Washington DC 20560

Smithsonian Facilities 600 Maryland Avenue S.W. Suite 5001 ktravers Stamp

3nw RAW_metricStamp

SHEET INDEX

ABBREVIATIONS AND DEFINITIONS

LOCATION OF SITE

SMITHSONIAN INSTITUTION -

NATIONAL ZOOLOGICAL PARK

3001 CONNECTICUT AVE, NW

WASHINGTON, DC 20008

SITE DEVELOPMENT

PLANS

FOR

LOWER ZOO 13.2kV -

480V SUBSTATION

DISTRICT OF COLUMBIA PERMIT REVIEW AGENCIES

LLC

Eng:

PM:

QC:

3nw Typewritten Text

3nw Text Box NOTE: REFERENCE THE COORDINATED DRAWINGS LISTED ON THE COVER SHEET AND CONTAINED IN VOLUME 1.

O

L

M

S

T

E

D

W

A

L

K

TH-01

TH-03

TH-02

TRAVERSE DATA:

BENCHMARK DATA:

LLC

3nw

MH

E-29B

MH

LV-14

LLC

3nw

EX. 10" WATER±

(INV.: 59.07±)

EX. 6" SAN. SEWER

SERVICE±

(INV.: 55.10±)

PROPOSED 3-WAY 4"C

CONCRETE ENCASED

DUCTBANK FOR FUTURE

480V FEEDERS

EX. 6" STEAM LINE±

(INV: 55.43±)

ELECTRICAL DUCTBANK #1 PROFILE

EXISTING GRADE

3-WAY 4"C CONCRETE

ENCASED DUCT BANK

PROVIDE 3-WAY 4"C

CONCRETE ENCASED

DUCTBANK FOR FUTURE

480V FEEDERS

LZSW

EX. 6" STEAM LINE±

(INV: 55.01±)

EX. 6" SAN. SEWER

SERVICE±

(INV.: 54.63±)

EX. 10" WATER±

(INV.: 57.58±)

12-WAY 4"C CONCRETE

ENCASED DUCT BANK

PROPOSED 12-WAY 4"C

CONCRETE ENCASED

DUCTBANK FOR FUTURE

480V FEEDERS

ELECTRICAL DUCTBANK #3 PROFILE

EX. SAN. SEWER

SERVICE (PER DATA)±

(INV.: 47.00±)

EX. 10" WATER±

(INV.: 49.92±)

EX. 6" WATER±

(INV.: 49.70±)

EX. 10" WATER±

(INV.: 51.80±)

EXISTING GRADE

MH

LV-14

EX. ELEC DUCTBANKS

(PER DATA)

EX. ELEC DUCTBANKS

(PER DATA)

EX. ELEC DUCTBANKS

(PER DATA)

LZSW

12-WAY STUBBED

EX. 6" SAN. SEWER

SERVICE±

(INV.: 56.07±)

EX. 10" WATER±

(INV.: 57.78±)

EX. 6" STEAM LINE±

(INV: 55.21±)

4-WAY 4"C CONCRETE

ENCASED DUCT BANK

PROPOSED 4-WAY 4"C

CONCRETE ENCASED

DUCTBANK

ELECTRICAL DUCTBANK #2 PROFILE

EXISTING GRADE

MH

E-29B

PB

PB

INTERCEPT POINT #1

PROVIDE NEW 4-WAY, 6"C

DUCTBANK AND CONNECT TO

EXISTING DUCTBANK.

CONTRACTOR TO VERIFY

EXISTING DUCTBANK DEPTH

4-WAY 6"C CONCRETE

ENCASED DUCT BANK

EXISTING TO

REMAIN 4-WAY, 6"C

DUCTBANK TO

EXISTING MANHOLE

E-29A

LLC

3nw

600 Maryland Avenue S.W. Suite 5001

Washington, DC 20560

WIRING SCHEDULE SWITCHBOARD LZSW - OUTDOOR TYPE

277/ 480 VOLTS MAIN 1: 1600A MAIN BUS FREE STANDING

3 PHASE 4 WIRE

MAIN 2: 1600A MAIN BUS, 1600A DISTRIBUTION

65,000 AIC RATING

FEEDER

EQUIPMENT SERVED

FEEDER SIZE

CIRCUIT BREAKER

CONNECTED LOAD (KVA)

NOTES

NO.

