 and EL2. The EMCS shall start P-6 when the outdoor air temperature sensor

(T2) detects a temperature below 68°F and AHU-1 is operating, and stop the pump at outdoor air temperatures of 68°F or greater, or when AHU-1 is not operating.

Humidity Control:

Space humidity sensor H1 shall modulate the output of humidifier H-1 to maintain setpoint of 35% RH. The high limit humidistat shall stop the humidifier if supply air humidity exceeds 90% RH.

OA

(0.75") W.C.

B630 AHU1 HC VLV

F I L T

E R

HIGH

DPS-1

LOW

24VAC

ORCA92600

BAC.92600.AO05

26.IP5

NO

NC C

C

CV1 (N)

H

B630 AHU1 FLT ST

BAC.92600.BI07

26.IP7

ORCA92600

SET@ 36°F

ORCA92600

B630 AHU1 SMK ALM

BAC.92600.BI08

26.IP8

SD1

MAG

BAC.92600.AI02

26.IP2

B630 AHU1 SA TMP

(-40°F/185°F)

ORCA92600

T2

B630 AHU1 SF ST

B630 AHU1 SF SS

BAC.92600.BI05

26.IP5

ORCA92600

BAC.92600.BO01

26.OP1

ORCA92600

ORCA92600

BAC.92600.BI09

26.IP9

B630 AHU1 FRZ ALM

MOTD

SA

18TP

T1

B620 AHU1 OVERRIDE

ORCA92600

BAC.92600.BI10

26.IP10

SETPOINT ADJUSTMENT

ORCA92600

ORCA92600

B630 AHU1 SP ADJ

BAC.92600.AI04

26.IP4

B630 AHU1 RM TP

BAC.92600.AI01

26.IP1

Mount 60" A.F.F

10K OHM

6-WIRE

22 G

OVERRIDE BUTTON

Space Temperature x

D

BAC.92600.BO03

26.OP3

B630 AHU1 DX STG1

ORCA92600

BAC.92600.BO04

26.OP4

B630 AHU1 DX STG2

ORCA92600

HWS

HWR

BAC.92600.BO02

26.OP2

BAC.92600.BI03

26.IP3

ORCA92600

B630 AHU1 HC PMP1 SS

ORCA92600

B630 AHU1 HC PMP2 SS

B630 AHU1 HC PMP2 ST

BAC.92600.BI06

26.IP6

ORCA92600

ORCA92600

BAC.92600.BO07

26.OP7

CONDENSING UNIT

BAC.92600.BI24

26.IP24

B630 CU ST

ORCA92600

ORCA92600

B630 CU GEN AL

BAC.92600.BI25

26.IP25

INSIDE

OUTSIDE AIR TEMPERATURE SENSOR DETAIL

SUN SHIELD FACING DOWNWARD AS SHOWN ABOVE.

HORIZONTAL POSITION WITH THE AIR VENTS ON THE

SUNLIGHT. THE SENSOR SHOULD BE MOUNTED IN THE

MOUNT SENSOR ON THE NORTH WALL, OUT OF DIRECT

MOUNTING

T1

OUTSIDE

WALL

BAC.92600.AI11

26.IP11

B630 OA TP

ORCA92600

BAC.92600.AI21

26.IP21

FLOOR FLOOR

NC COM

NO

MTR

(e)

(e)

MTR

(e)

(e)

(e)

CV1

B630 HW VLV

ORCA92600

BAC.92600.AO06

26.OP6

BAC.92600.BO10

26.OP10

B630 HWP4 SS

ORCA92600

ORCA92600

B630 HWP4 ST

BAC.92600.BI17

26.IP17

ORCA92600

ORCA92600

B630 HWP3 SS

BAC.92600.BO09

26.OP9

BAC.92600.BI16

26.IP16

B630 HWP3 ST

HWR

HWS

B630 HWS TP

BAC.92600.AI13

26.IP13

ORCA92600

ORCA92600

B630 HWR TP

BAC.92600.AI14

26.IP14

BAC.92600.BI20

26.IP20

B630 WATER METER

BAC.92600.BI18

26.IP18

B630GAS METER

BAC.92600.BI19

26.IP19

B630 ELEC METER

ORCA92600

ORCA92600

ORCA92600

GALLONS

BTU

KWh

X1

R1

R11

R2

3 4

1 2

X2

CP2600A

C

AHU1 SF

R12 (n)

MOUNT @ STARTER

R1BU1C

BAC.92600.BO01

26.OP01

B630 AHU1 SF SS

CP92600

WHT/BLU

WHT/YLW

YLW

ORNG

X

H

X

O A

OL'S

MAG STARTER

(COM)

B630 AHU1 SF ST

BAC.92600.BI05

26.IP05

CP92600

CS1

480VAC 3 PHASE

L1 L2 L3

R11 (n)

R1BU1C

120 VAC

B630 AHU1 HC PMP1 SS

BAC.92600.BO02

26.OP2

480VAC 3 PHASE

(COM)

