Atch 7.2 22B0017 - Controls.pdf
PDF 524 KB Posted
- Attached to
- Replace SAB HVAC Federal contract opportunity
- Solicitation number
- FA252122B0017
About this file
This document package includes control drawings and specifications for replacing the HVAC system at a Satellite Assembly Building, as well as the related federal contract opportunity solicitation.
The control drawings provide details on the HVAC system architecture, wiring diagrams for air handling units, chilled water system diagrams, and VAV terminal unit layout. The project involves replacing six Metasys controllers with EMCS controllers on various air handlers and VAV boxes. A new chiller and split system mini-split units will also be installed. Controls modifications include installing temperature and humidity sensors, and reprogramming VAV damper and heating controls.
The related federal contract opportunity is a solicitation to replace the SAB HVAC system at Cape Canaveral Air Force Station. The work includes duct and insulation repairs, installing two-ton mini-split systems, and replacing controllers on air handlers, VAV boxes, and the building automation system with EMCS products. The solicitation is issued by the Department of the Air Force Space Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 22B0017 Abstract signed.pdf | ||
| Atch 7.1a 22B0017 - Updated RFI Answers.pdf | ||
| Solicitation Amendment FA252122B00170003 SF 30.pdf | ||
| Atch 8.1- Temp Chiller Hookup 1.pdf | ||
| Atch 8.1a - Temp Chiller Hookup 2.pdf | ||
| Atch 7.1 22B0017 - RFI Answers.pdf | ||
| Solicitation Amend FA252122B00170002 SF 30.pdf | ||
| Atch 1 - SOW SAB HVAC dated 22 August 2022.pdf | ||
| Solicitation Amendment FA252122B00170001 SF 30.pdf | ||
| Atch 5 - ODS Statement.pdf | ||
| Atch 3 - Green Procurement Form.pdf | ||
| Atch 1 - SOW SAB HVAC.pdf | ||
| Atch 2 - Wage Determination (FL20220001).pdf | ||
| Atch 6 - BLANK BADGE Request -2 pages.pdf | ||
| Atch 4 - AP Statement.pdf | ||
| Atch 7 - RFI Question and Answer Template.docx | DOCX document | |
| Solicitation - FA252122B0017.pdf | ||
| Atch 8 - Chillers and UPS Photos.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Title Page
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
4/4/17
Revision History
A
B
C
DOACS Bronson Lab Bldg 100
2700 N. John Young Pkwy
Kissimmee, FL 34741
Satellite Assembly Building
Replace HVAC
HVAC Control Drawings
2459 Cheney Hwy, Suite 100
Titusville, Fl 32780
(407) 739-9562
Prepared by:
Facility Integration Solutions, Inc.
Drawing Index:
Sheet No. Description
1 Title Sheet
2 System Architecture
3 AHU-1 & 6 Control Details
4 AHU-10 Control Details
5 AHU-11 & 12 Control Details
6 CHW System Details
7 CHW System Panel Details
8 VAV Control Details
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FL
Chg’d Valve Sch 5/17/17
System Architecture
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM 4/4/17
Revision History
A
ECB-VAVs
VAV-1
ECB-VAVs
VAV-2
ECB-VAVs
VAV-3
ECB-VAVs
VAV-4
ECB-VAVs
VAV-5
ECB-VAVs
VAV-6
Daisy-chain Bacnet comm cable through all controllers shown below. No splices or T-Taps.
DOACS Bronson Lab Bldg 100
2700 N. John Young Pkwy
Kissimmee, FL 34741
Bill of Materials
Item Quan. Part Number Description
NM 1 TNM-6 Web-server/Network Manager with Bacnet and Memory Expansion
JACE-6
System Interface
Comm Rm
Customer
Network
System Access
Customer PC or
Notebook
Ethernet
Ethernet
ECB-VAVs
VAV-7
ECB-VAVs
VAV-8
ECB-VAVs
VAV-9
ECB-VAVs
VAV-10
ECB-VAVs
VAV-11
ECB-350
CEP
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FL
Existing JCI
FEC2621
AHU-1
Existing JCI
FEC2621
AHU-6
Existing JCI
FEC2621
AHU-10
Existing JCI
FEC2621
AHU-11
Existing JCI
FEC2621
AHU-12
New Trane 80T
Scroll Chiller
AHU-1 & 6 Wiring Detail
DOACS Bronson Lab Bldg 100
2700 N. John Young Pkwy
Kissimmee, FL 34741
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
AHU-1 & 6
O A
D a m p e r
OA
CHWSCHWR
R A
T e m p
D A
T e m p
C H
W V a lv e
CV1
E D
H S ta g e
4/4/17
DH-1
Revision History
A
B
C
M A
T e m p
R
IB
U
C C
R
IB
U
C C
E D
H S ta g e
C 1 2
VFD
S u p p ly F a n
S ta tu s
S F
E n a b le
SA
R
IB
U
C C
C C
L A
T e m p
RA
R o o m
T e m p /H u m id it y
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FLWiring to existing JCI FEC2621 controller
CV6
SEQUENCE OF OPERATION - AHUs 1 & 6
Occupied Mode The supply fan will be soft-started automatically and operate continually at 60 Hz with the outdoor air dampers opened to minimum position whenever the system is indexed to this mode, subject to the safeties.
