"Excellence is Our Standard, Customer Service is Our Passion"

Temperature Controls

Office Locations:

Rocky Mountain Region

8167 SouthPark Circle

Littleton, CO 80120

(303) 733-2300

C o v e r

S h e e t

California

1370 Reynolds Ave, Suite 103

Irvine, CA 92614

(949) 330-0673

Minnesota

1831 121 st

Street East

Burnsville, MN 55337

(800) 372-8837

Lighting Controls

Energy Management

CCTV

Access Control

System Integration

IT Services

Fire Alarm

Fire Suppression

Electrical Power Monitoring Systems

Vicinity Map

I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

Drawing

C o v e r

S h e e t d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

00-01-01

F a x

L i t t l e t o n

C o l o r a d o

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Buckley Air Force Base

BAFB Building 730 Air Stack Chiller Replacement

Buckley AFB, Colorado

Project Contractors:

Owner: Buckley AFB

General Contractor: Olgoonik Diversified Services, LLC

Project Engineered According to the Following:

1. Installation per SSC minimum installation standards or job specifications, whichever is more stringent.

2. Olgoonik Diversified Services, LLC,Purhchase Order Number 5002-254318-0015-16.16.900(S), Dated 03 May,

3. Setpoint Systems Corporation Scope of Work Letter, covering the building automation and automatic temperature control system, dated March 6, 2018, for BAFB B730 Air Stack Chiller Replacement Project, Job

#RM2018030009.

Setpoint Systems Corporation's Project Team:

Project Manager: Jon Wilson

Project Applications Engineer: Keith Johnson

Project Account Manager: Jeff Ellis

Copyright Protection for Drawings:

"The drawings, specifications and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright."

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise

AutoCAD SHX Text provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

I n d e x o f

D r a w i n g s d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

00-01-02 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Index of Drawings

I n d e x o f

D r a w i n g s

Sheet Number Format

03-01-01

Section Number

Series Number

Page Number

Drawing Number Legend

Section

Description

Cover, Symbols and Abbreviations

Campus Network

Building Network, Floor Plan

03 HVAC

04 Terminal Units

05 Misc

06 EPMS

Metering

Lighting

09 Access

10 CCTV

11 Fire Alarm

Fire Suppression

13 Schedules

14 Standard Details

Graphic Storyboard

Revised drawing sheet within existing drawing set.

This drawing set contains only those drawings affected by project C2910

Index of Drawings

Drawing # Drawing Name

00-01-01 Cover

00-01-02 Index

00-02-01 Standard Abbreviations

00-02-02

Standard Symbols

00-02-03 Standard Point Names

01-01-01

Campus Network Diagram

01-01-02

BACnet Devices and Computers

02-01-01

Building Network Diagram Page 1 of 2

02-01-02

Building Network Diagram Page 2 of 2

03-10-03 CHWS FLOW DIAGRAM

03-10-05 CHWS SYSTEM SOP

03-10-13 CP90800 Wire Chart 8

15-01-01

Graphics Storyboard

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

S t a n d a r d

A b b r e v i a t i o n s d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

00-02-01 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Standard Abbreviations

S t a n d a r d

A b b r e v i a t i o n s

NOTE: Not all Abbreviations are used in this project

Abbreviations compiled from ASHRAE FUNDAMENTALS HANDBOOK

POINT NAMING SCHEMES

LBBF SSS PPPPP MM

BUILDING LOCATION

BUILDING NAME/NUMBER

FLOOR NUMBER

SYSTEM TYPE

POINT FUNCTION

POINT FUNCTION MODIFIER

System Object Address / Point /Object Tag

DDC Device Subnet Number (Device#1 = 01)

BACnet Software Point/Object Address

DDC Device System Number (System#1 = 0100)

Hardware Address

Device Number

Point/Object Name/Descriptor

Point/Object Address

Point/Object State/Range

DEV0100

AHU1 OA DMPR

BAC.0100.AO03

0-10VDC

Control Drawing Point/Object Tag

BAC.00010101.BI1101

DDC Device Area Number (Area#1 = 0010000)

AI = Analog Input AO = Analog Output

BI = Binary Input BO = Binary Output

PI = Pulse Input

Point/Object Type

Point/Object Address Controller = XX Linknet = 1XX or 2XX eBCON (if applicable) Backplane Number eBCON (if applicable) I/O Module Number

AFF Above Finished Floor

AC Air Compressor

A/C Alternating Current

ACU Air Conditioning Unit

AD Air Dryer

AFMS Air Flow Monitoring Station

AHU Air Handling Unit

AI Analog Input

ALRM Alarm / Safety Input (suffix)

AO Analog Output

ATD Auto Tank Drain

AVE Averaging/Average

B Boiler

BI Binary Input

BO Binary Output

BOPD Break on Pressure Drop

BOPR Break on Pressure Rise

BOTD Break on Temperature Drop

BOTR Break on Temperature Rise

CAV Constant Air Volume

CFM Cubic Ft/Minute

CH Chiller

CHW Chilled Water

CHWR Chilled Water Return

CHWS Chilled Water Supply

CO Carbon Monoxide

CO2 Carbon Dioxide

COM Common

COND Condenser

CP Control Panel

CS Current Switch

CT Current Transformer

CT/CTR Cooling Tower

CU Condensing Unit

CUH Cabinet Unit Heater

CV Control Valve

CW Condenser Water

CWR Condenser Water Return

CWS Condenser Water Supply

D Damper

DA Damper Actuator (Pneumatic)

DB Dry Bulb (Temperature)

DC Direct Current

DEG F Degrees Fahrenheit

DM Damper Motor (Electric )

DPS Differential Pressure Switch

DPT Differential Pressure Transmitter

(E) Existing

EF Exhaust Fan

EP Electric Pneumatic Switch

ES End Switch

EVC Evaporative Cooling

FACP Fire Alarm Control Panel

FCU Fan Coil Unit

FLA Full Load Amps

FLT Filter

FM Flow Meter

FP Fan Powered

FS Flow Switch

FT Flow Transmitter

G Gauge

GND Ground

H Hot (Hot/Line)- voltage

HOA Hand-Off-Auto Switch

HT Humidity Transmitter

HVU Heating Ventilation Unit

HW Hot Water

HWR Hot Water Return

HWS Hot Water Supply

HX Heat Exchanger

I/P Current to Pneumatic Transducer

IAQ Indoor Air Quality

L Light

LF Line Filter

LLS Liquid Level Switch

LLT Liquid Level Transmitter

LTG Lighting Control

LTS Low Temperature Switch

MA Mixed Air

MAG Magnetic Starter

MAU Makeup Air Unit

MCC Motor Control Center

MOPD Make on Pressure Drop

MOPR Make on Pressure Rise

MOTD Make on Temperature Drop

MOTR Make on Temperature Rise

MZU Multi-Zone Unit

N Neutral (Wire) Voltage

NC Normally Closed

NO Normally Open

OA Outside Air

OL Overload

OWS Operator Work Station

P Pump

PB Push Button

PE Pressure Electric Switch

PS Proximity Switch

PRV Pressure Regulating Valve

PS Power Supply

PSW Pressure Switch

PT Pressure Transducer

R Relay

RA Return Air

RC Receiver Controller

RES Restrictor

RF Return Fan

RH Relative Humidity

RM Room

RPT Network Repeater

RTU Roof Top Unit

RV Relief Valve

SA Supply Air

SD Smoke Detector

SF Supply Fan

SRG Surge Protector

SV Solenoid Valve

SW Selector Switch

T Thermostat/Temperature

TB Terminal Block

TC Time Clock

TDR Time Delay Relay

TF Transfer Fan

THT Temperature Humidity Transmitter

TP Twisted Pair

TR Transformer

TRM Network End of Line Terminator

TS Temperature Sensor

TSP Twisted Shielded Pair

TT Temperature Transmitter

UH Unit Heater

UPS Uninterruptible Power Supply

UV Unit Ventilator

V Valve

VA Volt-Amps

VAC Volts Alternating Current

VAV Variable Air Volume

VDC Volts Direct Current

VF Ventilation Fan

VFD Variable Frequency Drive

VSW Vibration Switch

W Thermowell

WB Wet Bulb (Temperature)

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

S t a n d a r d

S y m b o l s d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

00-02-02 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Standard Symbols

S t a n d a r d

S y m b o l s

ELECTRIC VALVE

ELECTRIC VALVE

PNEUMATIC VALVE

PNEUMATIC VALVE

TEMPERATURE SENSOR

TEMPERATURE SENSOR

DIFFERENTIAL PRESSURE

FAN/PUMP VARIABLE

MAGNETIC

LOW / HIGH LIMIT SWITCH

(SPACE/ROOM)

(IMMERSION W/ WELL)

(STRAP ON)

PNEUMATIC DAMPER

PNEUMATIC DAMPER

ELECTRIC DAMPER

ELECTRIC DAMPER

BUTTERFLY VALVE

BUTTERFLY VALVE

BUTTERFLY VALVE

BUTTERFLY VALVE

RS-485 NETWORK

RS-485 NETWORK

DUCT SMOKE

DAMPER

DAMPER

CURRENT SWITCH OR

RESTRICTOR

CONTACTS

CONTACTS

SWITCH

SWITCH

SWITCH, N.O.