CP92600

B630 AHU1 HC PMP1 ST

BAC.92600.BI03

26.IP03

CP92600

CS2

R1BU1C

MOUNT @ STARTER

R13 (n)

WHT/BLU

WHT/YLW

ORNG

YLW

C

L3 L2

L1

NH

WHT/BLU

B630 AHU1 HC PMP2 SS

BAC.92600.BO07

26.OP7

(COM)

480VAC 3 PHASE

B630 AHU1 HC PMP2 ST

BAC.92600.BI06

26.IP6

CP92600

CP92600

CS3

L1 L2

L3

R14 (n)

MOUNT @ STARTER

R1BU1C

WHT/YLW

YLW

ORNG

H

C

N

BAC.92600.BO09

26.OP9

WHT/BLU

B630 HWP3 SS

MOUNT @ STARTER

R1BU1C

ORNG

YLW

WHT/YLW

BAC.92600.BI16

26.IP16

B630 HWP3 ST

ORCA92600

ORCA92600

480VAC 3 PHASE

R13

(COM)

CS1

L1 L3

L2

X

HWP3

MAG STARTER

OL'S

120 VAC

O

X

H A

C

MOUNT @ STARTER

BAC.92600.BO10

26.OP10

B630 HWP4 SS

ORCA92600

WHT/BLU

WHT/YLW

480VAC 3 PHASE

R1BU1C

R14

ORNG

YLW

X

H

HWP4

X

O A

OL'S

C

CS2

BAC.92600.BI17

26.IP17

B630 HWP4 ST

ORCA92600

L1

(COM)

L2 L3

MAG STARTER

120 VAC

Wire Color/Size

Red/18 TFF/MTW Stranded

Black/18 TFF/MTW Stranded

Blue/14 THHN Stranded

White/14 THHN Stranded

Orange/18 TFF/MTW Stranded

*Orange/Black Tracer/18 TFF/MTW Stranded

Brown/18 TFF/MTW Stranded

*Brown/White Tracer/18 TFF/MTW Stranded

Purple/14 THHN Stranded

Gray/14 THHN Stranded

24VDC Positive

24VDC Negative

24VAC Hot

24VAC Neutral

Inputs

Inputs (GND)

Outputs

Outputs (GND)

24VAC Hot Interlock

24VAC Neutral Interlock

System

Green 22TSP MS/TP Wiring (Modbus)

Green CAT5 Ethernet

SSC Standard Wire Chart m

A

K

O h m

V D

C

V D

C

Jumper in 10K Ohm position for all inputs .

Wire Color/Size

Red/18 TFF/MTW Stranded

Black/18 TFF/MTW Stranded

Blue/14 THHN Stranded

White/14 THHN Stranded

Orange/18 TFF/MTW Stranded

*Orange/Black Tracer/18 TFF/MTW Stranded

Brown/18 TFF/MTW Stranded

*Brown/White Tracer/18 TFF/MTW Stranded

Purple/14 THHN Stranded

Gray/14 THHN Stranded

24VDC Positive

24VDC Negative

24VAC Hot

24VAC Neutral

Inputs

Inputs (GND)

Outputs

Outputs (GND)

24VAC Hot Interlock

24VAC Neutral Interlock

System

Green 22TSP MS/TP Wiring (Modbus)

Green CAT5 Ethernet

SSC Standard Wire Chart m

A

K

O h m

V D

C

V D

C

Jumper in 10K Ohm position for all inputs .

Roof

Damper

Backdraft

RA

BAC.92600.BI26

26.IP26

BAC.92600.BO13

26.OP13

EF2

B630 KIT EF2 SS

Roof

B630 KIT EF2 ST

ORCA92600

KITCHEN

Roof

Backdraft

Damper

RA

EF3

Roof

GRILL

ORCA92600

BAC.92600.BO14

26.OP14

B630 GRILL EF3 SS

B630 GRILL EF3 ST

ORCA92600

ORCA92600

BAC.92600.BI27

26.IP27

120 VAC

MOUNT @ STARTER

R3

WHT/BLU

WHT/YLW

O

ORNG

480VAC 3 PHASE

R1BU1C

H

YLW

X

X

EF3

A

C

OL'S

CS3

(COM)

CS2

(COM)

MOUNT @ STARTER

R2

WHT/YLW

WHT/BLU

O

L3 L2L1

R1BU1C

ORNG

YLW

X

H

MAG STARTER

EF2

X

A

C

OL'S

L3

480VAC 3 PHASE

L1 L2

MAG STARTER

120 VAC

BAC.92600.BO13

26.OP13

B630 KIT EF2 SS

B630 KIT EF2 ST

ORCA92600

ORCA92600

BAC.92600.BI26

26.IP26

B630 GRILL EF3 ST

B630 GRILL EF3 SS

BAC.92600.BO14

26.OP14

BAC.92600.BI27

26.IP27

ORCA92600

ORCA92600