Chilled Water/EDH The chiller water valve will be modulated to maintain 55F supply air temp to the associated VAV boxes. In the case that the high bay temp drops below the heating set point, the CHWV and EDH will be modulated to maintain the high bay heating set point.
Supply Air Reset The supply temperature controller’s setpoint will be reset inversely to the change in space temperature over a predetermined schedule. The supply air temperature controller will modulate the cooling valve sequentially to control space temperature at an adjustable setpoint.
Unoccupied Mode The supply fan will be cycled on and off by the space temperature controller with the outdoor air dampers in full closed position.
The cooling command and the heating command will be modulated on demand whenever the system is indexed to this mode.
Note:
Denotes items specifically not furnished by
FIS, Inc.
Room temp/humidity sensor
AHU-10 Wiring Details
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
4/4/17
Revision History
A
Facility Integration Solutions, Inc.
F S
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
DOACS Bronson Lab Bldg 100
2700 N. John Young Pkwy
Kissimmee, FL 34741
SEQUENCE OF OPERATION - AHU 10
Occupied Mode The supply fan will be soft-started automatically and operate continually at 60 Hz with the outdoor air dampers opened to minimum position whenever the system is indexed to this mode, subject to the safeties.
Supply Air Reset The supply temperature controller’s setpoint will be reset inversely to the change in space temperature over a predetermined schedule. The supply air temperature controller will modulate the cooling valve sequentially to control space temperature at an adjustable setpoint.
Unoccupied Mode The supply fan will be cycled on and off by the space temperature controller with the outdoor air dampers in full closed position. The cooling command and the heating command will be modulated on demand whenever the system is indexed to this mode.
RA
CHWSCHWR
D A
T e m p
C H
W V a lv e
CV10
R A
T e m p
VFD
S u p p ly F a n
S ta tu s
S F
E n a b le
SA
R
IB
U
C C
C C
L A
T e m p
R o o m
T e m p /H u m id it y
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FLWiring to existing JCI FEC2621 controller
Room temp/humidity
AHU-11 & 12 Wiring Detail
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
4/4/17
Revision History
A
DOACS Bronson Lab Bldg 100
2700 N. John Young Pkwy
Kissimmee, FL 34741
AHU-11 & 12
RA
CHWSCHWR
D A
T e m p
C H
W V a lv e
CV11
E D
H S ta g e
DH-1
R A
T e m p
R
IB
U
C C
R
IB
U
C C
E D
H S ta g e
C 1 2
VFD
S u p p ly F a n
S ta tu s
S F
E n a b le
SA
R
IB
U
C C
C C
L A
T e m p
R o o m
T e m p /H u m id it y
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FL
SEQUENCE OF OPERATION - AHUs 11 & 12
Occupied Mode The supply fan will be soft-started automatically and operate continually at 60 Hz with the outdoor air dampers opened to minimum position whenever the system is indexed to this mode, subject to the safeties.
Supply Air Reset The supply temperature controller’s setpoint will be reset inversely to the change in space temperature over a predetermined schedule. The supply air temperature controller will modulate the cooling valve sequentially to control space temperature at an adjustable setpoint.
Unoccupied Mode The supply fan will be cycled on and off by the space temperature controller with the outdoor air dampers in full closed position. The cooling command and the heating command will be modulated on demand whenever the system is indexed to this mode.
Wiring to existing JCI FEC2621 controller
CV12
Room temp/humidity
Chilled Water System Detail
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
C H
W R
C H
W S
Building Load
C H
-1 C
H W
R T e m p
C H
-1 C
H W
S T e m p
C o n tr o l
P a n e l
TWTW
CHWP-1
CHWP-2
4/4/17
B
C h lr -1
E n a b le
Revision History
A
B
TWTW
S e c C
H W
R T e m p
S E
C C
H W
S T e m p
A C J K
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FL
New
CH-1
THR
Mount OA Temp/
Humid sensor outside on north wall
O A
H u m id it y
D
O A
T e m p
E
C H
W P
-1 E n a b le
Wire to energize starter in ‘Auto’.
F G
CR
R
IB
U
C C
S C
X
V
Loop load wire through CT.