SOLENOID

PRESSURE REDUCING

PANEL LIGHT

PRESSURE GAUGE

SWITCH

SWITCH

TRANSFORMER

MOTOR STARTER

TRANSDUCER

(SECURITY FLAT PLATE ROOM)

GROUND

FLOW SWITCH

TRANSDUCER/SWITCH

RELAY

C

CONTACTOR COIL

RELAY COILR

FLOW METER

DESCRIPTIONSYMBOL

DIFFERENTIAL PRESSURE

DESCRIPTIONSYMBOL

STANDARD FLOW DIAGRAM SYMBOLS

TRANSDUCER/SWITCH

FLOW METER

C

DESCRIPTIONSYMBOL

FAN

FAN

PUMP

PUMP

D

C

X

COOLING COIL

COOLING COIL

H

H

C

X

HEATING COIL

HEAT EXCHANGER

HUMIDIFIER

FILTER

AIR FLOW MONITOR

AIR FLOW MONITOR

FREQUENCY DRIVE

STARTER

PARALLEL BLADE

OPPOSED BLADE

(CENTRIFUGAL)

(PLUG)

(BASE MOUNT)

(IN-LINE)

CHILLED WATER

DIRECT EXPANSION

STEAM/HOT WATER

GAS-FIRED

STEAM INJECTION

SECTION

(RIGID)

(CAPILARY AVERAGING)

HUMIDITY SENSOR/TRANSMITTER

(POINT/TIP)

TEMPERATURE SENSOR

THERMOSTAT/TEMPERATURE

TEMPERATURE SENSOR

TEMPERATURE SENSOR

TEMPERATURE SENSOR

(SPACE/ROOM)

THERMOSTAT

(PROGRAMMABLE)

THERMOSTAT

(SPACE/ROOM)

HUMIDITY SENSOR/TRANSMITTER

SWITCH (DPS)

TRANSMITTER (DPT)

PRESSURE

TRANSMITTER (PT)

TERMINATOR

REPEATER

DETECTOR

CURRENT TRANSDUCER

(PNEUMATIC)

(PNEUMATIC)

(CURRENT TO PNEUMATIC)

(ELECTRIC / PNEUMATIC)

(VENTURI)

(PRESSURE/ELECTRIC)

(TURBINE)

(DUCT-MOUNTED)

(FAN-INLET)

END SWITCH

(DAMPER)

(2-WAY)

(3-WAY)

(2-WAY)

(3-WAY)

ACTUATOR WITH POSITIONER

ACTUATOR NO POSITIONER

ACTUATOR NO END SWITCH

ACTUATOR W/END SWITCH

ELECTRIC (2-WAY)

ELECTRIC (3-WAY)

PNEUMATIC (2-WAY)

PNEUMATIC (3-WAY)

VALVE

DESCRIPTIONSYMBOL

STANDARD WIRING DIAGRAM SYMBOLS

DESCRIPTIONSYMBOL

LIGHT

TB2

WIRING TERMINALS

Wht/Yel

Wht/Blu

Wht/Blk

Orn

Yel

Blu

120vac

10-30V

Com RIBUIC

RELAY IN A BOX

WIRING TERMINALS

DAMPER ACTUATOR

WIRING TERMINALS

VALVE ACTUATOR

Wire Color/Size

Red/18 TFF/MTW Stranded

Black/18 TFF/MTW Stranded

Blue/14 THHN Stranded

White/14 THHN Stranded

Orange/18 TFF/MTW Stranded

*Orange/Black Tracer/18 TFF/MTW Stranded

Brown/18 TFF/MTW Stranded

*Brown/White Tracer/18 TFF/MTW Stranded

Purple/14 THHN Stranded

Gray/14 THHN Stranded

24VDC Positive

24VDC Negative

24VAC Hot

24VAC Neutral

Inputs

Inputs (GND)

Outputs

Outputs (GND)

24VAC Hot Interlock

24VAC Neutral Interlock

System

Green 22TSP MS/TP & Modbus Wiring

Green CAT5 Ethernet

Signifies field wiring by SSC.

Wire colors in parenthesis (color) is the manufacturers wire color.

Black/12 THHN Stranded

White/12 THHN Stranded

120VAC Hot

120VAC Neutral

Wiring Standards

(NORMALLY OPEN)

(NORMALLY CLOSED)

(LOW TEMPERATURE)

(PRESSURE)

(MOMENTARY PB)

VALVE

(FLOW)

(DAMPER END)

OVERLOADS

DESCRIPTIONSYMBOL

MOTORMTR

Setpoint Systems Corporation

G

VFD

MAG

HIGH

LOW

DPS

LOW

HIGH

DPT

A

F

M

S

FS

R

CS

CT

TRM

RPT

I

P

E

P

P/E

G

0 30

10 20

SD

ES

DA

S

M

DA

DM

DM

A AB

NO

NC COM

B

A AB

NC COM

A AB

NO

NC COM

B

A AB

NC COM

SWITCH, N.O.

(LATCHED PB)

SWITCH, N.C.

(MOMENTARY PB)

SWITCH, N.C.

(LATCHED PB)

SWITCH, N.O.

(TOGGLE)

MTR

L2L1 L3

H A

O

M

120V

OL'S

AUX

H A

O

HAND-OFF-AUTO

SWITCH

MAGNETIC STARTER

Signifies panel wiring by SSC.

Symbols compiled from ASHRAE FUNDAMENTALS HANDBOOK

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

S t a n d a r d

P o i n t

N a m e s d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

00-02-03 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Standard Point Names

S t a n d a r d

P o i n t

N a m e s

NOTE: Not all Abbreviations are used in this project

Abbreviations compiled from ASHRAE FUNDAMENTALS HANDBOOK

POINT NAMING SCHEMES

LBBF SSS PPPPP MM

BUILDING LOCATION

BUILDING NAME/NUMBER

FLOOR NUMBER

SYSTEM TYPE

POINT FUNCTION

POINT FUNCTION MODIFIER

System Object Address / Point /Object Tag

DDC Device Subnet Number (Device#1 = 01)

BACnet Software Point/Object Address

DDC Device System Number (System#1 = 0100)

Hardware Address

Device Number

Point/Object Name/Descriptor

Point/Object Address

Point/Object State/Range

DEV0100

AHU1 OA DMPR

BAC.0100.AO03

0-10VDC

Control Drawing Point/Object Tag

BAC.00010101.BI1101

DDC Device Area Number (Area#1 = 0010000)

AI = Analog Input AO = Analog Output

BI = Binary Input BO = Binary Output

PI = Pulse Input

Point/Object Type

Point/Object Address Controller = XX Linknet = 1XX or 2XX eBCON (if applicable) Backplane Number eBCON (if applicable) I/O Module Number

AC Air Compressor

ACCU Air Cooled Cond Unit

AFMS Air Flow Monitoring Station

AHU Air Handling Unit

ALRM Alarm or Safety Input (Suffix)

