2h. B730Chiller-C2910 As-Built Drawings 01-29-2020.pdf
PDF 2 MB Posted
- Solicitation number
- FA2543-22-Q-AS01
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
"Excellence is Our Standard, Customer Service is Our Passion"
Temperature Controls
Office Locations:
Rocky Mountain Region
8167 SouthPark Circle
Littleton, CO 80120
(303) 733-2300
C o v e r
S h e e t
California
1370 Reynolds Ave, Suite 103
Irvine, CA 92614
(949) 330-0673
Minnesota
1831 121 st
Street East
Burnsville, MN 55337
(800) 372-8837
Lighting Controls
Energy Management
CCTV
Access Control
System Integration
IT Services
Fire Alarm
Fire Suppression
Electrical Power Monitoring Systems
Vicinity Map
I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
Drawing
C o v e r
S h e e t d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
00-01-01
F a x
L i t t l e t o n
C o l o r a d o
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Buckley Air Force Base
BAFB Building 730 Air Stack Chiller Replacement
Buckley AFB, Colorado
Project Contractors:
Owner: Buckley AFB
General Contractor: Olgoonik Diversified Services, LLC
Project Engineered According to the Following:
1. Installation per SSC minimum installation standards or job specifications, whichever is more stringent.
2. Olgoonik Diversified Services, LLC,Purhchase Order Number 5002-254318-0015-16.16.900(S), Dated 03 May,
3. Setpoint Systems Corporation Scope of Work Letter, covering the building automation and automatic temperature control system, dated March 6, 2018, for BAFB B730 Air Stack Chiller Replacement Project, Job
#RM2018030009.
Setpoint Systems Corporation's Project Team:
Project Manager: Jon Wilson
Project Applications Engineer: Keith Johnson
Project Account Manager: Jeff Ellis
Copyright Protection for Drawings:
"The drawings, specifications and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright."
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise
AutoCAD SHX Text provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
I n d e x o f
D r a w i n g s d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
00-01-02 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Index of Drawings
I n d e x o f
D r a w i n g s
Sheet Number Format
03-01-01
Section Number
Series Number
Page Number
Drawing Number Legend
Section
Description
Cover, Symbols and Abbreviations
Campus Network
Building Network, Floor Plan
03 HVAC
04 Terminal Units
05 Misc
06 EPMS
Metering
Lighting
09 Access
10 CCTV
11 Fire Alarm
Fire Suppression
13 Schedules
14 Standard Details
Graphic Storyboard
Revised drawing sheet within existing drawing set.
This drawing set contains only those drawings affected by project C2910
Index of Drawings
Drawing # Drawing Name
00-01-01 Cover
00-01-02 Index
00-02-01 Standard Abbreviations
00-02-02
Standard Symbols
00-02-03 Standard Point Names
01-01-01
Campus Network Diagram
01-01-02
BACnet Devices and Computers
02-01-01
Building Network Diagram Page 1 of 2
02-01-02
Building Network Diagram Page 2 of 2
03-10-03 CHWS FLOW DIAGRAM
03-10-05 CHWS SYSTEM SOP
03-10-13 CP90800 Wire Chart 8
15-01-01
Graphics Storyboard
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
S t a n d a r d
A b b r e v i a t i o n s d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
00-02-01 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Standard Abbreviations
S t a n d a r d
A b b r e v i a t i o n s
NOTE: Not all Abbreviations are used in this project
Abbreviations compiled from ASHRAE FUNDAMENTALS HANDBOOK
POINT NAMING SCHEMES
LBBF SSS PPPPP MM
BUILDING LOCATION
BUILDING NAME/NUMBER
FLOOR NUMBER
SYSTEM TYPE
POINT FUNCTION
POINT FUNCTION MODIFIER
System Object Address / Point /Object Tag
DDC Device Subnet Number (Device#1 = 01)
BACnet Software Point/Object Address
DDC Device System Number (System#1 = 0100)
Hardware Address
Device Number
Point/Object Name/Descriptor
Point/Object Address
Point/Object State/Range
DEV0100
AHU1 OA DMPR
BAC.0100.AO03
0-10VDC
Control Drawing Point/Object Tag
BAC.00010101.BI1101
DDC Device Area Number (Area#1 = 0010000)
AI = Analog Input AO = Analog Output
BI = Binary Input BO = Binary Output
PI = Pulse Input
Point/Object Type
Point/Object Address Controller = XX Linknet = 1XX or 2XX eBCON (if applicable) Backplane Number eBCON (if applicable) I/O Module Number
AFF Above Finished Floor
AC Air Compressor
A/C Alternating Current
ACU Air Conditioning Unit
AD Air Dryer
AFMS Air Flow Monitoring Station
AHU Air Handling Unit
AI Analog Input
ALRM Alarm / Safety Input (suffix)
AO Analog Output
ATD Auto Tank Drain
AVE Averaging/Average
B Boiler
BI Binary Input
BO Binary Output
BOPD Break on Pressure Drop
BOPR Break on Pressure Rise
BOTD Break on Temperature Drop
BOTR Break on Temperature Rise
CAV Constant Air Volume
CFM Cubic Ft/Minute
CH Chiller
CHW Chilled Water
CHWR Chilled Water Return
CHWS Chilled Water Supply
CO Carbon Monoxide
CO2 Carbon Dioxide
COM Common
COND Condenser
CP Control Panel
CS Current Switch
CT Current Transformer
CT/CTR Cooling Tower
CU Condensing Unit
CUH Cabinet Unit Heater
CV Control Valve
CW Condenser Water
CWR Condenser Water Return
CWS Condenser Water Supply
D Damper
DA Damper Actuator (Pneumatic)
DB Dry Bulb (Temperature)
DC Direct Current
DEG F Degrees Fahrenheit
DM Damper Motor (Electric )
DPS Differential Pressure Switch
DPT Differential Pressure Transmitter
(E) Existing
EF Exhaust Fan
EP Electric Pneumatic Switch
ES End Switch
EVC Evaporative Cooling
FACP Fire Alarm Control Panel
FCU Fan Coil Unit
FLA Full Load Amps
FLT Filter
FM Flow Meter
FP Fan Powered
FS Flow Switch
FT Flow Transmitter
G Gauge
GND Ground
H Hot (Hot/Line)- voltage
HOA Hand-Off-Auto Switch
HT Humidity Transmitter
HVU Heating Ventilation Unit
HW Hot Water
HWR Hot Water Return
HWS Hot Water Supply
HX Heat Exchanger
I/P Current to Pneumatic Transducer
IAQ Indoor Air Quality
L Light
LF Line Filter
LLS Liquid Level Switch
LLT Liquid Level Transmitter
LTG Lighting Control
LTS Low Temperature Switch
MA Mixed Air
MAG Magnetic Starter
MAU Makeup Air Unit
MCC Motor Control Center
MOPD Make on Pressure Drop
MOPR Make on Pressure Rise
MOTD Make on Temperature Drop
MOTR Make on Temperature Rise
MZU Multi-Zone Unit
N Neutral (Wire) Voltage
NC Normally Closed
NO Normally Open
OA Outside Air
OL Overload
OWS Operator Work Station
P Pump
PB Push Button
PE Pressure Electric Switch
PS Proximity Switch
PRV Pressure Regulating Valve
PS Power Supply
PSW Pressure Switch
PT Pressure Transducer
R Relay
RA Return Air
RC Receiver Controller
RES Restrictor
RF Return Fan
RH Relative Humidity
RM Room
RPT Network Repeater
RTU Roof Top Unit
RV Relief Valve
SA Supply Air
SD Smoke Detector
SF Supply Fan
SRG Surge Protector
SV Solenoid Valve
SW Selector Switch
T Thermostat/Temperature
TB Terminal Block
TC Time Clock
TDR Time Delay Relay
TF Transfer Fan
THT Temperature Humidity Transmitter
TP Twisted Pair
TR Transformer
TRM Network End of Line Terminator
TS Temperature Sensor
TSP Twisted Shielded Pair
TT Temperature Transmitter
UH Unit Heater
UPS Uninterruptible Power Supply
UV Unit Ventilator
V Valve
VA Volt-Amps
VAC Volts Alternating Current
VAV Variable Air Volume
VDC Volts Direct Current
VF Ventilation Fan
VFD Variable Frequency Drive
VSW Vibration Switch
W Thermowell
WB Wet Bulb (Temperature)
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
S t a n d a r d
S y m b o l s d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
00-02-02 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Standard Symbols
S t a n d a r d
S y m b o l s
ELECTRIC VALVE
ELECTRIC VALVE
PNEUMATIC VALVE
PNEUMATIC VALVE
TEMPERATURE SENSOR
TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE
FAN/PUMP VARIABLE
MAGNETIC
LOW / HIGH LIMIT SWITCH
(SPACE/ROOM)
(IMMERSION W/ WELL)
(STRAP ON)
PNEUMATIC DAMPER
PNEUMATIC DAMPER
ELECTRIC DAMPER
ELECTRIC DAMPER
BUTTERFLY VALVE
BUTTERFLY VALVE
BUTTERFLY VALVE
BUTTERFLY VALVE
RS-485 NETWORK
RS-485 NETWORK
DUCT SMOKE
DAMPER
DAMPER
CURRENT SWITCH OR
RESTRICTOR
CONTACTS
CONTACTS
SWITCH
SWITCH
SWITCH, N.O.