CT
C H
W P
-1 A m p s
C H
W P
-2 E n a b le
H I
CR
R
IB
U
C C
S C
X
V
CT
C H
W P
-2 A m p s
C H
W R
C H
W S
Bacnet
See sheet 7 for panel connections
SEQUENCE OF OPERATION – Chilled Water System
On a call for cooling as indicated by any AHU CHW control valve being more than 5% open, the lead CHWP will be energized. Should the lead pump fail to start, it will be alarmed and the lag pump will be started. Once flow is established the chiller will be enabled.
The lead pump will be rotated on a weekly basis to even the run times.
Once running, the chiller will operate under its OEM controls to maintain the CHWS temp set point.
A Bacnet interface is provided to the chiller. All applicable and pertinent points available in the chiller OEM controller will be mapped through for trending and alarming.
Bill of Materials
Item Quan. Part Number Description
TW 4 KTW-24-XW Immersion temp sensor w/well and WP box, 10k T-II
THR 1 H5-05PST OA temp w/humidity sensor
CR 3 RIBU1C Control relay, SPDT
CT 2 SCX10V150 Current transducer, split core
DDC 1 CDIB-350X-00 Distech FPC, 10UI, 8UO
PS 1 PSH40A Power supply
Air Handling Unit Valve Schedule
Unit Useage Valve Control Total Line Valve Calc Actual Actual Valve
Type Type GPM Size Size Cv #3 Cv pd Part Number
AHU-1 Cooling 3 Way Modulating 37.00 2" 1.5" 21.39 37.00 1.00 B340/ARB24-SR
AHU-6 Cooling 3 Way Modulating 47.00 2.5" 2" 27.17 46.00 1.04 B349/ARB24-SR
AHU-10 Cooling 3 Way Modulating 24.00 2" 1.5" 13.87 37.00 0.42 B340/ARB24-SR
AHU-11 Cooling 3 Way Modulating 20.00 1.5" 1.25" 11.56 19.00 1.11 B330/ARB24-SR
AHU-12 Cooling 3 Way Modulating 36.00 2" 1.5" 20.81 37.00 0.95 B340/ARB24-SR
Liebert-1 Cooling 3 Way Modulating 24.00 1.5" 1.25" 13.87 19.00 1.60 B330/ARB24-SR
Liebert-2 Cooling 3 Way Modulating 24.00 1.5" 1.25" 13.87 19.00 1.60 B330/ARB24-SR
CHW Panel Wiring Detail
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
4/4/17
Revision History
A
PS
DDC
A C E
B F H
C H
-1 C
H W
R T e m p
C H
-1 C
H W
S T e m p
O A
T e m p
C H
-1 E n a b le
C H
W P
-1 E n a b le
C H
W P
-2 E n a b le
Bacnet
D
O A
H u m id it y
120 vac
G
C H
W P
-1 A m p s
I
C H
W P
-2 A m p s
DOACS Bronson Lab Bldg 100
2700 N. John Young Pkwy
Kissimmee, FL 34741
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FL
J
C o m C
H W
R T e m p
K
C o m C
H W
S T e m p
Remove existing Andover controller from existing enclosure in chiller plant and install new Distech controller in its place.
VAV Box Detail
Mango Tropical Cafe
8102 International Drive
Orlando, FL 32819-9323
FIS, Inc.
Job Number 979-17005 Rev A
JMM
Facility Integration Solutions, Inc.
F S
4/4/17
Typical VAV Box Layout
To/From
24VAC
To/From
Communication
Loop Sensor Cable
E
D
H
VAV
Controller
Revision History
A
24 VAC Com
24 VAC Hot
BacNet
* Space Temperature
EC-Smart-Vue
CAT5
Space Sensor
Space & DA temperature sensors and EDH on SAV boxes only.
Replace SAB HVAC
RFS-0873
Cape Canaveral Air Force Station, FL
* Heat Stage 1
* Heat Stage 2
* Heat Stage 3
Bill of Materials - VAV Boxes
Item Quan. Part Number Description
DDC 11 CDIB-VASX-01 VAV controller
RT 11 PDITE-SMRT-VUE Smart room temp sensor
DAT 11 ST-D24 Discharge air temp sensor, 10k T-II
* DA Temp
VAV Terminal Unit Schedule
Tag ID Design CFM Min CFM Inlet Size EDH Kw
VAV-1 440 110 8" 3
VAV-2 880 220 8" 5
VAV-3 880 220 8" 5
VAV-4 800 200 8" 5
VAV-5 600 150 8" 3
VAV-6 600 150 8" 3
VAV-7 800 200 8" 3
VAV-8 800 200 8" 3
VAV-9 1600 400 6" 3
VAV-10 880 220 8" 5
VAV-11 300 75 5" 2