AMPS Amperes

AVG Average

BLDG Building

BLR Boiler

BYP Bypass

C Coil

CAV Constant Air Volume

COND Condenser

CLG COIL Cooling Coil

CLS Closed

CFM Cubic Feet Per Minute

CH Chiller

CHW Chilled Water

CHWR Chilled Water Return

CHWS Chilled Water Supply

CLG Cooling

COMP Compressor

CO Carbon Monoxide

CO2 Carbon Dioxide

CP Circulation Pump

CRAC Computer Room AC Unit

CRAH Computer Room AHU

CS Current Switch

CT Cooling Tower

CU Condensing Unit

CUH Cabinet Unit Heater

CW Condenser Water

CWR Condenser Water Return

CWS Condenser Water Supply

DB Dry Bulb

DHWR Domestic Hot Water Return

DHWS Domestic Hot Water Supply

DIS Disable

DMPR Damper

DOM Domestic

DP Differential Pressure

DP Dew Point

DRN Drain

DX Direct Expansion

EF Exhaust Fan

ELEC Electric

EM Emergency

ENA Enable

ENT Entering

EPO Emergency Power Off

EVAP CLG Evaporative Cooling

FACP Fire Alarm Control Panel

FAN Fan

FB Face/Bypass

FCU Fan Coil Unit

FDBK Feedback

FILL Fill

FLOW Flow Rate

FLT Fault

FLTR Filter

FPB Fan Powered Box

FREQ Frequency

FUEL Fuel

FURN Furnace

GEN Generator

GLY Glycol

HRN Horn

HI High

HTR Heater

HUM Humidity

HVU Heating Ventilation Unit

HW Hot Water

HWR Hot Water Return

HWS Hot Water Supply

HX Heat Exchanger

HZ Hertz

IR Infrared

ISO Isolation

LO Low

LVG Leaving

LVL Level Switch/Sensor

LOW LIMIT Freezestat

LTG Light

LTG Light Control

MA Mixed Air

MAU Makeup Air Unit

MAX Maximum

MIN Minimum

MTN Motion

MTR Meter

NO2 Nitrous Dioxide

O2 Oxygen

OA Outside Air

OCC Occupancy/Occupied

OPN Open

OVRD Override

PH Preheat

P Pump

POS Position

PRESS Pressure

PRI Primary

RA Return Air

RF Return Fan

RH Reheat

RM Room

RTU Rooftop Air Handling Unit

SA Supply Air

SCBR Scrubber

SEC Secondary

SEN Sensor

SF Supply Fan

SLC Silence

SMK Smoke

SP Static Pressure

SPC Space

SPEED Speed

SS Start/Stop

SCR Silicone Controlled Rectifier

STG Stage

STM Steam

STS Status

START Start

STOP Stop

STPT Setpoint

SW Switch

TF Transfer Fan

TEF Toilet Exhaust Fan

TEMP Temperature

TNK Tank

UH Unit Heater

UNOC Unoccupancy/Unoccupied

VA Volt/Amps

VFD Variable Frequency Drive

VLV Valve

VP Velocity Pressure

WTR Water

WB Wet Bulb

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

C a m p u s

N e t w o r k

D i a g r a m d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

01-01-01 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Firmware Version# 3.40

Fiber Network

BACnet Network

Future

Fitness Center

Building 35

DEV100400

DEV100500

DEV100700

HQ JCC

Building 26 Solar 11

AREA: DEV100000

MAC: 00-40-ae-00-44-56

BACnet Ethernet 10001

OWS12

DEV100200

DEV100300

DEV100900

Training Center

Building 30

DEV101100

DEV101200

6th Ave Gate

Visitor Center

Building 41

DEV100800

Dorm

Building 28

DEV101000

DEV101300

MCAF Dorm

Building 205

OWS11

DEV100600

DEV101600

Sat Pharm

Building 7

OWS# 10044

OWS# Laptop

DEV100100

Mail Center

Building 207

OWS#

DEV101400

DEV101500

Fire Station

Building 806

DEV702400

DEV702500

DEV702600

DEV702700

ABW HQ

Building 606

AREA: DEV700000

MAC: 00-40-ae-02-2e-6f

BACnet Ethernet 10001

DEV702100

DEV702200

DEV702300

Medical

Building 600

DEV700700

OWS 10060

DEV701000

DEV702000

DEV703000

DEV704000

CC Chapel

Building 316

AREA: DEV800000

MAC: 00-40-ae-00-2f-d4

BACnet Ethernet 10001

OWS9

DEV803500

DEV803600

DEV803700

Youth Center

Building 350

DEV805100

DEV805200

DEV805300

Consolidated

Services (CSF)

Building 347

OWS13

DEV802700

DEV802800

DEV802900

Child

Development

Center (CDC)

Building 351

OWS14

DEV804300

DEV804400

DEV804500

COMM

Building 730

AREA: DEV900000

MAC: 00-40-AE-00-10-68

BACnet Ethernet 10001

OWS#

DEV900100

DEV900200

DEV900300

DEV900400

DEV900500

DEV900600

DEV900700

METERS

Building 841

DEV905000

SP OPS

Building 620

DEV902500

CDC

Building 725

OWS11

DEV902200

DEV902300

DEV902400

Dining

Building 630

DEV902600

DEV900100 RTR

DEV902700

JAAB

Building 1005 Solar 12

AREA: DEV500000

MAC: 00-40-ae-00-2e-d0

BACnet Ethernet 10001

DEV502000

DEV502100

DEV502200

DEV502300

CE Shops

Building 1007

OWS4

DEV502400

DEV502500

Mississippi Gate

Building B1554

DEV503000

AFOSI

Building 1550

DEV502700

Entomology Lab

Building 1019

DEV502900

Consolidated

Fuels

Building 1054

DEV501000

COANG COMM

Building 850

AREA: DEV400000

MAC: 00-40-ae-02-31-a0

BACnet Ethernet 10001

OWS#

SQ OP COANG

Building 701

DEV408000

SQ OP COANG

Building 700

DEV404000

BX

Building 1

OWS# Laptop

TRANE BCU-1

DEV403500

DEV403700

DEV403600

DEV403800

DEV403900

Civil Eng

Building 830

DEV403000

DEV403100

COANG HDQTR

Building 706

DEV402000

Tower

Building 1530

DEV401000

Alert hangars

Building 912-917

DEV405000

ANG hangar

Building 801

DEV403200

Army Hangar

Building 1510

DEV507000

Wing Headquarters

Building 1030

AREA: DEV600000

MAC: 00-40-ae-00-2d-10

BACnet Ethernet 10001

OWS6, OWS7

DEV604000

DEV604100

TRANE BCU-2

Outdoor Rec.

Facility

Building 1022

DEV600100

BRAC Security

Building 1029

DEV600200

DEV600300

Leadership Dev.

Building 1032

OWS#

DEV602000

DEV602100

DEV602200

AFR Training

Facility

Building 392

OWS#

DEV801500

DEV801600

DEV801700

DEV801800

DEV801900

ARPC

Building 390

DEV800900

DEV801000

DEV801100

DEV801200

DEV801300

DEV801400

Dorm

Building 205

CARD ACCESS

DEV4000-4900

Laptop DEV10053

Solar Array

Building 1535

DEV500300

Working Dog

Kennel

Building 1522

DEV505300

Dorm

Building 28

CARD ACCESS

DEV2000-3600

Laptop DEV10051

Vehicle Maint

Building 340

DEV703200

DEV900800

Freight Transfer

Building 1120

DEV405100

DEV405200

TLF/VQ

Building 331/332

AREA: DEV200000

MAC: 00-40-ae-00-f2-e2

BACnet Ethernet 10001

DEV202600

DEV203100

DEV203200

DEV203300

DEV203400

DEV203500

DEV203600

DEV203700

Building 1006

DEV502600

Building 1015

DEV503300

Building 1017

DEV503400

Building 1009

DEV502800

Building 1013

DEV503200

ACFT Support

Building 814

DEV406100

DEV402900

Fuel Cell

Building 800

DEV405500

Jet Engine Shop

Building 960

DEV405400

hangar

Building 909

DEV405300

SFOF

Building 1028

DEV500400

DEV500500

DEV500600

DEV500700

DEV500800

Muntitions Admin

Building 1640

DEV401100

Munitions Admin

Building 1641

DEV401200

Muntitions Admin

Building 1642

DEV401300

Weapons

Building 805

DEV404600

Alert Crew Hqtrs

Building 911

DEV4900

Medical Whse

Building 602

DEV700100

DEV700200

Army Hangar

B1000

DEV503200

Army Hangar

B1500

DEV503100

Stand Alone

Stand Alone

Fuel Storage

Building 728

DEV906000

DEV906100

Stand Alone

DEV205000 Meter

DEV205300 Meter

DEV205400 Meter

DEV205500 Meter

BAFB Air Force WAN

REVISED 6-28-2017

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

B A C n e t

D e v i c e s a n d

C o m p u t e r s d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

01-01-02 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

REVISED 06-22-2018

BACNET DEVICES and INTERFACES

Address: Building: Description:

1 BX BCU RTUS

2 B1030 BCU CHLR

3 B1032 BCU CHLR

6 B730 BCU CHLR3

7 B730 BCU CHLR2

11 B26 Veris Solar

12 B1005 Veris Solar

13 B351 Veris Elec

14 B801 Veris Elec

15 B1005 Veris Elec

16 B26 Veris Elec

17 B620 Veris Elec

18 B1054 Veris Elec

19 B1029 Veris Elec

20 B392 Veris Elec

21 B7 Veris Elec

22 B207 Veris Elec

23 B390 Veris Elec

24 B1030 Veris Elec

25 SolarArray Inverter1

26 SolarArray Inverter2

27 B350 Veris Elec

30 B701 Veris Elec

31 B331 Veris Elec

32 B340 Veris Elec

33 B1522 Veris Elec

34 B1120 Veris Elec

35 B1 BX Veris Elec

36 B1 Comm Veris Elec

37 B205 Veris Elec

38 B1510 Veris Elec

39 B1007 Veris Elec

40 B1554 Emon Energy Meter

41 B600 Veris Elec

42 B602 Veris Elec

43 B850 Veris Elec West

44 B850 Veris Elec East

45 B1500 Veris Elec

46 B1000 Veris Elec

47 B1530 Veris Elec

48 B1032 Veris Elec

49 B1022 Veris Elec

50 B909 Veris Elec

51 B960 Veris Elec

52 B700 Veris Elec

53 B800 Veris Elec

54 B841 Veris Elec North

55 B841 Veris Elec South

56 B730 Veris Elec

57 B28 Veris Elec

58 B35 Veris Elec

59 B316 Veris Elec

60 B347 Veris Elec

61 B814 Veris Elec

62 B606 Veris Elec

63 B630 Veris Elec

64 B725 Veris Elec

65 B706 Veris Elec

66 B1028 Veris Elec

67 B1642 Veris Elec

68 B1640 Veris Elec

69 B1641 Veris Elec

70 B914 Main Elec

71 B914 North Inverter

72 B806 Veris Elec

75 B806 Chiller BACnet

73 B914 South Inverter

74 B805 Veris Elec

99 B392 York Chiller

100 B392 Fieldserver

101 B390 CHLR1

102 B390 CHLR2

103 B390 CRAC1

104 B390 CRAC2

105 B390 CRAC3

106 B390 CRAC4

107 B390 CRAC5

108 B390 CRAC6

109 B390 CRAC7

110 B205 Fieldserver

200 SolarArray Fieldserver

201 B205 Fieldserver

10000 B1 BX TRANE BCU

10281 B1028 Chiller 1

10282 B1028 Chiller 2

10283 B1028 CRAC-1

10284 B1028 CRAC-2

11049 B1 BX Fire Alarm Interface

11050 B1 BX RTU-1

11051 B1 BX RTU-2

11052 B1 BX RTU-3

11053 B1 BX RTU-4

11054 B1 BX RTU-5

11055 B1 BX RTU-6

11056 B1 BX RTU-7

11057 B1 BX RTU-8

11059 B1 BX RTU-10

11068 B1 BX RTU-29

11071 B1 BX RTU-32

12062 B1 BX RTU-13

11063 B1 BX RTU-14

12064 B1 BX RTU-15

12065 B1 BX RTU-16

12072 B1 BX RTU-17

12073 B1 BX RTU-18

12066 B1 BX RTU-19

12067 B1 BX RTU-26

12069 B1 BX RTU-30

12070 B1 BX RTU-31

12000 B1 BX RTU-11

12058 B1 BX RTU-9

12061 B1 BX RTU-12

45810 B602 Trane RTU-4

45811 B392 BLR1

45812 B392 BLR2

45813 B390 BLR1

45814 B390 BLR2

45815 B28 CHLR

50015 B347 Boiler-1 BACnet

50035 B35 Boiler-3 (Master) BACnet

50036 B35 Boiler-2 BACnet

50037 B35 Boiler-1 BACnet

50075 B806 Boiler-1 BACnet

50076 B806 Boiler-2 BACnet

50081 B35 HWP-1 BACnet

50082 B35 HWP-2 BACnet

51003 B1550 CRAC-1 BACnet

51004 B1550 CRAC-2 BACnet

#### B1550 FCU-1 BACnet

#### B1550 FCU-2 BACnet

#### B1550 FCU-3 BACnet

51034 B26 AHU-2 BAcnet

51035 B26 AHU-1 BACnet

51036 B1550 AHU-1 BACnet

50110 B316 Boiler-2 BACnet

50111 B316 Boiler-1 BACnet

60100 B600 AHU-2 SF1

60200 B600 AHU-2 SF2

60300 B600 AHU-2 RF1

60400 B600 AHU-2 RF2

60500 B600 AHU-3 SF1

60600 B600 AHU-3 SF2

60700 B600 AHU-3 RF1

60800 B600 AHU-3 RF2

61002 B730 PCO Web CHLR1

61004 B730 CRAC-9

61005 B730 CRAC-10

505401 B1024 MAU-1

550098 B1028 Mammoth AHU-1

550099 B1028 Mammoth AHU-2

601024 B26 B-3 (Leader) BACnet

601025 B26 B-4 BACnet

601026 B26 B-1 (Leader) BACnet

601027 B26 B-2 BACnet

601028 B1550 Boiler-1(Leader) BACnet

601029 B1550 Boiler-2 BACnet

650030 B1032 Boiler-1

650031 B1032 Boiler-2

701001 B600 HWP-1

701002 B600 HWP-2

701003 B600 CHP-1

701004 B600 CHP-2

BAFB Computers

Address: Building: Description: IP:

DEV9900 B351 OWS14 169.254.127.119

DEV10001 B725 OWS11 131.04.136.133

DEV10007 B316 OWS9 131.04.176.61

DEV10011 B205 OWS11 131.40.160.237

DEV10012 xx Laptop HVAC Jack xx

DEV10029 xx Laptop HVAC LT6 xx

DEV10031 B1030 OWS6 2nd Floor 169.254.45.248

DEV10032 B1005 OWS1 131.04.153.215

DEV10033 B1005 OWS2 ORCAweb Server 131.04.153.199

DEV10034 B1007 OWS4 131.40.132.185

DEV10035 B1005 OWS3 131.40.153.189

DEV10036 B347 OWS13 131.40.176.199

DEV10037 B1032 OWS# 131.40.150.83

DEV10038 B433 Laptop CEITS 131.40.168.161

DEV10039 xx Laptop CSF/EMCS xx

DEV10041 B1030 OWS7 1st Floor 131.04.148.184

DEV10042 xx Laptop EMCS xx

DEV10043 B1005 OWS# xx

DEV10044 B7 OWS# xx

DEV10045 B7 OWS# Laptop xx

DEV10046 B391 OWS# xx

DEV10047 xx Laptop HVAC Shop xx

DEV10048 B730 Laptop# xx

DEV10048 B1005 ORCAweb Server xx

DEV10049 B1005 HISTORIAN xx

DEV10050 B207 OWS# xx

DEV10051 B28 Laptop# xx

DEV10053 B205 Laptop# xx

DEV10054 B392 OWS# 131.40.176.239

DEV10060 B600 OWS# 131.40.156.247

DEV10073 B350 OWS# 131.40.176.220

B430 OWS#1 131.40.168.135

B430 OWS#2 131.40.168.135

B331 OWS# 131.40.64.26

B390 OWS# 131.40.176.239

B316 OWS# 131.40.176.74

Address: Building: Description: IP:

DEV10081 B730 OWS# xx

DEVxx B26 OWS12 xx

DEVxx B1BX OWS# Laptop xx

DEVxx xx Laptop HVAC xx

BACnet Devices and Computers

B A C n e t

D e v i c e s a n d

C o m p u t e r s

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

Building Network Diagram Page 1 of 2

B u i l d i n g

N e t w o r k

D i a g r m

P g e o f

Fiber

Ethernet

RS485

Field Wiring eBUS

Since 1983

CP6

To PPP-1, PPP-2, PPP-3, PPP-4, and PPP-5

Operator Workstation (by SSC)

With OWS/Illustrator

Location to be Verified

TRM

Since 1983

CP1

DEV900144

DFM-400P

RS-485 MS/TP

OWS-1

PTR-1

Dom H2O Meter

Nat. Gas Meter

Since 1983

CP2

DEV900200

DSC-1616E

AHU-2

TRM

Since 1983

CP7

DEV900103

DFM-400P

RS-485 MS/TP

Located in Mech Rm 177 (West Wall)

DEV900300

DSC-1616E

1 2 34 75 6 8

Since 1983

CP3

E-net Switch

8-Port

AHU-1

Since 1983

CP4

Located in Mech Rm L005 (West Wall)

Since 1983

CP5

DEV900500

DSC-1616E

Underfloor

DEV900500-100

DFM-1600

Registers

Underfloor

Registers

Located in Janitor L001A

DEV900501

CRAC-4 & 5

DAC-606

DEV900302

CRAC-1, 2 & 3

DAC-606

Since 1983

CP8

Located in Mech Rm L012

DEV900602

ADM-2W704

Gate Control

Serving VAV, CRAC, CUH, and UH Controllers

DEV900102

LIGHTING

DAC-9004

Since 1983

CP6-1

DEV900603

ADM-2W704

Door Control

Since 1983

CP6-2

DEV900604

ADM-2W704

Door Control

Since 1983

CP6-3

DEV900605

ADM-2W704

Door Control

Since 1983

CP6-4

DEV900606

ADM-2W704

Door Control

Since 1983

CP6-5

DEV900607

ADM-2W704

Door Control

Since 1983

CP6-6

Since 1983

CP9

Located in Mech Rm L0900

RS-485 MS/TP

Mount at UH

Located in Elec Rm 175

DCA-1: RM 177 DCA-2: RM 177 DCA-3: RM 171N DCA-4: RM 171C DCA-5: RM 171F DCA-6: RM L012 DCA-7: RM L038

RS-485 MS/TP

CAT 5 Ethernet

CAT 5 Ethernet

DEV900104

CRAC-1

DAC-1146

CRAC-2 CRAC-3 CRAC-4

Since 1983

CP100

DEV900100

DSC-1616E

DEV900105 DEV900106 DEV900107

DAC-1146 DAC-1146 DAC-1146

Since 1983

CP10

DEV900800

DSC-1616E

CHWS

DEV900800-1

DFM-1616

CHWS

Located in Mech Rm L012

CRAC-9 CRAC-10

BACnet

Interface

BACnet

Interface

22/2 TSP MSTP

Located in CP100A

Since 1983

AREA

DEV900000

DSM-RTR

SW2 (Located inside CP100)

To BUCKnet

CHILLER-3

BACnet

Interface

Add. #61004Add. #6 Add. #61005

Since 1983

CP900145

DEV900145

DAC-606

Generator

Veris Electric Meter

Bldg kW

CHILLER-2

BACnet

Interface

Add. #7

ADD; 56

RS-485 BAUD RATE 38,400

DSC-1616E

DEV900700

HW System

DFM-1600

DEV900700-100

HW System

16-Port

E-net Switch

ASM-24E

DEV900600

Access System

ADM-2W704

DEV900601

Door Control

DSM-RTR

DEV900900

Door Control

I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

B u i l d i n g

N e t w o r k

D i a g r g e o f d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

02-01-01 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

DEV900119-DEV900142

DVC-V

DEV900143

VAV

DVC-V

DEV900118

VAV

Boiler B1

ProtoNode

DEV50112

Boiler B2

ProtoNode

DEV50113

Boiler B3

ProtoNode

DEV50114

TRM

TRM

DSC-1616E

DEV900400

Underfloor

Registers

DFM-1600

DEV900400-100

Underfloor

Registers

DFW-440

DEV900400-101

Underfloor

Registers

DAC-9004

DEV900301

UH-3

TRM

NEW BILL OF MATERIALS

ID#

QUANTITY

TAG PART DESCRIPTION MFG

29904 1 TRM 151924 TRM768 BACnet Network Terminator Delta

CHILLER-1

BACnet

Interface

Add. #8

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

SWITCH-5

AutoCAD SHX Text

TM

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

Building Network Diagram Page 2 of 2

B u i l d i n g

N e t w o r k

D i a g r g e o f

I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

B u i l d i n g

N e t w o r k

D i a g r g e o f d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

02-01-02 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

Specification Reference

15950A: 1.3.5.1.2, 2.2a

Drawing Code AF 131-20-07

M6.01

RS485

To PPP-2

PPP-1

TRM

RS485 #1

24vac #1

To All Loop #1

Controllers

Located in Mech Rm 177

(West Wall)