SOLENOID
PRESSURE REDUCING
PANEL LIGHT
PRESSURE GAUGE
SWITCH
SWITCH
TRANSFORMER
MOTOR STARTER
TRANSDUCER
(SECURITY FLAT PLATE ROOM)
GROUND
FLOW SWITCH
TRANSDUCER/SWITCH
RELAY
C
CONTACTOR COIL
RELAY COILR
FLOW METER
DESCRIPTIONSYMBOL
DIFFERENTIAL PRESSURE
DESCRIPTIONSYMBOL
STANDARD FLOW DIAGRAM SYMBOLS
TRANSDUCER/SWITCH
FLOW METER
C
DESCRIPTIONSYMBOL
FAN
FAN
PUMP
PUMP
D
C
X
COOLING COIL
COOLING COIL
H
H
C
X
HEATING COIL
HEAT EXCHANGER
HUMIDIFIER
FILTER
AIR FLOW MONITOR
AIR FLOW MONITOR
FREQUENCY DRIVE
STARTER
PARALLEL BLADE
OPPOSED BLADE
(CENTRIFUGAL)
(PLUG)
(BASE MOUNT)
(IN-LINE)
CHILLED WATER
DIRECT EXPANSION
STEAM/HOT WATER
GAS-FIRED
STEAM INJECTION
SECTION
(RIGID)
(CAPILARY AVERAGING)
HUMIDITY SENSOR/TRANSMITTER
(POINT/TIP)
TEMPERATURE SENSOR
THERMOSTAT/TEMPERATURE
TEMPERATURE SENSOR
TEMPERATURE SENSOR
TEMPERATURE SENSOR
(SPACE/ROOM)
THERMOSTAT
(PROGRAMMABLE)
THERMOSTAT
(SPACE/ROOM)
HUMIDITY SENSOR/TRANSMITTER
SWITCH (DPS)
TRANSMITTER (DPT)
PRESSURE
TRANSMITTER (PT)
TERMINATOR
REPEATER
DETECTOR
CURRENT TRANSDUCER
(PNEUMATIC)
(PNEUMATIC)
(CURRENT TO PNEUMATIC)
(ELECTRIC / PNEUMATIC)
(VENTURI)
(PRESSURE/ELECTRIC)
(TURBINE)
(DUCT-MOUNTED)
(FAN-INLET)
END SWITCH
(DAMPER)
(2-WAY)
(3-WAY)
(2-WAY)
(3-WAY)
ACTUATOR WITH POSITIONER
ACTUATOR NO POSITIONER
ACTUATOR NO END SWITCH
ACTUATOR W/END SWITCH
ELECTRIC (2-WAY)
ELECTRIC (3-WAY)
PNEUMATIC (2-WAY)
PNEUMATIC (3-WAY)
VALVE
DESCRIPTIONSYMBOL
STANDARD WIRING DIAGRAM SYMBOLS
DESCRIPTIONSYMBOL
LIGHT
TB2
WIRING TERMINALS
Wht/Yel
Wht/Blu
Wht/Blk
Orn
Yel
Blu
120vac
10-30V
Com RIBUIC
RELAY IN A BOX
WIRING TERMINALS
DAMPER ACTUATOR
WIRING TERMINALS
VALVE ACTUATOR
Wire Color/Size
Red/18 TFF/MTW Stranded
Black/18 TFF/MTW Stranded
Blue/14 THHN Stranded
White/14 THHN Stranded
Orange/18 TFF/MTW Stranded
*Orange/Black Tracer/18 TFF/MTW Stranded
Brown/18 TFF/MTW Stranded
*Brown/White Tracer/18 TFF/MTW Stranded
Purple/14 THHN Stranded
Gray/14 THHN Stranded
24VDC Positive
24VDC Negative
24VAC Hot
24VAC Neutral
Inputs
Inputs (GND)
Outputs
Outputs (GND)
24VAC Hot Interlock
24VAC Neutral Interlock
System
Green 22TSP MS/TP & Modbus Wiring
Green CAT5 Ethernet
Signifies field wiring by SSC.
Wire colors in parenthesis (color) is the manufacturers wire color.
Black/12 THHN Stranded
White/12 THHN Stranded
120VAC Hot
120VAC Neutral
Wiring Standards
(NORMALLY OPEN)
(NORMALLY CLOSED)
(LOW TEMPERATURE)
(PRESSURE)
(MOMENTARY PB)
VALVE
(FLOW)
(DAMPER END)
OVERLOADS
DESCRIPTIONSYMBOL
MOTORMTR
Setpoint Systems Corporation
G
VFD
MAG
HIGH
LOW
DPS
LOW
HIGH
DPT
A
F
M
S
FS
R
CS
CT
TRM
RPT
I
P
E
P
P/E
G
0 30
10 20
SD
ES
DA
S
M
DA
DM
DM
A AB
NO
NC COM
B
A AB
NC COM
A AB
NO
NC COM
B
A AB
NC COM
SWITCH, N.O.
(LATCHED PB)
SWITCH, N.C.
(MOMENTARY PB)
SWITCH, N.C.
(LATCHED PB)
SWITCH, N.O.
(TOGGLE)
MTR
L2L1 L3
H A
O
M
120V
OL'S
AUX
H A
O
HAND-OFF-AUTO
SWITCH
MAGNETIC STARTER
Signifies panel wiring by SSC.
