Exhibit_J_-_Clearline_Operator_Submittal_REVIEWED.pdf

PDF 7 MB Posted

Attached to
Santa Cruz Downtown Library Tenant Improvements
Solicitation number
IFB No. ED-0328
Issued by
Santa Cruz County, San Francisco City, California

About this file

This submittal document is a product and technical data sheet for WindowMaster Clearline motorized window actuators being supplied by Pacific Glazing Contractors for the Downtown Library and Affordable Housing Project located at 119 Lincoln Street, Santa Cruz, California. The submittal includes shop drawings and specifications for the WMX 804-1G chain actuators (UL certified), control systems, and associated installation hardware. The project calls for multiple actuator units controlled through WindowMaster WCC motor control panels with integrated MotorLink technology, allowing for synchronized operation of up to four actuators per window and three-speed functionality (slow automatic speed, faster manual speed, and full emergency speed). The documentation specifies approximately 94 total actuators organized into twelve control groups (WCC-1 through WCC-12), with individual groups controlling between 8 and 20 actuators depending on location. The actuators feature a 24VDC nominal voltage system with programmable pressure safety functions to prevent entrapment, electronic position feedback accurate to one millimeter, and integrated reverse functionality to extend weather seal lifespan. The submittal was initially reviewed on June 4, 2026, marked as "Reviewed/Exceptions Noted," and resubmitted on July 2, 2026, with final architect review dated July 14, 2026, following coordination discussions between the architect of record, subcontractor, and WindowMaster representatives.

The exterior scope of work performed by Pacific Glazing Contractors includes only the actuators, brackets, pigtails, and basic wiring routing through curtainwall verticals, with all control panels, wind and rain sensors, field programming, and low-voltage electrical infrastructure (conduits, junction boxes, switch boxes, and final wiring connections) designated as tenant improvement contractor scope. The actuator system operates on a 120VAC input converted to 24VDC output through motor control panels, with wire sizing and distance limitations to be verified by the electrical contractor. All WCC motor control panels are delivered with factory default programming and require site-specific configuration by the customer or controls contractor after installation, a responsibility explicitly excluded from the manufacturer's scope. The documentation includes detailed wiring diagrams, connection specifications, and technical data sheets for the WMX 804-1G UL-certified actuators, which feature a maximum locking force of 3,000 Newtons, adjustable opening speeds of 0.118 to 0.374 inches per second, sound pressure levels of 33-43 dBA depending on speed, and a five-year warranty from shipment date.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ECHELCON, INC.

Review is for general conformance with the contract documents for this project only. Subcontractor or supplier is responsible for omissions, quantities, dimensions, field conditions, coordination with all trades, and information pertaining to fabrication processes or construction techniques. Review shall not relieve subcontractor or supplier from responsibility for errors, omissions or deviation from contract documents. Stamped submission does not constitute a change order.

By:

Date:

Submittal # Description:

Echelcon Comments/ Notes:

1. Reviewed for general conformance at this time, pending further review and comments from Architect & Engineer.

SUBMITTAL APPROVAL COVER SHEET

Downtown Library and Affordable Housing Project

119 Lincoln St.

Santa Cruz, CA 95060

CONSULTANT/ OTHER

ENGINEER

ARCHITECT

Adam Hudson 7/14/26

08 44 13.02- 07.1 Clearline Operators

Revised submittal per 7/2/2026 discussion between AOR, subcontractor and WindowMaster. Previous version included materials and scope that are not part of shell and core SOW.

Those items have been removed.

J Pereira 8.5.2026

TOS COMMENTS:

The previous version of this submittal reviewed on 6.4.2026 was marked REVIEWED/EXCEPTIONS NOTED. Resubmittal is not required.

Coordinate curtainwall elevations with GC.

DannyNguyenPham Text Box

FOR REFERENCE ONLY

Project Name:

Project #:

Submittal #:

Spec Number:

Spec Title:

Product Name:

Product Location:

Lead Time:

*Subject to change at time of order

Quantity

1 PDF

408-201-4233Kathy Greninger - Project Manager

Pacific Glazing Contractors

084413.01 2.03.F

ATTN: Jackson Bigham Glazed Aluminum Curtainwall

Scott Clark

CAUTION: Samples may be sharp; handle with care and caution.