DEV30202

VAV-239

DVC-V322A

DEV30203

VAV-240

DVC-V322A

DEV30204

VAV-209

DVC-V322A

DEV30205

VAV-241

DVC-V322A

DEV30206

VAV-242

DVC-V322A

DEV30207

VAV-236

DVC-V322A

DEV30208

VAV-235

DVC-V322A

DEV30209

VAV-237

DVC-V322A

DEV30201

UH-2

DAC-304

RS485

From DEV30200

PPP-2

TRM

RS485 #1

24vac #1

To All Loop #1

Controllers

Located in Storage 172B

DEV30210

VAV-234

DVC-V322A

DEV30211

VAV-233

DVC-V322A

DEV30212

VAV-232

DVC-V322A

DEV30213

VAV-231

DVC-V322A

DEV30214

VAV-230

DVC-V322A

DEV30215

VAV-205

DVC-V322A

DEV30216

VAV-202

DVC-V322A

RS485 #2

24vac #2

To All Loop #2

Controllers

DEV30219

VAV-238

DVC-V322A

DEV30220

VAV-243

DVC-V322A

DEV30217

CRAC-7&8

DAC-606

RS485

To PPP-4

PPP-3

TRM

RS485 #1

24vac #1

To All Loop #1

Controllers

Located in Flight Storage

DEV30225

VAV-223

DVC-V322A

DEV30226

VAV-226

DVC-V322A

DEV30227

VAV-225

DVC-V322A

DEV30228

VAV-224

DVC-V322A

DEV30229

VAV-227

DVC-V322A

DEV30230

VAV-228

DVC-V322A

DEV30231

VAV-229

DVC-V322A

DEV30232

VAV-222

DVC-V322A

DEV30233

VAV-221

DVC-V322A

173J

RS485

To PPP-5

PPP-4

TRM

RS485 #1

24vac #1

To All Loop #1

Controllers

Located in Storage 172B

DEV30235

VAV-213

DVC-V322A

DEV30236

VAV-214

DVC-V322A

DEV30237

VAV-215

DVC-V322A

DEV30238

VAV-216

DVC-V322A

DEV30240

VAV-218

DVC-V322A

DEV30241

VAV-217

DVC-V322A

RS485 #2

24vac #2

To All Loop #2

Controllers

DEV30242

VAV-219

DVC-V322A

DEV30239

CH-2

DAC-304

RS485 #3

24vac #3

To All Loop #3

Controllers

DEV30251

VAV-203

DVC-V322A

DEV30252

VAV-204

DVC-V322A

DEV30250

CRAC-6

DAC-606

DEV30243

VAV-212

DVC-V322A

DEV30244

VAV-208

DVC-V322A

DEV30246

VAV-211

DVC-V322A

DEV30247

VAV-210

DVC-V322A

DEV30248

VAV-206

DVC-V322A

DEV30249

VAV-207

DVC-V322A

DEV30245

CH-1

DAC-304

DEV30253

VAV-220

DVC-V322A

DEV30254

UH-1

DAC-304

DEV30221

VAV-E01

DVC-V322A

DEV30222

VAV-EO4

DVC-V322A

DEV30223

VAV-EO3

DVC-V322A

DEV30224

VAV-EO2

DVC-V322A

RS485

From PPP-4

PPP-5

TRM RS485 #1

24vac #1

To All Loop #1

Controllers

Located in Storage 172B

DEV30255

VAV-C05

DVC-V322A

DEV30256

VAV-C06

DVC-V322A

DEV30257

VAV-C07

DVC-V322A

DEV30258

VAV-C08

DVC-V322A

DEV30259

VAV-C10

DVC-V322A

DEV30260

VAV-C09

DVC-V322A

RS485

From PPP-1

RS485

From PPP-2

RS485

From PPP-3

RS485

From DEV30200

RPT=DEV30234

Since 1983

CP11

Since 1983

CP10

Mount at UH

Mount in CH

Mount at UH

Mount in CH

RS-485 Comm Trunk

From DEV30200 (DSC)

Located in Mech Rm 177

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise

AutoCAD SHX Text provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

AutoCAD SHX Text

LO

AutoCAD SHX Text

RPT

AutoCAD SHX Text

TM

AutoCAD SHX Text

TM

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

AutoCAD SHX Text

LO

LO

CRAC-3

30 GPM

15 TONS

CRAC-2

30 GPM

15 TONS

CRAC-1

30 GPM

15 TONS

CRAC-5

8.5 GPM

4.2 TONS

CRAC-4

12.5 GPM

6.2 TONS

CRAC-7

7.5 GPM

3.6 TONS

CRAC-6

8.5 GPM

4.2 TONS

CRAC-8

7.5 GPM

3.6 TONS

AIR COOLED

CHILLER

ACC-2

AHU-2

78 GPM

45.5 TONS

AHU-1

61 GPM

35.6 TONS

60 TONS

CP90800

COM P-1A SS

BAC.90800.BO08

D.A. = ON

CP90800

COM P-1A STATUS

BAC.90800.BI115

D.A. = ON

CP90800

COM P-1B SS

BAC.90800.BO09

D.A. = ON

CP90800

COM P-1B STATUS

BAC.90800.BI116

D.A. = ON

P-1B

P-1A

AIR COOLED

CHILLER

ACC-1

AIR COOLED

CHILLER

ACC-3

DEV90800

COM CCWR TEMP

BAC.90800.AI102

4-20mA/ 32-95°F

DEV90800

COM CCWS TEMP

BAC.90800.AI101

4-20mA/ 32-95°F

TT 02-01

CP90800

COM ISBP VLV

BAC.90800.AO02

0-10V DC

Chiller BacNet Interface is provided by Equipment Mfgr.

The Following points will be mapped to the DDC Central Workstation:

1. Chiller Enable

2. Chiller Leaving Water Temperature Set Point

3. Chiller General Alarm

4. Chiller Run Status

5. Compressor Operating Current (Amps)

6. operating Voltage

7. Chiller Water Flow Status

All the Above Listed Points Are to be Provided by the Chiller Control Panel.

CP90800

COM CWP-3A SS

BAC.90800.BO12

D.A. = ON

CP90800

COM CWP-3A STATUS

BAC.90800.BI111

D.A. = ON

CP90800

COM CWP-3B SS

BAC.90800.BO13

D.A. = ON

CP90800

COM CWP-3B STATUS

BAC.90800.BI112

D.A. = ON

P-3BP-3A

TT 02-06

TT 02-03

CP90800

COM 2CWS TEMP

BAC.90800.AI105

4-20mA/ -58-122°F

CP90800

COM 2CWR TEMP

BAC.90800.AI106

4-20mA/ -58-122°F

CP90800

COM CWS MIX VLV

BAC.90800.AO04

0-10V DC

CP90800

COM P-2B SS

BAC.90800.BO11

D.A. = ON

CP90800

COM P-2B STATUS

BAC.90800.BI113

D.A. = ON

P-2B

CP90800

COM P-2A SS

BAC.90800.BO10

D.A. = ON

CP90800

COM P-2B STATUS

BAC.90800.BI114

D.A. = ON

P-2A

TT 02-04

TT 02-05

CP90800

COM PCWR TEMP

BAC.90800.AI04

4-20 mA/ 32-212°F

CP90800

COM PCWS TEMP

BAC.90800.AI03

4-20mA/ 32-212°F

ICE STORAGE TANK

ST-1

CP90800

COM IST1 LEVEL

BAC.90800.AI07

4-20mA/0-6"

CP90800

COM CW GLYCOL LOW

BAC.90800.BI109

D.A. = Alarm

CP90800

COM CW GFP STATUS

BAC.90800.BI110

D.A. = ON

P-5B

P-5A

P-6B

P-6A

P-6B

P-7A

CRAC-9

60 GPM

20 TONS

CRAC-10

60 GPM

20 TONS

CP90800

COM P-5B SS

BAC.90800.BO15

D.A. = ON

CP90800

COM P-5B STATUS

BAC.90800.BI15

D.A. = ON

CP90800

COM P-5A SS

BAC.90800.BO14

D.A. = ON

CP90800

COM P-5A STATUS

BAC.90800.BI14

D.A. = ON

CP90800

COM P-6A SS

BAC.90800.BO101

D.A. = ON

CP90800

COM P-6A VFD SPD

BAC.90800.AO105

0-10VDC

CP90800

COM P-6A STATUS

BAC.90800.BI10

D.A. = ON

CP90800

COM P-7A SS

BAC.90800.BO103

D.A. = ON

CP90800

COM P-7A VFD SPD

BAC.90800.AO107

0-10VDC

CP90800

COM P-7A STATUS

BAC.90800.BI12

D.A. = ON

CP90800

COM P-6B SS

BAC.90800.BO102

D.A. = ON

CP90800

COM P-6B VFD SPD

BAC.90800.AO106

0-10VDC

CP90800

COM P-6B STATUS

BAC.90800.BI11

D.A. = ON

CP90800

COM P-7B SS

BAC.90800.BO104

D.A. = ON

CP90800

COM P-7B VFD SPD

BAC.90800.AO108

0-10VDC

CP90800

COM P-7B STATUS

BAC.90800.BI13

D.A. = ON

CP90800

COM CHWS LOOP GPM

BAC.90800.AI16

4-20mA=0-400 GPM

TT 02-02

DEV90800

COM CH3 CWS ISOV

BAC.90800.BO06

DA=OPEN

DEV90800

COM CH1 CWS ISOV

BAC.90800.BO05

DA=OPEN

FS 02-01

FS 02-02

CP90800

COM CH1 AMPS

BAC.90800.AI05

DA=AMPS

CS-STD

R

RIB-10A

R

RIB-10A

CS-STD

R

RIB-10A

R

RIB-10A

CS-STD

R

RIB-10A

R

RIB-10A

R

RIB-10A

CS-STD

CS-STD

R

RIB-10A

Onicon Flow Meter

HI

LO

DEV100

COM P6 LOOP DP

BAC.100.AI08

4-20mA=0-60PSI

HI

LO

DEV100

COM P7 LOOP DP

BAC.100.AI09

4-20mA=0-60PSI

CS-STD

BILL OF MATERIALS

ID#

QUANTITY

TAG PART DESCRIPTION TYPE

72046 6 CS-STD H600 Split Core Adjustable Current Switch, LED Field

29658 2 DPT3 W30-35E-3VLV 0-60 PSID DIFF PRESS TRANS W/ BYPASS

FIELD

30765 8 RIB-10A RIBU1C

Enclosed 10A SPDT Relay 10VDC

FIELD

CHWS FLOW DIAGRAM

C H

W S

F L O

W

D

I A G

R A M

I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m

S i t e

N a m e

F i l e

N a m e

S i t e

L o c a t i o n

C H

W S

F L O

W

D

I A G

R A M d w g

S h e e t

T i t l e

R e v

D a t e

D e s c r i p t i o n

P M

A E

J o b

03-10-03 x

L i t t l e t o n

C o l o r a

S o u t h P a r k

C i r c l e

B A F B

B u i l d i n g

B u c k l e y

A F B

C o l o r a d o

C

B A F B

B

F r e e

C o o l i n g

J W

K J

C

B A F B

B

A i r

S t a c k

C h i l l e r

R e p l a c e m e n t

A s B u i l t

D r a w i n g s

J W

K J

See CHWS Flow

Diagram Part 2 for Continuation

DEV90800

COM HX-1 CHWR ISO VLV

BAC.90800.BO07

DA=OPEN

Chiller BacNet Interface is provided by Equipment Mfgr.