Symbols compiled from ASHRAE FUNDAMENTALS HANDBOOK
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
S t a n d a r d
P o i n t
N a m e s d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
00-02-03 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Standard Point Names
S t a n d a r d
P o i n t
N a m e s
NOTE: Not all Abbreviations are used in this project
Abbreviations compiled from ASHRAE FUNDAMENTALS HANDBOOK
POINT NAMING SCHEMES
LBBF SSS PPPPP MM
BUILDING LOCATION
BUILDING NAME/NUMBER
FLOOR NUMBER
SYSTEM TYPE
POINT FUNCTION
POINT FUNCTION MODIFIER
System Object Address / Point /Object Tag
DDC Device Subnet Number (Device#1 = 01)
BACnet Software Point/Object Address
DDC Device System Number (System#1 = 0100)
Hardware Address
Device Number
Point/Object Name/Descriptor
Point/Object Address
Point/Object State/Range
DEV0100
AHU1 OA DMPR
BAC.0100.AO03
0-10VDC
Control Drawing Point/Object Tag
BAC.00010101.BI1101
DDC Device Area Number (Area#1 = 0010000)
AI = Analog Input AO = Analog Output
BI = Binary Input BO = Binary Output
PI = Pulse Input
Point/Object Type
Point/Object Address Controller = XX Linknet = 1XX or 2XX eBCON (if applicable) Backplane Number eBCON (if applicable) I/O Module Number
AC Air Compressor
ACCU Air Cooled Cond Unit
AFMS Air Flow Monitoring Station
AHU Air Handling Unit
ALRM Alarm or Safety Input (Suffix)
AMPS Amperes
AVG Average
BLDG Building
BLR Boiler
BYP Bypass
C Coil
CAV Constant Air Volume
COND Condenser
CLG COIL Cooling Coil
CLS Closed
CFM Cubic Feet Per Minute
CH Chiller
CHW Chilled Water
CHWR Chilled Water Return
CHWS Chilled Water Supply
CLG Cooling
COMP Compressor
CO Carbon Monoxide
CO2 Carbon Dioxide
CP Circulation Pump
CRAC Computer Room AC Unit
CRAH Computer Room AHU
CS Current Switch
CT Cooling Tower
CU Condensing Unit
CUH Cabinet Unit Heater
CW Condenser Water
CWR Condenser Water Return
CWS Condenser Water Supply
DB Dry Bulb
DHWR Domestic Hot Water Return
DHWS Domestic Hot Water Supply
DIS Disable
DMPR Damper
DOM Domestic
DP Differential Pressure
DP Dew Point
DRN Drain
DX Direct Expansion
EF Exhaust Fan
ELEC Electric
EM Emergency
ENA Enable
ENT Entering
EPO Emergency Power Off
EVAP CLG Evaporative Cooling
FACP Fire Alarm Control Panel
FAN Fan
FB Face/Bypass
FCU Fan Coil Unit
FDBK Feedback
FILL Fill
FLOW Flow Rate
FLT Fault
FLTR Filter
FPB Fan Powered Box
FREQ Frequency
FUEL Fuel
FURN Furnace
GEN Generator
GLY Glycol
HRN Horn
HI High
HTR Heater
HUM Humidity
HVU Heating Ventilation Unit
HW Hot Water
HWR Hot Water Return
HWS Hot Water Supply
HX Heat Exchanger
HZ Hertz
IR Infrared
ISO Isolation
LO Low
LVG Leaving
LVL Level Switch/Sensor
LOW LIMIT Freezestat
LTG Light
LTG Light Control
MA Mixed Air
MAU Makeup Air Unit
MAX Maximum
MIN Minimum
MTN Motion
MTR Meter
NO2 Nitrous Dioxide
O2 Oxygen
OA Outside Air
OCC Occupancy/Occupied
OPN Open
OVRD Override
PH Preheat
P Pump
POS Position
PRESS Pressure
PRI Primary
RA Return Air
RF Return Fan
RH Reheat
RM Room
RTU Rooftop Air Handling Unit
SA Supply Air
SCBR Scrubber
SEC Secondary
SEN Sensor
SF Supply Fan
SLC Silence
SMK Smoke
SP Static Pressure
SPC Space
SPEED Speed
SS Start/Stop
SCR Silicone Controlled Rectifier
STG Stage
STM Steam
STS Status
START Start
STOP Stop
STPT Setpoint
SW Switch
TF Transfer Fan
TEF Toilet Exhaust Fan
TEMP Temperature
TNK Tank
UH Unit Heater
UNOC Unoccupancy/Unoccupied
VA Volt/Amps
VFD Variable Frequency Drive
VLV Valve
VP Velocity Pressure
WTR Water
WB Wet Bulb
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
C a m p u s
N e t w o r k
D i a g r a m d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
01-01-01 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Firmware Version# 3.40
Fiber Network
BACnet Network
Future
Fitness Center
Building 35
DEV100400
DEV100500
DEV100700
HQ JCC
Building 26 Solar 11
AREA: DEV100000
MAC: 00-40-ae-00-44-56
BACnet Ethernet 10001
OWS12
DEV100200
DEV100300
DEV100900
Training Center
Building 30
DEV101100
DEV101200
6th Ave Gate
Visitor Center
Building 41
DEV100800
Dorm
Building 28
DEV101000
DEV101300
MCAF Dorm
Building 205
OWS11
DEV100600
DEV101600
Sat Pharm
Building 7
OWS# 10044
OWS# Laptop
DEV100100
Mail Center
Building 207
OWS#
DEV101400
DEV101500
Fire Station
Building 806
DEV702400
DEV702500
DEV702600
DEV702700
ABW HQ
Building 606
AREA: DEV700000
MAC: 00-40-ae-02-2e-6f
BACnet Ethernet 10001
DEV702100
DEV702200
DEV702300
Medical
Building 600
DEV700700
OWS 10060
DEV701000
DEV702000
DEV703000
DEV704000
CC Chapel
Building 316
AREA: DEV800000
MAC: 00-40-ae-00-2f-d4
BACnet Ethernet 10001
OWS9
DEV803500
DEV803600
DEV803700
Youth Center
Building 350
DEV805100
DEV805200
DEV805300
Consolidated
Services (CSF)
Building 347
OWS13
DEV802700
DEV802800
DEV802900
Child
Development
Center (CDC)
Building 351
OWS14
DEV804300
DEV804400
DEV804500
COMM
Building 730
AREA: DEV900000
MAC: 00-40-AE-00-10-68
BACnet Ethernet 10001
OWS#
DEV900100
DEV900200
DEV900300
DEV900400
DEV900500
DEV900600
DEV900700
METERS
Building 841
DEV905000
SP OPS
Building 620
DEV902500
CDC
Building 725
OWS11
DEV902200
DEV902300
DEV902400
Dining
Building 630
DEV902600
DEV900100 RTR
DEV902700
JAAB
Building 1005 Solar 12
AREA: DEV500000
MAC: 00-40-ae-00-2e-d0
BACnet Ethernet 10001
DEV502000
DEV502100
DEV502200
DEV502300
CE Shops
Building 1007
OWS4
DEV502400
DEV502500
Mississippi Gate
Building B1554
DEV503000
AFOSI
Building 1550
DEV502700
Entomology Lab
Building 1019
DEV502900
Consolidated
Fuels
Building 1054
DEV501000
COANG COMM
Building 850
AREA: DEV400000
MAC: 00-40-ae-02-31-a0
BACnet Ethernet 10001
OWS#
SQ OP COANG
Building 701
DEV408000
SQ OP COANG
Building 700
DEV404000
BX
Building 1
OWS# Laptop
TRANE BCU-1
DEV403500
DEV403700
DEV403600
DEV403800
DEV403900
Civil Eng
Building 830
DEV403000
DEV403100
COANG HDQTR
Building 706
DEV402000
Tower
Building 1530
DEV401000
Alert hangars
Building 912-917
DEV405000
ANG hangar
Building 801
DEV403200
Army Hangar
Building 1510
DEV507000
Wing Headquarters
Building 1030
AREA: DEV600000
MAC: 00-40-ae-00-2d-10
BACnet Ethernet 10001
OWS6, OWS7
DEV604000
DEV604100
TRANE BCU-2
Outdoor Rec.
Facility
Building 1022
DEV600100
BRAC Security
Building 1029
DEV600200
DEV600300
Leadership Dev.
