Existing Chiller Photographs and FAQ.docx
DOCX document 3 MB Posted
- Attached to
- FCC Beaumont - Emergency Chiller Replacement - Supply and Install Federal contract opportunity
- Solicitation number
- 15B50225Q00000039
About this file
This document is a FAQ and photographic reference guide for an emergency chiller replacement project at the Federal Correctional Complex in Beaumont, Texas (Project 23Z5AQ9). The document provides technical specifications and site details for the Central Administration Building (CAB) chiller located at 5430 Knauth Rd, Beaumont, TX 77705.
Key technical specifications include integration with Johnson Controls BAS system, 3-pole 250 amp breaker requirements, 250 mcm wire with 2" conduit, 4" piping, and 1" Cell glass insulation. The chiller location is described as the northeast corner of the CAB, with a concrete drive ending 25 feet from the unit and approximately 200 feet from the electrical room. The scope includes replacing isolation valves and installing permanent T-fittings with valves on each line to accommodate future temporary unit connections. The document references multiple attached photographs of the existing installation, though the actual images are not viewable in the provided text content.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFQ 15B50225Q00000039.pdf | ||
| 15B50225Q00000039 QAs.docx | DOCX document | |
| Pump Room Photos.pdf | ||
| Instructions to Offerors CAB Chiller.doc | DOC document | |
| SF 1413-23.pdf | ||
| 15B50225Q00000039 Questions and Answers.docx | DOCX document | |
| 15B50225Q00000039 Site Visit.pdf | ||
| RFQ 15B50225Q00000039.pdf | ||
| Instructions to Offerors - CAB Chiller.doc | DOC document | |
| Wage Determination 15-5217.pdf | ||
| Statement of Work - CAB Chiller.pdf | ||
| RFQ 15B50225Q00000039.pdf | ||
| Criminal History Check Forms - Blank.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Federal Correctional Complex Beaumont, Texas Project 23Z5AQ9 Emergency CAB Chiller Replacement
The CAB Chiller is located at the northeast Corner of the Central Administration Building (CAB) at 5430 Knauth Rd, Beaumont, TX 77705. There is a concrete drive at the which ends approximately 25 feet from the CAB Chiller. The CAB chiller is surrounded by a block wall. The distance from the chiller to the electrical room is approximately 200 feet.
Clarification
1. The name of the company to tie into the existing BAS system.
Johnson Controls.
2. Breaker size.
3 pole 250 amp
3. Wire and conduit size.
250 mcm wire and 2 ½ conduit
4. Piping size.
4”
5. Insulation type and thickness.
1 ¾” Cell glass
6. New Valves to be installed.
Replace isolation valves and install a “T” on each line for a temporary unit. “T’s” will also require a valve and will be permanent for emergency use if a temporary unit is required.
image5.jpeg image6.jpeg image7.jpeg image8.jpeg image9.jpeg image10.jpeg image11.jpeg image12.jpeg image1.PNG image2.PNG image3.jpeg image4.jpeg
File details come from the government source that posted it. Updated .