The Following points will be mapped to the DDC Central Workstation:

1. Chiller Enable

2. Chiller Leaving Water Temperature Set Point

3. Chiller General Alarm

4. Chiller Run Status

5. Compressor Operating Current (Amps)

6. operating Voltage

7. Chiller Water Flow Status

All the Above Listed Points Are to be Provided by the Chiller Control Panel.

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS(CWR ICE)

AutoCAD SHX Text

CWR(CWS ICE)

AutoCAD SHX Text

CWS(CWR ICE)

AutoCAD SHX Text

CWR(CWS ICE)

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

CWS(CWR ICE)

AutoCAD SHX Text

CWR(CWS ICE)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DPT3

AutoCAD SHX Text

DPT3

AutoCAD SHX Text Copyright Protection For Drawings

AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."

CHILLED WATER SYSTEM SEQUENCE OF OPERATION:

THE CHILLED WATER SYSTEM SHALL PROVIDE COOLING FOR THE ENTIRE FACILITY. THE OVERALL BUILDING

COOLING LOAD WILL BE SEPARATED INTO TWO INTERFACED SYSTEMS. THESE SYSTEMS WILL SERVE THE

FOLLOWING DISTINCT LOADS: UPPER LEVEL (VAV AIR HANDLING SYSTEM - AHU -2), LOWER LEVER

(UNDERFLOOR VAV AIR HANDLING SYSTEM - AHU -1); (CRAC-4, 5, 6, 7, & 8); (CRAC-1, 2, & 3), AND NEW

COMMUNICATION ROOM (CRAC 9 &10, WITH PROVISION FOR (F) CRAC 11 & 12).

UPPER LEVEL COOLING IS PROVIDED DURING THE OCCUPIED MODE BY THE AIRSIDE ECONOMIZER CYCLE

AND THE ACC3 CHILLED WATER SYSTEM. COOLING REQUIRED IN THE UNOCCUPIED MODE IS PROVIDED BY

THE ECONOMIZER CYCLE. THE OCCUPIED MODE IS 7:00 AM TO 5:00 AM (ADJUSTABLE) SEVEN DAYS PER

WEEK, 365 DAYS PER YEAR.

LOWER LEVEL COOLING IS PROVIDED DUR08ING THE ICE-DISCHARGING MODE BY AHU-1 ECONOMIZER

CYCLE AND THE CHILLED WATER SYSTEM. AHU-1 COOLING REQUIRED IN THE ICE-MAKING MODE IS

PROVIDED BY THE AHU-1 AIRSIDE ECONOMIZER CYCLE IN SEQUENCE WITH THE WATER-SIDE ECONOMIZER

USING THE ICE-STORAGE SYSTEM. THE OCCUPIED MODE IS 24 HOURS PER DAY SEVEN DAYS A WEEK.

COMMUNICATIONS ROOM COOLING IS PROVIDED BY THE CHILLED WATER SYSTEM SERVED FROM ACC1 &

ACC2. THE OCCUPIED MODE IS 24 HOURS PER DAY SEVEN DAYS PER WEEK.

NCC EQUIPMENT & SIPRNET ROOMS ARE PROVIDED BY THE CHILLED WATER SYSTEM. THE OCCUPED MODE IS

24 HOURS PER DAY SEVEN DAYS PER WEEK. THE FOLLOWING EXISTING HVAC EQUIPMENT SERVING THESE

ROOMS IS SERVED BY BACKUP POWER THROUGH THE EMERGENCY GENERATOR INCLUDING; ACC-2, P-1A, CRAC-1, CRAC-2 & CRAC-3.

THE NEW COMMUNICATION ROOM CHILLED WATER SYSTEM WILL BE PROVIDED WITH EMERGENCY POWER

SOURCES TO ENABLE ACC-1, P-5A, P-6A, & P-7A, CRAC-9 & 10.

CHILLED WATER SYSTEM CONTOL:

THE (E) BAS MONITORS THE CHILLED WATER SUPPLY AND RETURN TEMPERATURES, AND SHALL SEND AN

ALARM IF THE CHILLED WATER SUPPLY TEMPERATURE IS ABOVE 50°F (ADJ). THIS SHALL BE EXPANDED TO

ALL 3 CHILLERS. THE BAS SHALL SEND A LINEAR SIGNAL TO THE CHILLER MICRO-COMPUTER (CMC) TO

RESET THE PRIMARY CHILLED WATER SUPPLY TEMPERATURE SETPOINT FROM 42°F, WHEN THE CHILLED

WATER RETURN TEMPERATURE IS 58°, TO 48°F WHEN THE CHILLED WATER RETURN TEMPERATURE IS 50°F

WITH A STRAIGHT-LINE (PROPORTIONAL) RELATIONSHIP BETWEEN.

CHILLER CONTROL:

ACC-3; AHU SYSTEM; WHEN FLOW HAS BEEN PROVEN THROUGH THE CHILLER (ACC-3) BY THE FLOW SWITCH

FOR AT LEAST TWO MINUTES (ADJ), THEN THE CMC (CHILLER MICRO-COMPUTOR) SHALL STAGE THE

COMPRESSORS AND THE CONDENSER FANS TO MAINTAIN THE CHILLED WATER SUPPLY TEMPERATURE

SETPOINT. THE CMC SHALL MONITOR THE OPERATION OF THE CHILLER FOR ALL SAFETIES AND ALARMS AND

SHALL SEND A GENERIC ALARM TO THE BAS FOR ANY FAILURE/ALARM. THE AMPERAGE OF THE CHILLER

SHALL BE MEASURED BY THE BAS THE BACNET INTERFACE.

CHILLER PRIORITY:

DURING CHILLER PRIORITY, (N) ACC-3 SHALL OPERATE TO MAINTAIN THE CHILLED WATER SUPPLY

TEMPERATURE SETPOINT (42°F). WHEN THE CHILLER IS NOT CAPABLE OF MAINTAINING THE SUPPLY

TEMPERATURE SETPOINT. THEN THE MODULATING THREE-WAY VALVE LOCATED AT (E) IST-1 OUTLET SHALL

BE CONTROLLED TO MAINTAIN THE SUPPLY TEMPERATURE SETPOINT.

ICE-DISCHARGING PRIORITY:

DURING ICE-DISCHARGING PRIORITY THE MODULATING THREE-WAY VALVE LOCATED AT IST-1 OUTLET (COM

IST1 ICE MIX VLV) SHALL BE CONTROLLED TO MAINTAIN THE SUPPLY TEMPERATURE SETPOINT. WHE IST-1 IS

NOT CAPABLE OF MAINTAINING THE SUPPLY TEMPERATURE SETPOINT. THEN (N) ACC-3 STAGES SHALL BE CYCLED

TO MAINTAIN THE SUPPLY TEMPERATURE SETPOINT.

ICE-MAKING MODE:

THE TWO-POSITION THREE-WAY RELOCATED TO CWS PIPE AT IST-1 SHALL BE IN THE NORMAL POSITION.

ACC-1/OR ACC-2 SHALL PROVIDE COOLING FOR THE COMMUNICATIONS ROOMS AND THE NCC

EQUIPMENT/SIPRNET ROOMS.