Building 1032
OWS#
DEV602000
DEV602100
DEV602200
AFR Training
Facility
Building 392
OWS#
DEV801500
DEV801600
DEV801700
DEV801800
DEV801900
ARPC
Building 390
DEV800900
DEV801000
DEV801100
DEV801200
DEV801300
DEV801400
Dorm
Building 205
CARD ACCESS
DEV4000-4900
Laptop DEV10053
Solar Array
Building 1535
DEV500300
Working Dog
Kennel
Building 1522
DEV505300
Dorm
Building 28
CARD ACCESS
DEV2000-3600
Laptop DEV10051
Vehicle Maint
Building 340
DEV703200
DEV900800
Freight Transfer
Building 1120
DEV405100
DEV405200
TLF/VQ
Building 331/332
AREA: DEV200000
MAC: 00-40-ae-00-f2-e2
BACnet Ethernet 10001
DEV202600
DEV203100
DEV203200
DEV203300
DEV203400
DEV203500
DEV203600
DEV203700
Building 1006
DEV502600
Building 1015
DEV503300
Building 1017
DEV503400
Building 1009
DEV502800
Building 1013
DEV503200
ACFT Support
Building 814
DEV406100
DEV402900
Fuel Cell
Building 800
DEV405500
Jet Engine Shop
Building 960
DEV405400
hangar
Building 909
DEV405300
SFOF
Building 1028
DEV500400
DEV500500
DEV500600
DEV500700
DEV500800
Muntitions Admin
Building 1640
DEV401100
Munitions Admin
Building 1641
DEV401200
Muntitions Admin
Building 1642
DEV401300
Weapons
Building 805
DEV404600
Alert Crew Hqtrs
Building 911
DEV4900
Medical Whse
Building 602
DEV700100
DEV700200
Army Hangar
B1000
DEV503200
Army Hangar
B1500
DEV503100
Stand Alone
Stand Alone
Fuel Storage
Building 728
DEV906000
DEV906100
Stand Alone
DEV205000 Meter
DEV205300 Meter
DEV205400 Meter
DEV205500 Meter
BAFB Air Force WAN
REVISED 6-28-2017
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
B A C n e t
D e v i c e s a n d
C o m p u t e r s d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
01-01-02 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
REVISED 06-22-2018
BACNET DEVICES and INTERFACES
Address: Building: Description:
1 BX BCU RTUS
2 B1030 BCU CHLR
3 B1032 BCU CHLR
6 B730 BCU CHLR3
7 B730 BCU CHLR2
11 B26 Veris Solar
12 B1005 Veris Solar
13 B351 Veris Elec
14 B801 Veris Elec
15 B1005 Veris Elec
16 B26 Veris Elec
17 B620 Veris Elec
18 B1054 Veris Elec
19 B1029 Veris Elec
20 B392 Veris Elec
21 B7 Veris Elec
22 B207 Veris Elec
23 B390 Veris Elec
24 B1030 Veris Elec
25 SolarArray Inverter1
26 SolarArray Inverter2
27 B350 Veris Elec
30 B701 Veris Elec
31 B331 Veris Elec
32 B340 Veris Elec
33 B1522 Veris Elec
34 B1120 Veris Elec
35 B1 BX Veris Elec
36 B1 Comm Veris Elec
37 B205 Veris Elec
38 B1510 Veris Elec
39 B1007 Veris Elec
40 B1554 Emon Energy Meter
41 B600 Veris Elec
42 B602 Veris Elec
43 B850 Veris Elec West
44 B850 Veris Elec East
45 B1500 Veris Elec
46 B1000 Veris Elec
47 B1530 Veris Elec
48 B1032 Veris Elec
49 B1022 Veris Elec
50 B909 Veris Elec
51 B960 Veris Elec
52 B700 Veris Elec
53 B800 Veris Elec
54 B841 Veris Elec North
55 B841 Veris Elec South
56 B730 Veris Elec
57 B28 Veris Elec
58 B35 Veris Elec
59 B316 Veris Elec
60 B347 Veris Elec
61 B814 Veris Elec
62 B606 Veris Elec
63 B630 Veris Elec
64 B725 Veris Elec
65 B706 Veris Elec
66 B1028 Veris Elec
67 B1642 Veris Elec
68 B1640 Veris Elec
69 B1641 Veris Elec
70 B914 Main Elec
71 B914 North Inverter
72 B806 Veris Elec
75 B806 Chiller BACnet
73 B914 South Inverter
74 B805 Veris Elec
99 B392 York Chiller
100 B392 Fieldserver
101 B390 CHLR1
102 B390 CHLR2
103 B390 CRAC1
104 B390 CRAC2
105 B390 CRAC3
106 B390 CRAC4
107 B390 CRAC5
108 B390 CRAC6
109 B390 CRAC7
110 B205 Fieldserver
200 SolarArray Fieldserver
201 B205 Fieldserver
10000 B1 BX TRANE BCU
10281 B1028 Chiller 1
10282 B1028 Chiller 2
10283 B1028 CRAC-1
10284 B1028 CRAC-2
11049 B1 BX Fire Alarm Interface
11050 B1 BX RTU-1
11051 B1 BX RTU-2
11052 B1 BX RTU-3
11053 B1 BX RTU-4
11054 B1 BX RTU-5
11055 B1 BX RTU-6
11056 B1 BX RTU-7
11057 B1 BX RTU-8
11059 B1 BX RTU-10
11068 B1 BX RTU-29
11071 B1 BX RTU-32
12062 B1 BX RTU-13
11063 B1 BX RTU-14
12064 B1 BX RTU-15
12065 B1 BX RTU-16
12072 B1 BX RTU-17
12073 B1 BX RTU-18
12066 B1 BX RTU-19
12067 B1 BX RTU-26
12069 B1 BX RTU-30
12070 B1 BX RTU-31
12000 B1 BX RTU-11
12058 B1 BX RTU-9
12061 B1 BX RTU-12
45810 B602 Trane RTU-4
45811 B392 BLR1
45812 B392 BLR2
45813 B390 BLR1
45814 B390 BLR2
45815 B28 CHLR
50015 B347 Boiler-1 BACnet
50035 B35 Boiler-3 (Master) BACnet
50036 B35 Boiler-2 BACnet
50037 B35 Boiler-1 BACnet
50075 B806 Boiler-1 BACnet
50076 B806 Boiler-2 BACnet
50081 B35 HWP-1 BACnet
50082 B35 HWP-2 BACnet
51003 B1550 CRAC-1 BACnet
51004 B1550 CRAC-2 BACnet
#### B1550 FCU-1 BACnet
#### B1550 FCU-2 BACnet
#### B1550 FCU-3 BACnet
51034 B26 AHU-2 BAcnet
51035 B26 AHU-1 BACnet
51036 B1550 AHU-1 BACnet
50110 B316 Boiler-2 BACnet
50111 B316 Boiler-1 BACnet
60100 B600 AHU-2 SF1
60200 B600 AHU-2 SF2
60300 B600 AHU-2 RF1
60400 B600 AHU-2 RF2
60500 B600 AHU-3 SF1
60600 B600 AHU-3 SF2
60700 B600 AHU-3 RF1
60800 B600 AHU-3 RF2
61002 B730 PCO Web CHLR1
61004 B730 CRAC-9
61005 B730 CRAC-10
505401 B1024 MAU-1
550098 B1028 Mammoth AHU-1
550099 B1028 Mammoth AHU-2
601024 B26 B-3 (Leader) BACnet
601025 B26 B-4 BACnet
601026 B26 B-1 (Leader) BACnet
601027 B26 B-2 BACnet
601028 B1550 Boiler-1(Leader) BACnet
601029 B1550 Boiler-2 BACnet
650030 B1032 Boiler-1
650031 B1032 Boiler-2
701001 B600 HWP-1
701002 B600 HWP-2
701003 B600 CHP-1
701004 B600 CHP-2
BAFB Computers
Address: Building: Description: IP:
DEV9900 B351 OWS14 169.254.127.119
DEV10001 B725 OWS11 131.04.136.133
DEV10007 B316 OWS9 131.04.176.61
DEV10011 B205 OWS11 131.40.160.237
DEV10012 xx Laptop HVAC Jack xx
DEV10029 xx Laptop HVAC LT6 xx
DEV10031 B1030 OWS6 2nd Floor 169.254.45.248
DEV10032 B1005 OWS1 131.04.153.215
DEV10033 B1005 OWS2 ORCAweb Server 131.04.153.199
DEV10034 B1007 OWS4 131.40.132.185
DEV10035 B1005 OWS3 131.40.153.189
DEV10036 B347 OWS13 131.40.176.199
DEV10037 B1032 OWS# 131.40.150.83
