This document outlines requirements for fire curtain activation in a Fisher House facility. The fire curtains in a 20-bedroom Fisher House design must operate simultaneously upon activation of either the smoke detector located in the foyer or the smoke detector located in the corridor outside the kitchen. Each smoke detector must be located no more than 5 feet from the nearest curtain, in accordance with NFPA 72 (2010) standards.
The related federal contract opportunity is solicitation number 36C26122R0051 for life safety corrections at Fisher House 1 through the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21. The solicitation seeks to address requirements for smoke detector placement to activate fire curtains as outlined in the technical specifications.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fisher House Fire Curtain Activation by Smoke Detectors
For the Fisher House 20-Bedroom Design, both fire curtains shall operate simultaneously upon activation of either (1) the smoke detector located in the Foyer, or (2) the smoke detector located in the corridor outside of the kitchen (see attached drawing).
Each smoke detector must be located not more than 5 feet from the nearest curtain, in accordance with NFPA 72 (2010), 17.7.5.6.5.1 (see text on next page).
11/21/2011a
Reference: NFPA 72 (2010)
11/21/2011a
Smoke Detectors for Fisher House Fire Curtain Activation (each detector must be not more than 5 ft from the curtain)