FRAME POLE AMP A Ø B Ø C Ø

MAIN-1 AMAZONIA BUILDING "MSA" VIA ATS

(5 SETS) 4#400KCMIL + #3/0G

1600 3 1600 192.0 192.0 192.0 1,2

MAIN-2 DISTRIBUTION SECTION-3 --- 1600 3 1600 273.0 273.0 273.0 1

1 FUTURE POLICE STATION --- 600 3 500 3

2 FUTURE MULTI-USE BUILDING --- 600 3 500 3

3 SPACE & PROVISIONS --- 400 3 - 4

4 SPACE & PROVISIONS --- 400 3 - 4

5 SPACE & PROVISIONS --- 400 3 - 4

6 SPACE & PROVISIONS --- 400 3 - 4

7 SPACE & PROVISIONS --- 225 3 - 4

8 SPACE & PROVISIONS --- 225 3 - 4

9 SPACE & PROVISIONS --- 225 3 - 4

10 SPACE & PROVISIONS --- 225 3 - 4

11 SPACE & PROVISIONS --- 100 3 - 4

12 SPACE & PROVISIONS --- 100 3 - 4

465.0 465.0 465.0

CONNECTED LOAD MAIN-1 (KVA) =

576.0

(NOTE 5) CONNECTED LOAD MAIN 2 (KVA)=

819.0

DEMAND LOAD MAIN-1 (KVA) =

460.8

(NOTE 5) DEMAND LOAD MAIN 2 (KVA)=

614.3

LOCATION AMAZONIA YARD

SWITCHBOARD NOTES:

1. MAIN BREAKER: PROVIDE 100% RATED INSULATED CASE CIRCUIT BREAKER WITH ADJUSTIBLE LSIG TRIP SETTINGS.

2. PROVIDE NEW FEEDERS TO AMAZONIA ATS VIA EXISTING CONDUITS.

3. PROVIDE 80% RATED MOLDED CASE ELECTRONIC TRIP CIRCUIT BREAKER WITH ADJUSTABLE LSI TRIP SETTINGS.

4. PROVIDE SPACE & PROVISIONS FOR FUTURE MOLDED CASE ELECTRONIC TRIP CIRCUIT BREAKERS WITH ADJUSTABLE LSI TRIP SETTINGS.

5. LOAD INDICATE IS THE PROJECTED LOAD FOR FUTURE PROJECTS SERVED FROM THE DISTRIBUTION SECTION OF THIS SWITCHBOARD.

DEVICE SETTINGS - SWITCHBOARD LZSW

FRAME CURRENT RATING TRIP

PHASE - PROTECTION GROUND - PROTECTION

TAG DESCRIPTION

SIZE SENSOR PLUG DEVICE CURVE LTD LTD STD STD INSTANT CURVE GFD GFD

SIZE SIZE

PICK-UP BAND PICK-UP BAND PICK-UP BAND

MAIN CIRCUIT BREAKERS

MAIN-1 FIXED MOUNTED INSULATED CASE - MAIN BREAKER-1 1600 1600 1600

DIGITRIP

1150+

ANSI I2T IN

1.00

20.0

4.0

0.2

10.0

ANSI I2T OUT

0.25

0.2

(1600A) (6400A) (16000A) (400A)

MAIN-2 FIXED MOUNTED INSULATED CASE - MAIN BREAKER-2 1600 1600 1600

DIGITRIP

1150+

ANSI I2T IN

1.00

20.0

4.0

0.2

10.0

ANSI I2T OUT

0.25

0.2

(1600A) (6400A) (16000A) (400A)

DEVICE SETTINGS - FEEDERS

1 MOLDED CASE ELECTRONIC TRIP FEEDER BREAKER 600 600 500 DIGITRIP 310 ANSI I2T IN

1.00

FIXED

2.0

100ms

FIXED

(500A) (1000A) (5500A)

2 MODELD CASE ELECTRONIC TIRP FEEDER BREAKER 600 600 500 DIGITRIP 310 ANSI I2T IN

1.00

FIXED

2.0

100ms

FIXED

(500A) (1000A) (5500A)

A. THE INFORMATION SHOWN ABOVE ARE RECOMMENDED SETTINGS AND DETERMINED USING BASIS OF DESIGN EQUIPMENT. FINAL SETTINGS SHALL BE DETERMINED BY COORDINATION STUDY OUTLINED

IN SPECIFICATIONS AND ADJUSTED AS REQUIRED.

B.

ABBREVIATIONS: LTD - LONG TIME DELAY; STD - SHORT TIME DELAY; GFD - GROUND FAULT DELAY; C.T. - CURRENT TRANSFORMER.

Smithsonian Facilities

1633109_3T001 (1)
~1533106a-A-001
~1533106a-A-101
CIVIL_100%.pdf
CIV010 COVER SHEET AND GENERAL NOTES-CIV010.pdf
CIV100 EXISTING CONDITIONS PLAN-CIV100
CIV200 SITE PLAN-CIV200
CIV310 UTILITY PROFILES-CIV310