DEV10038 B433 Laptop CEITS 131.40.168.161
DEV10039 xx Laptop CSF/EMCS xx
DEV10041 B1030 OWS7 1st Floor 131.04.148.184
DEV10042 xx Laptop EMCS xx
DEV10043 B1005 OWS# xx
DEV10044 B7 OWS# xx
DEV10045 B7 OWS# Laptop xx
DEV10046 B391 OWS# xx
DEV10047 xx Laptop HVAC Shop xx
DEV10048 B730 Laptop# xx
DEV10048 B1005 ORCAweb Server xx
DEV10049 B1005 HISTORIAN xx
DEV10050 B207 OWS# xx
DEV10051 B28 Laptop# xx
DEV10053 B205 Laptop# xx
DEV10054 B392 OWS# 131.40.176.239
DEV10060 B600 OWS# 131.40.156.247
DEV10073 B350 OWS# 131.40.176.220
B430 OWS#1 131.40.168.135
B430 OWS#2 131.40.168.135
B331 OWS# 131.40.64.26
B390 OWS# 131.40.176.239
B316 OWS# 131.40.176.74
Address: Building: Description: IP:
DEV10081 B730 OWS# xx
DEVxx B26 OWS12 xx
DEVxx B1BX OWS# Laptop xx
DEVxx xx Laptop HVAC xx
BACnet Devices and Computers
B A C n e t
D e v i c e s a n d
C o m p u t e r s
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
Building Network Diagram Page 1 of 2
B u i l d i n g
N e t w o r k
D i a g r m
P g e o f
Fiber
Ethernet
RS485
Field Wiring eBUS
Since 1983
CP6
To PPP-1, PPP-2, PPP-3, PPP-4, and PPP-5
Operator Workstation (by SSC)
With OWS/Illustrator
Location to be Verified
TRM
Since 1983
CP1
DEV900144
DFM-400P
RS-485 MS/TP
OWS-1
PTR-1
Dom H2O Meter
Nat. Gas Meter
Since 1983
CP2
DEV900200
DSC-1616E
AHU-2
TRM
Since 1983
CP7
DEV900103
DFM-400P
RS-485 MS/TP
Located in Mech Rm 177 (West Wall)
DEV900300
DSC-1616E
1 2 34 75 6 8
Since 1983
CP3
E-net Switch
8-Port
AHU-1
Since 1983
CP4
Located in Mech Rm L005 (West Wall)
Since 1983
CP5
DEV900500
DSC-1616E
Underfloor
DEV900500-100
DFM-1600
Registers
Underfloor
Registers
Located in Janitor L001A
DEV900501
CRAC-4 & 5
DAC-606
DEV900302
CRAC-1, 2 & 3
DAC-606
Since 1983
CP8
Located in Mech Rm L012
DEV900602
ADM-2W704
Gate Control
Serving VAV, CRAC, CUH, and UH Controllers
DEV900102
LIGHTING
DAC-9004
Since 1983
CP6-1
DEV900603
ADM-2W704
Door Control
Since 1983
CP6-2
DEV900604
ADM-2W704
Door Control
Since 1983
CP6-3
DEV900605
ADM-2W704
Door Control
Since 1983
CP6-4
DEV900606
ADM-2W704
Door Control
Since 1983
CP6-5
DEV900607
ADM-2W704
Door Control
Since 1983
CP6-6
Since 1983
CP9
Located in Mech Rm L0900
RS-485 MS/TP
Mount at UH
Located in Elec Rm 175
DCA-1: RM 177 DCA-2: RM 177 DCA-3: RM 171N DCA-4: RM 171C DCA-5: RM 171F DCA-6: RM L012 DCA-7: RM L038
RS-485 MS/TP
CAT 5 Ethernet
CAT 5 Ethernet
DEV900104
CRAC-1
DAC-1146
CRAC-2 CRAC-3 CRAC-4
Since 1983
CP100
DEV900100
DSC-1616E
DEV900105 DEV900106 DEV900107
DAC-1146 DAC-1146 DAC-1146
Since 1983
CP10
DEV900800
DSC-1616E
CHWS
DEV900800-1
DFM-1616
CHWS
Located in Mech Rm L012
CRAC-9 CRAC-10
BACnet
Interface
BACnet
Interface
22/2 TSP MSTP
Located in CP100A
Since 1983
AREA
DEV900000
DSM-RTR
SW2 (Located inside CP100)
To BUCKnet
CHILLER-3
BACnet
Interface
Add. #61004Add. #6 Add. #61005
Since 1983
CP900145
DEV900145
DAC-606
Generator
Veris Electric Meter
Bldg kW
CHILLER-2
BACnet
Interface
Add. #7
ADD; 56
RS-485 BAUD RATE 38,400
DSC-1616E
DEV900700
HW System
DFM-1600
DEV900700-100
HW System
16-Port
E-net Switch
ASM-24E
DEV900600
Access System
ADM-2W704
DEV900601
Door Control
DSM-RTR
DEV900900
Door Control
I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
B u i l d i n g
N e t w o r k
D i a g r g e o f d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
02-01-01 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
DEV900119-DEV900142
DVC-V
DEV900143
VAV
DVC-V
DEV900118
VAV
Boiler B1
ProtoNode
DEV50112
Boiler B2
ProtoNode
DEV50113
Boiler B3
ProtoNode
DEV50114
TRM
TRM
DSC-1616E
DEV900400
Underfloor
Registers
DFM-1600
DEV900400-100
Underfloor
Registers
DFW-440
DEV900400-101
Underfloor
Registers
DAC-9004
DEV900301
UH-3
TRM
NEW BILL OF MATERIALS
ID#
QUANTITY
TAG PART DESCRIPTION MFG
29904 1 TRM 151924 TRM768 BACnet Network Terminator Delta
CHILLER-1
BACnet
Interface
Add. #8
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
SWITCH-5
AutoCAD SHX Text
TM
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
Building Network Diagram Page 2 of 2
B u i l d i n g
N e t w o r k
D i a g r g e o f
I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
B u i l d i n g
N e t w o r k
D i a g r g e o f d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
02-01-02 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
Specification Reference
15950A: 1.3.5.1.2, 2.2a
Drawing Code AF 131-20-07
M6.01
RS485
To PPP-2
PPP-1
TRM
RS485 #1
24vac #1
To All Loop #1
Controllers
Located in Mech Rm 177
(West Wall)
DEV30202
VAV-239
DVC-V322A
DEV30203
VAV-240
DVC-V322A
DEV30204
VAV-209
DVC-V322A
DEV30205
VAV-241
DVC-V322A
DEV30206
VAV-242
DVC-V322A
DEV30207
VAV-236
DVC-V322A
DEV30208
VAV-235
DVC-V322A
DEV30209
VAV-237
DVC-V322A
DEV30201
UH-2
DAC-304
RS485
From DEV30200
PPP-2
TRM
RS485 #1
24vac #1
To All Loop #1
Controllers
Located in Storage 172B
DEV30210
VAV-234
DVC-V322A
DEV30211
VAV-233
DVC-V322A
DEV30212
VAV-232
DVC-V322A
DEV30213
VAV-231
DVC-V322A
DEV30214
VAV-230
DVC-V322A
DEV30215
VAV-205
DVC-V322A
DEV30216
VAV-202
DVC-V322A
RS485 #2
24vac #2
To All Loop #2
Controllers
DEV30219
VAV-238
DVC-V322A
DEV30220
VAV-243
DVC-V322A
DEV30217
CRAC-7&8
DAC-606
RS485
To PPP-4
PPP-3
TRM
RS485 #1
24vac #1
To All Loop #1
Controllers
Located in Flight Storage
DEV30225
VAV-223
DVC-V322A
DEV30226
VAV-226
DVC-V322A
DEV30227
VAV-225
DVC-V322A
DEV30228
VAV-224
DVC-V322A
DEV30229
VAV-227
DVC-V322A
DEV30230
VAV-228
DVC-V322A
DEV30231
VAV-229
DVC-V322A
DEV30232
VAV-222
DVC-V322A
DEV30233
VAV-221
DVC-V322A
173J
RS485
To PPP-5
PPP-4
TRM
RS485 #1
24vac #1
To All Loop #1
Controllers
Located in Storage 172B
DEV30235
VAV-213
DVC-V322A
DEV30236
VAV-214
DVC-V322A
DEV30237
VAV-215
DVC-V322A
DEV30238
VAV-216
DVC-V322A