THE MODULATING THREE-WAY VALVE LOCATED AT IST-1 OUTLET (COM ICE MIX VLV) SHALL BE CONTROLLED

TO PROVIDE FULL FLOW THROUGH IST-1 AND ACC-3 SHALL BE ENABLED AND CONTROLLED TO MAKE ICE.

WHEN THE CHILLED WATER RETURN TEMPERATURE REACHES 26°F (ADJUSTABLE) OR THE ICE INVENTORY IS

FULL, THEN ACC-3 SHALL BE DISABLED.

P-3A & P-3B SHALL BE DISABLED; AHU1 & AHU2 SHALL OPERATE WITHOUT CHILLED WATER COIL:

ICE-DISCHARGING MODE:

DURING THE MONTHS OF NOVEMBER THROUGH MARCH (ADJUSTABLE), ICE-DISCHARGING SHALL BE

PRIORITY AND BUILDING COOLING SHALL BE PROVIDED BY IST FOR THE COMMUNICATIONS CHILLED WATER

SYSTEM IF THE AHU'S ARE ON AIR-SIDE ECONOMIZER OR DURING UNOCCUPIED TIME PERIOD FOR AHU'S.

THIS MAY BE ASSIGNED TO OAT'S OF 55°F OR LESS. IF THE ASSIGNMENT OF ICE-DISCHARGE HAS BEEN

MADE TO THE “COMMUNICATIONS” SYSTEM AND THE OAT RISES ABOUT 55°, THEN THE ACC-3 SYSTEM

SHALL ACTUATE TO SERVE THE AHU'S COOLING DEMAND; BYPASSING THE IST. THE RELOCATED

TWO-POSITION THREE-WAY VALVE SHALL BE CONTROLLED TO BYPASS ACC-3 SYSTEM AND SHALL OPERATE

THROUGH IST-1 TO BLEND WITH COMMUNICATIONS SYSTEM CWR TO PROVIDE NECESSARY COOLING. THE

CHILLER ACC-1 AND/OR ACC SHALL OPERATE TO FURTHER REDUCE CHILLED WATER TEMPERATURE IF

NECESSARY.

DURING THE MONTHS OF MAY THROUGH SEPTEMBER (ADJUSTABLE). THE CHILLER SHALL BE “PRIORITY”

AND THE TWO-POSITION “IST” THREE-WAY VALVE SHALL BE IN THE NORMAL POSITION. ACC-3 SHALL

PROVIDE COOLING FOR AHU'S FOLLOWING AIR-SIDE ECONOMIZER MODE. ICE DISCHARGING WILL BE

UTILIZED WHEN ACC-3 CANNOT PROVIDE NECESSARY COOLING BY BLENDING CWS THROUGH “IST”.

COMMUNICATION CHILLED WATER SYSTEM (ACC-1 & ACC-2)

THIS SYSTEM SHALL WORK INDEPENDENT OF THE NEW ACC-3 “CHILLER SYSTEM”. THE SYSTEM OPERATION

IS INTENDED TO BE PRIMARY-SECONDARY PIPING SYSTEM.

THE “ICE STORAGE” WILL BECOME INCORPORATED WITH THE SYSTEM OPERATION TO EXTEND THE HOURS

OF ICE STORAGE (ENERGY SAVINGS) FUNCTION.

THE CHILLED WATER SYSTEM SHALL BE ACTUATED THROUGH THE BAS. WHENEVER THE CRAC UNITS ARE

CALLING FOR COOLING THE SYSTEM WILL BE ACTUATED. THIS IS ANTICIPATED TO BE 24/7/365.

THE SYSTEM SHALL OPERATE AS A PRIMARY-SECONDARY PUMPING SCHEME. THE PRIMARY PUMPS ARE (E)

P-1A WITH (E) P-1B STANDBY, AND (N) P-5A WITH (N) P-5B STANDBY. THE STANDBY PUMPS SHALL BE

AUTOMATICALLY ACTIVATED IF ITS CORRESPONDING PUMP FAILS WHEN CALLED FOR.

PUMP P-1A SHALL BE INTERFACED WITH CHILLER (ACC-1), WHEN FLOW IS PROVEN FOLLOWING P-1A

STARTUP ACC-1 PACKAGED CONTROLS SHALL ACTIVATE TO MAINTAIN SUPPLY WATER TEMPERATURE

SETPOINT.

PUMP-5A SHALL BE INTERFACED WITH CHILLER (ACC-2), WHEN FLOW IS PROVEN FOLLOWING P-5A STARTUP

ACC-2 PACKAGED CONTROLS SHALL ACTIVATE TO MAINTAIN SUPPLY WATER TEMPERATURE SETPOINT

THE CHILLER AND PUMPS SHALL OPERATE IN LEAD-LAG STARTUP MODE. THE FIRST CHILLER SHALL OPERATE

WHEN COOLING DEMAND IS CALLED FOR FROM THE CRAC UNITS. THE PRIMARY-PIPING LOOP “ONICON”

FLOW CONTROL STATION SHALL CYCLE THE TWO CHILLERS BASED ON FLOW DIRECTION. THE FLOW

DIRECTION SHALL PROVIDE PUMP OPERATION CYCLE TO MAINTAIN POSITIVE FLOW (MORE GPM) IN PRIMARY

SYSTEM VERSUS SECONDARY SYSTEM.

THE SECONDARY PUMPS P-6A & P-7A SHALL OPERATE WHEN THERE IS A COOLING DEMAND IN THE SECONDARY

SYSTEM CRAC UNITS.

THE PRIMARY PUMPING LOOP SHALL MAINTAIN 44°F (ADJUSTABLE) CHILLED WATER SUPPLY TEMPERATURE.

IF THE LOCKOUT PARAMETER FOR THE USE OF THE ICE STORAGE SYSTEM IS NOT OVER-RIDDEN THE

CHILLED WATER SHALL BE PRIORITIZED.

CHILLED WATER PUMP CONTROL:

THE CHILLED WATER PUMPS SHALL BE CONTROLLED TO OPERATE IN A PRIMARY/STANDBY ARRANGEMENT.

WHEN THE CHILLED WATER SYSTEM(S) ARE ENABLED, THE BAS SHALL START THE PRIMARY LEAD CHILLED

WATER PUMPS. PUMP STATUS SHALL BE PROVIDED TO THE BAS THROUGH THE CURRENT SENSORS LOCATED

AT EACH PUMP. IF THE PRIMARY PUMP FAILS TO OPERATE THE BAS SHALL STOP THE PRIMARY PUMP, START

THE STANDBY PUMP, CHANGE THE DESIGNATION OF THE STANDBY PUMP TO THE PRIMARY PUMP, AND SEND

AN ALARM. THE PRIMARY PUMP SHALL RUN UNTIL THE CHILLED WATER SYSTEM IS DISABLED AND AT LEAST

FIVE MINUTES(ADJ) AFTER THE CHILLER OPERATION HAS CEASED. PRIMARY-STANBY PUMP STATUS SHALL

ALTERNATE ON A WEEKLY BASIS.

GLYCOL FEEDER CONTROL: (EXISTING)

THE BAS SHALL MONITOR THE GLYCOL FEEDER LOW LIQUID LEVEL AND THE GLYCOL FEEDER PUMP STATUS

AND SHALL SEND AN ALARM FOR A LOW LIQUID LEVEL CONDITION.

LOW TEMPERATURE OPERATION:

WHEN OAT REACHES 40°F, CHILLER PUMPS P5A AND P1A SHALL OPERATE TO MAINTAIN FLOW THROUGH

ACC-1 AND ACC-2. TC ISOLATION VALVES SHALL OPEN.

FLUID COOLER OPERATION:

Chilled Water Mode Selection:

When outside air temperature is 32 Deg F (adj.) or below the fluid cooler primary pump will be started and fluid cooler will be enabled. When the outside air temperature is 40

Deg F (adj.) or above the fluid cooler operation will be locked out and ACC-1 and ACC-2 will be enabled.

Isolation Valve Operation:

When HX-1 CHWS temp reaches 44 Deg F (adj.) HX-1 Isolation Valve will be opened and

Chiller 1 and chiller 2 isolation valves will be closed.

Fluid Cooler Operation:

During Fluid…