DEV30240
VAV-218
DVC-V322A
DEV30241
VAV-217
DVC-V322A
RS485 #2
24vac #2
To All Loop #2
Controllers
DEV30242
VAV-219
DVC-V322A
DEV30239
CH-2
DAC-304
RS485 #3
24vac #3
To All Loop #3
Controllers
DEV30251
VAV-203
DVC-V322A
DEV30252
VAV-204
DVC-V322A
DEV30250
CRAC-6
DAC-606
DEV30243
VAV-212
DVC-V322A
DEV30244
VAV-208
DVC-V322A
DEV30246
VAV-211
DVC-V322A
DEV30247
VAV-210
DVC-V322A
DEV30248
VAV-206
DVC-V322A
DEV30249
VAV-207
DVC-V322A
DEV30245
CH-1
DAC-304
DEV30253
VAV-220
DVC-V322A
DEV30254
UH-1
DAC-304
DEV30221
VAV-E01
DVC-V322A
DEV30222
VAV-EO4
DVC-V322A
DEV30223
VAV-EO3
DVC-V322A
DEV30224
VAV-EO2
DVC-V322A
RS485
From PPP-4
PPP-5
TRM RS485 #1
24vac #1
To All Loop #1
Controllers
Located in Storage 172B
DEV30255
VAV-C05
DVC-V322A
DEV30256
VAV-C06
DVC-V322A
DEV30257
VAV-C07
DVC-V322A
DEV30258
VAV-C08
DVC-V322A
DEV30259
VAV-C10
DVC-V322A
DEV30260
VAV-C09
DVC-V322A
RS485
From PPP-1
RS485
From PPP-2
RS485
From PPP-3
RS485
From DEV30200
RPT=DEV30234
Since 1983
CP11
Since 1983
CP10
Mount at UH
Mount in CH
Mount at UH
Mount in CH
RS-485 Comm Trunk
From DEV30200 (DSC)
Located in Mech Rm 177
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise
AutoCAD SHX Text provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
AutoCAD SHX Text
LO
AutoCAD SHX Text
RPT
AutoCAD SHX Text
TM
AutoCAD SHX Text
TM
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
AutoCAD SHX Text
LO
LO
CRAC-3
30 GPM
15 TONS
CRAC-2
30 GPM
15 TONS
CRAC-1
30 GPM
15 TONS
CRAC-5
8.5 GPM
4.2 TONS
CRAC-4
12.5 GPM
6.2 TONS
CRAC-7
7.5 GPM
3.6 TONS
CRAC-6
8.5 GPM
4.2 TONS
CRAC-8
7.5 GPM
3.6 TONS
AIR COOLED
CHILLER
ACC-2
AHU-2
78 GPM
45.5 TONS
AHU-1
61 GPM
35.6 TONS
60 TONS
CP90800
COM P-1A SS
BAC.90800.BO08
D.A. = ON
CP90800
COM P-1A STATUS
BAC.90800.BI115
D.A. = ON
CP90800
COM P-1B SS
BAC.90800.BO09
D.A. = ON
CP90800
COM P-1B STATUS
BAC.90800.BI116
D.A. = ON
P-1B
P-1A
AIR COOLED
CHILLER
ACC-1
AIR COOLED
CHILLER
ACC-3
DEV90800
COM CCWR TEMP
BAC.90800.AI102
4-20mA/ 32-95°F
DEV90800
COM CCWS TEMP
BAC.90800.AI101
4-20mA/ 32-95°F
TT 02-01
CP90800
COM ISBP VLV
BAC.90800.AO02
0-10V DC
Chiller BacNet Interface is provided by Equipment Mfgr.
The Following points will be mapped to the DDC Central Workstation:
1. Chiller Enable
2. Chiller Leaving Water Temperature Set Point
3. Chiller General Alarm
4. Chiller Run Status
5. Compressor Operating Current (Amps)
6. operating Voltage
7. Chiller Water Flow Status
All the Above Listed Points Are to be Provided by the Chiller Control Panel.
CP90800
COM CWP-3A SS
BAC.90800.BO12
D.A. = ON
CP90800
COM CWP-3A STATUS
BAC.90800.BI111
D.A. = ON
CP90800
COM CWP-3B SS
BAC.90800.BO13
D.A. = ON
CP90800
COM CWP-3B STATUS
BAC.90800.BI112
D.A. = ON
P-3BP-3A
TT 02-06
TT 02-03
CP90800
COM 2CWS TEMP
BAC.90800.AI105
4-20mA/ -58-122°F
CP90800
COM 2CWR TEMP
BAC.90800.AI106
4-20mA/ -58-122°F
CP90800
COM CWS MIX VLV
BAC.90800.AO04
0-10V DC
CP90800
COM P-2B SS
BAC.90800.BO11
D.A. = ON
CP90800
COM P-2B STATUS
BAC.90800.BI113
D.A. = ON
P-2B
CP90800
COM P-2A SS
BAC.90800.BO10
D.A. = ON
CP90800
COM P-2B STATUS
BAC.90800.BI114
D.A. = ON
P-2A
TT 02-04
TT 02-05
CP90800
COM PCWR TEMP
BAC.90800.AI04
4-20 mA/ 32-212°F
CP90800
COM PCWS TEMP
BAC.90800.AI03
4-20mA/ 32-212°F
ICE STORAGE TANK
ST-1
CP90800
COM IST1 LEVEL
BAC.90800.AI07
4-20mA/0-6"
CP90800
COM CW GLYCOL LOW
BAC.90800.BI109
D.A. = Alarm
CP90800
COM CW GFP STATUS
BAC.90800.BI110
D.A. = ON
P-5B
P-5A
P-6B
P-6A
P-6B
P-7A
CRAC-9
60 GPM
20 TONS
CRAC-10
60 GPM
20 TONS
CP90800
COM P-5B SS
BAC.90800.BO15
D.A. = ON
CP90800
COM P-5B STATUS
BAC.90800.BI15
D.A. = ON
CP90800
COM P-5A SS
BAC.90800.BO14
D.A. = ON
CP90800
COM P-5A STATUS
BAC.90800.BI14
D.A. = ON
CP90800
COM P-6A SS
BAC.90800.BO101
D.A. = ON
CP90800
COM P-6A VFD SPD
BAC.90800.AO105
0-10VDC
CP90800
COM P-6A STATUS
BAC.90800.BI10
D.A. = ON
CP90800
COM P-7A SS
BAC.90800.BO103
D.A. = ON
CP90800
COM P-7A VFD SPD
BAC.90800.AO107
0-10VDC
CP90800
COM P-7A STATUS
BAC.90800.BI12
D.A. = ON
CP90800
COM P-6B SS
BAC.90800.BO102
D.A. = ON
CP90800
COM P-6B VFD SPD
BAC.90800.AO106
0-10VDC
CP90800
COM P-6B STATUS
BAC.90800.BI11
D.A. = ON
CP90800
COM P-7B SS
BAC.90800.BO104
D.A. = ON
CP90800
COM P-7B VFD SPD
BAC.90800.AO108
0-10VDC
CP90800
COM P-7B STATUS
BAC.90800.BI13
D.A. = ON
CP90800
COM CHWS LOOP GPM
BAC.90800.AI16
4-20mA=0-400 GPM
TT 02-02
DEV90800
COM CH3 CWS ISOV
BAC.90800.BO06
DA=OPEN
DEV90800
COM CH1 CWS ISOV
BAC.90800.BO05
DA=OPEN
FS 02-01
FS 02-02
CP90800
COM CH1 AMPS
BAC.90800.AI05
DA=AMPS
CS-STD
R
RIB-10A
R
RIB-10A
CS-STD
R
RIB-10A
R
RIB-10A
CS-STD
R
RIB-10A
R
RIB-10A
R
RIB-10A
CS-STD
CS-STD
R
RIB-10A
Onicon Flow Meter
HI
LO
DEV100
COM P6 LOOP DP
BAC.100.AI08
4-20mA=0-60PSI
HI
LO
DEV100
COM P7 LOOP DP
BAC.100.AI09
4-20mA=0-60PSI
CS-STD
BILL OF MATERIALS
ID#
QUANTITY
TAG PART DESCRIPTION TYPE
72046 6 CS-STD H600 Split Core Adjustable Current Switch, LED Field
29658 2 DPT3 W30-35E-3VLV 0-60 PSID DIFF PRESS TRANS W/ BYPASS
FIELD
30765 8 RIB-10A RIBU1C
Enclosed 10A SPDT Relay 10VDC
FIELD
CHWS FLOW DIAGRAM
C H
W S
F L O
W
D
I A G
R A M
I n t e r n e t h t t p w w w s e t p o i n t s y s t e m s c o m
S i t e
N a m e
F i l e
N a m e
S i t e
L o c a t i o n
C H
W S
F L O
W
D
I A G
R A M d w g
S h e e t
T i t l e
R e v
D a t e
D e s c r i p t i o n
P M
A E
J o b
03-10-03 x
L i t t l e t o n
C o l o r a
S o u t h P a r k
C i r c l e
B A F B
B u i l d i n g
B u c k l e y
A F B
C o l o r a d o
C
B A F B
B
F r e e
C o o l i n g
J W
K J
C
B A F B
B
A i r
S t a c k
C h i l l e r
R e p l a c e m e n t
A s B u i l t
D r a w i n g s
J W
K J
See CHWS Flow
Diagram Part 2 for Continuation
DEV90800
COM HX-1 CHWR ISO VLV
BAC.90800.BO07
DA=OPEN
Chiller BacNet Interface is provided by Equipment Mfgr.
The Following points will be mapped to the DDC Central Workstation:
1. Chiller Enable
2. Chiller Leaving Water Temperature Set Point
3. Chiller General Alarm
4. Chiller Run Status
5. Compressor Operating Current (Amps)
6. operating Voltage
7. Chiller Water Flow Status
All the Above Listed Points Are to be Provided by the Chiller Control Panel.
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS(CWR ICE)
AutoCAD SHX Text
CWR(CWS ICE)
AutoCAD SHX Text
CWS(CWR ICE)
AutoCAD SHX Text
CWR(CWS ICE)
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
CWS(CWR ICE)
AutoCAD SHX Text
CWR(CWS ICE)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DPT3
AutoCAD SHX Text
DPT3
AutoCAD SHX Text Copyright Protection For Drawings
AutoCAD SHX Text "The drawings, specifications, and other documents prepared by Setpoint Systems Corporation for this project are instruments of Setpoint Systems Corporation's service for use solely with respect to this project, and unless otherwise provided, Setpoint Systems Corporation shall be deemed the author of these documents and shall retain all common law, statutory, and other reserved rights, including the copyright."
CHILLED WATER SYSTEM SEQUENCE OF OPERATION:
THE CHILLED WATER SYSTEM SHALL PROVIDE COOLING FOR THE ENTIRE FACILITY. THE OVERALL BUILDING
COOLING LOAD WILL BE SEPARATED INTO TWO INTERFACED SYSTEMS. THESE SYSTEMS WILL SERVE THE
FOLLOWING DISTINCT LOADS: UPPER LEVEL (VAV AIR HANDLING SYSTEM - AHU -2), LOWER LEVER
(UNDERFLOOR VAV AIR HANDLING SYSTEM - AHU -1); (CRAC-4, 5, 6, 7, & 8); (CRAC-1, 2, & 3), AND NEW
COMMUNICATION ROOM (CRAC 9 &10, WITH PROVISION FOR (F) CRAC 11 & 12).
UPPER LEVEL COOLING IS PROVIDED DURING THE OCCUPIED MODE BY THE AIRSIDE ECONOMIZER CYCLE
AND THE ACC3 CHILLED WATER SYSTEM. COOLING REQUIRED IN THE UNOCCUPIED MODE IS PROVIDED BY
THE ECONOMIZER CYCLE. THE OCCUPIED MODE IS 7:00 AM TO 5:00 AM (ADJUSTABLE) SEVEN DAYS PER
WEEK, 365 DAYS PER YEAR.
LOWER LEVEL COOLING IS PROVIDED DUR08ING THE ICE-DISCHARGING MODE BY AHU-1 ECONOMIZER
CYCLE AND THE CHILLED WATER SYSTEM. AHU-1 COOLING REQUIRED IN THE ICE-MAKING MODE IS
PROVIDED BY THE AHU-1 AIRSIDE ECONOMIZER CYCLE IN SEQUENCE WITH THE WATER-SIDE ECONOMIZER
USING THE ICE-STORAGE SYSTEM. THE OCCUPIED MODE IS 24 HOURS PER DAY SEVEN DAYS A WEEK.
COMMUNICATIONS ROOM COOLING IS PROVIDED BY THE CHILLED WATER SYSTEM SERVED FROM ACC1 &
ACC2. THE OCCUPIED MODE IS 24 HOURS PER DAY SEVEN DAYS PER WEEK.
NCC EQUIPMENT & SIPRNET ROOMS ARE PROVIDED BY THE CHILLED WATER SYSTEM. THE OCCUPED MODE IS
24 HOURS PER DAY SEVEN DAYS PER WEEK. THE FOLLOWING EXISTING HVAC EQUIPMENT SERVING THESE
ROOMS IS SERVED BY BACKUP POWER THROUGH THE EMERGENCY GENERATOR INCLUDING; ACC-2, P-1A, CRAC-1, CRAC-2 & CRAC-3.
THE NEW COMMUNICATION ROOM CHILLED WATER SYSTEM WILL BE PROVIDED WITH EMERGENCY POWER
SOURCES TO ENABLE ACC-1, P-5A, P-6A, & P-7A, CRAC-9 & 10.
CHILLED WATER SYSTEM CONTOL:
THE (E) BAS MONITORS THE CHILLED WATER SUPPLY AND RETURN TEMPERATURES, AND SHALL SEND AN
ALARM IF THE CHILLED WATER SUPPLY TEMPERATURE IS ABOVE 50°F (ADJ). THIS SHALL BE EXPANDED TO
ALL 3 CHILLERS. THE BAS SHALL SEND A LINEAR SIGNAL TO THE CHILLER MICRO-COMPUTER (CMC) TO
RESET THE PRIMARY CHILLED WATER SUPPLY TEMPERATURE SETPOINT FROM 42°F, WHEN THE CHILLED
WATER RETURN TEMPERATURE IS 58°, TO 48°F WHEN THE CHILLED WATER RETURN TEMPERATURE IS 50°F
WITH A STRAIGHT-LINE (PROPORTIONAL) RELATIONSHIP BETWEEN.
CHILLER CONTROL:
ACC-3; AHU SYSTEM; WHEN FLOW HAS BEEN PROVEN THROUGH THE CHILLER (ACC-3) BY THE FLOW SWITCH
FOR AT LEAST TWO MINUTES (ADJ), THEN THE CMC (CHILLER MICRO-COMPUTOR) SHALL STAGE THE
COMPRESSORS AND THE CONDENSER FANS TO MAINTAIN THE CHILLED WATER SUPPLY TEMPERATURE
SETPOINT. THE CMC SHALL MONITOR THE OPERATION OF THE CHILLER FOR ALL SAFETIES AND ALARMS AND
SHALL SEND A GENERIC ALARM TO THE BAS FOR ANY FAILURE/ALARM. THE AMPERAGE OF THE CHILLER
SHALL BE MEASURED BY THE BAS THE BACNET INTERFACE.
CHILLER PRIORITY:
DURING CHILLER PRIORITY, (N) ACC-3 SHALL OPERATE TO MAINTAIN THE CHILLED WATER SUPPLY
TEMPERATURE SETPOINT (42°F). WHEN THE CHILLER IS NOT CAPABLE OF MAINTAINING THE SUPPLY
TEMPERATURE SETPOINT. THEN THE MODULATING THREE-WAY VALVE LOCATED AT (E) IST-1 OUTLET SHALL
BE CONTROLLED TO MAINTAIN THE SUPPLY TEMPERATURE SETPOINT.
ICE-DISCHARGING PRIORITY:
DURING ICE-DISCHARGING PRIORITY THE MODULATING THREE-WAY VALVE LOCATED AT IST-1 OUTLET (COM
IST1 ICE MIX VLV) SHALL BE CONTROLLED TO MAINTAIN THE SUPPLY TEMPERATURE SETPOINT. WHE IST-1 IS
NOT CAPABLE OF MAINTAINING THE SUPPLY TEMPERATURE SETPOINT. THEN (N) ACC-3 STAGES SHALL BE CYCLED
TO MAINTAIN THE SUPPLY TEMPERATURE SETPOINT.
ICE-MAKING MODE:
THE TWO-POSITION THREE-WAY RELOCATED TO CWS PIPE AT IST-1 SHALL BE IN THE NORMAL POSITION.
ACC-1/OR ACC-2 SHALL PROVIDE COOLING FOR THE COMMUNICATIONS ROOMS AND THE NCC
EQUIPMENT/SIPRNET ROOMS.
THE MODULATING THREE-WAY VALVE LOCATED AT IST-1 OUTLET (COM ICE MIX VLV) SHALL BE CONTROLLED
TO PROVIDE FULL FLOW THROUGH IST-1 AND ACC-3 SHALL BE ENABLED AND CONTROLLED TO MAKE ICE.
WHEN THE CHILLED WATER RETURN TEMPERATURE REACHES 26°F (ADJUSTABLE) OR THE ICE INVENTORY IS
FULL, THEN ACC-3 SHALL BE DISABLED.
P-3A & P-3B SHALL BE DISABLED; AHU1 & AHU2 SHALL OPERATE WITHOUT CHILLED WATER COIL:
ICE-DISCHARGING MODE:
DURING THE MONTHS OF NOVEMBER THROUGH MARCH (ADJUSTABLE), ICE-DISCHARGING SHALL BE
PRIORITY AND BUILDING COOLING SHALL BE PROVIDED BY IST FOR THE COMMUNICATIONS CHILLED WATER
SYSTEM IF THE AHU'S ARE ON AIR-SIDE ECONOMIZER OR DURING UNOCCUPIED TIME PERIOD FOR AHU'S.
THIS MAY BE ASSIGNED TO OAT'S OF 55°F OR LESS. IF THE ASSIGNMENT OF ICE-DISCHARGE HAS BEEN
MADE TO THE “COMMUNICATIONS” SYSTEM AND THE OAT RISES ABOUT 55°, THEN THE ACC-3 SYSTEM
SHALL ACTUATE TO SERVE THE AHU'S COOLING DEMAND; BYPASSING THE IST. THE RELOCATED
TWO-POSITION THREE-WAY VALVE SHALL BE CONTROLLED TO BYPASS ACC-3 SYSTEM AND SHALL OPERATE
THROUGH IST-1 TO BLEND WITH COMMUNICATIONS SYSTEM CWR TO PROVIDE NECESSARY COOLING. THE
CHILLER ACC-1 AND/OR ACC SHALL OPERATE TO FURTHER REDUCE CHILLED WATER TEMPERATURE IF
NECESSARY.
DURING THE MONTHS OF MAY THROUGH SEPTEMBER (ADJUSTABLE). THE CHILLER SHALL BE “PRIORITY”
AND THE TWO-POSITION “IST” THREE-WAY VALVE SHALL BE IN THE NORMAL POSITION. ACC-3 SHALL
PROVIDE COOLING FOR AHU'S FOLLOWING AIR-SIDE ECONOMIZER MODE. ICE DISCHARGING WILL BE
UTILIZED WHEN ACC-3 CANNOT PROVIDE NECESSARY COOLING BY BLENDING CWS THROUGH “IST”.
COMMUNICATION CHILLED WATER SYSTEM (ACC-1 & ACC-2)
THIS SYSTEM SHALL WORK INDEPENDENT OF THE NEW ACC-3 “CHILLER SYSTEM”. THE SYSTEM OPERATION
IS INTENDED TO BE PRIMARY-SECONDARY PIPING SYSTEM.
THE “ICE STORAGE” WILL BECOME INCORPORATED WITH THE SYSTEM OPERATION TO EXTEND THE HOURS
OF ICE STORAGE (ENERGY SAVINGS) FUNCTION.
THE CHILLED WATER SYSTEM SHALL BE ACTUATED THROUGH THE BAS. WHENEVER THE CRAC UNITS ARE
CALLING FOR COOLING THE SYSTEM WILL BE ACTUATED. THIS IS ANTICIPATED TO BE 24/7/365.
THE SYSTEM SHALL OPERATE AS A PRIMARY-SECONDARY PUMPING SCHEME. THE PRIMARY PUMPS ARE (E)
P-1A WITH (E) P-1B STANDBY, AND (N) P-5A WITH (N) P-5B STANDBY. THE STANDBY PUMPS SHALL BE
AUTOMATICALLY ACTIVATED IF ITS CORRESPONDING PUMP FAILS WHEN CALLED FOR.
PUMP P-1A SHALL BE INTERFACED WITH CHILLER (ACC-1), WHEN FLOW IS PROVEN FOLLOWING P-1A
STARTUP ACC-1 PACKAGED CONTROLS SHALL ACTIVATE TO MAINTAIN SUPPLY WATER TEMPERATURE
SETPOINT.
PUMP-5A SHALL BE INTERFACED WITH CHILLER (ACC-2), WHEN FLOW IS PROVEN FOLLOWING P-5A STARTUP
ACC-2 PACKAGED CONTROLS SHALL ACTIVATE TO MAINTAIN SUPPLY WATER TEMPERATURE SETPOINT
THE CHILLER AND PUMPS SHALL OPERATE IN LEAD-LAG STARTUP MODE. THE FIRST CHILLER SHALL OPERATE
WHEN COOLING DEMAND IS CALLED FOR FROM THE CRAC UNITS. THE PRIMARY-PIPING LOOP “ONICON”
FLOW CONTROL STATION SHALL CYCLE THE TWO CHILLERS BASED ON FLOW DIRECTION. THE FLOW
DIRECTION SHALL PROVIDE PUMP OPERATION CYCLE TO MAINTAIN POSITIVE FLOW (MORE GPM) IN PRIMARY
SYSTEM VERSUS SECONDARY SYSTEM.
THE SECONDARY PUMPS P-6A & P-7A SHALL OPERATE WHEN THERE IS A COOLING DEMAND IN THE SECONDARY
SYSTEM CRAC UNITS.
THE PRIMARY PUMPING LOOP SHALL MAINTAIN 44°F (ADJUSTABLE) CHILLED WATER SUPPLY TEMPERATURE.
IF THE LOCKOUT PARAMETER FOR THE USE OF THE ICE STORAGE SYSTEM IS NOT OVER-RIDDEN THE
CHILLED WATER SHALL BE PRIORITIZED.
CHILLED WATER PUMP CONTROL:
THE CHILLED WATER PUMPS SHALL BE CONTROLLED TO OPERATE IN A PRIMARY/STANDBY ARRANGEMENT.
WHEN THE CHILLED WATER SYSTEM(S) ARE ENABLED, THE BAS SHALL START THE PRIMARY LEAD CHILLED
WATER PUMPS. PUMP STATUS SHALL BE PROVIDED TO THE BAS THROUGH THE CURRENT SENSORS LOCATED
AT EACH PUMP. IF THE PRIMARY PUMP FAILS TO OPERATE THE BAS SHALL STOP THE PRIMARY PUMP, START
THE STANDBY PUMP, CHANGE THE DESIGNATION OF THE STANDBY PUMP TO THE PRIMARY PUMP, AND SEND
AN ALARM. THE PRIMARY PUMP SHALL RUN UNTIL THE CHILLED WATER SYSTEM IS DISABLED AND AT LEAST
FIVE MINUTES(ADJ) AFTER THE CHILLER OPERATION HAS CEASED. PRIMARY-STANBY PUMP STATUS SHALL
ALTERNATE ON A WEEKLY BASIS.
GLYCOL FEEDER CONTROL: (EXISTING)
THE BAS SHALL MONITOR THE GLYCOL FEEDER LOW LIQUID LEVEL AND THE GLYCOL FEEDER PUMP STATUS
AND SHALL SEND AN ALARM FOR A LOW LIQUID LEVEL CONDITION.
LOW TEMPERATURE OPERATION:
WHEN OAT REACHES 40°F, CHILLER PUMPS P5A AND P1A SHALL OPERATE TO MAINTAIN FLOW THROUGH
ACC-1 AND ACC-2. TC ISOLATION VALVES SHALL OPEN.
FLUID COOLER OPERATION:
Chilled Water Mode Selection:
When outside air temperature is 32 Deg F (adj.) or below the fluid cooler primary pump will be started and fluid cooler will be enabled. When the outside air temperature is 40
Deg F (adj.) or above the fluid cooler operation will be locked out and ACC-1 and ACC-2 will be enabled.
Isolation Valve Operation:
When HX-1 CHWS temp reaches 44 Deg F (adj.) HX-1 Isolation Valve will be opened and
Chiller 1 and chiller 2 isolation valves will be closed.
Fluid Cooler Operation:
During Fluid…