Notes

MOTORIZED WINDOW ACTUATORS CLEARLINE-SPECIFICATION SECTION 087516.13

PRODUCT & TECHNICAL DATA CLEARLINE CHAIN ACTUATOR 804 UL

UL MOTOR PRODUCT AND TECHNICAL DATA

OVERRIDE SWITCHES WSK 103

5 Year Warranty from date of shipment

Submittal Transmittal

1600 Lana Way

Hollister, CA 95023

Phone 408.778.9243

945 West Julian St.

San Jose, CA 95126

Santa Cruz Library

25-789

To: ECHELCON INC.

Window Master Clearline Operators

The following documents are submitted for review and approval.

Curtainwall Awning windows

Description- 1 PDF INCLUDES:

WINDOW MASTER CLEARLINE OPERATORS

7/6/2026

REV. 2 SHOP DRAWINGS (SEPARATING SKIN AND T.I. SCOPE)

DannyNguyenPham

CHAIN STROKE

CLEAR OPENING DIAGRAM

APPROX. 13"

VENT PROJECTION

APPROX. 97

8"CHAIN STROKE

APPROX. 10 5

16"CHAIN EXTENSION

APPROX. 6 3

8"

CLEAR OPENING

APPROX. 27°

L PUSH POINTC

L VENTC

1 PUSH POINT DETAIL

SCALE : N.T.S.

APPROX. 33" - 43"

(VARIES)

24"

NOTE PIGTAIL

ORIENTATION

(6' length)

DETAIL

FULL SIZE (NOT BY WINDOWMASTER CLEARLINE INC.)

VENT PREPARATION- 11

32"

1 3 16"

CL VENT CL PUSH POINT

16"

DETAIL

FULL SIZE (NOT BY WINDOWMASTER CLEARLINE INC.)

VENT PREPARATION- 21

FULL SIZE

DETAIL ITEM 11

16"

ITEM 1 1 - 2

FULL SIZE 1

ITEM 1 1 - 1

FULL SIZE 1

*NOTE:

PACKING BY OTHERS

8"

8"

8"

2"

32"

NOTE PIGTAIL

ORIENTATION

(2) 8-32" TAP HOLES

(2) 7

32" DIA. HOLES

(2) 8-32" TAP HOLES

CUSTOMER

ORDER NO.

ARCHITECT

WINDOW MFR.

PART NO.ITEM QTY.DESCRIPTION

DATE :DWN BY : REVISED :

AS NOTED

SCALE

OF 6

SHEET NO.

PROJECT:

PACIFIC GLAZING CONTRACTORS

OBE ZS-2750

SANTA CRUZ

MHE 02-20-2026

P.O. BOX 1368 - NORTH WALES, PENNSYLVANIA 19454

DOWNTOWN LIBRARY

Fresh Air. Fresh People.

ACTUATOR COLOR = GREY : (RAL 9006)

WINDOWMASTER JOB NO. / WINDOWMASTER QUOTE NO.

300606

PO#

PAC 801 01

8-32 8-32 8-32

WAB 801 0101

WMX 804-1G 250 UL

PACKER

NUT

PAN-HEAD MACH. SCREW 1"

PAN-HEAD MACH. SCREW 2 1/4"

CHAIN BRACKET

KEY SWITCH

ACTUATOR

ITEM NO.

US-41349

30278

US-40792

32002

1 04-13-2026

ELECTRICAL NOTES:

1. OUR MOTORIZED SYSTEM INCLUDES: THE ACTUATOR,

SWITCH, CONTROL PANEL AND ATTACHMENT AT

THE WINDOW.

IT DOES NOT INCLUDE: ANY INSTALLATION, FIELD WIRING,

SWITCH BOXES, ELECTRICAL CONDUITS, OR JUNCTION

BOXES NECESSARY TO COMPLY WITH ELECTRICAL CODES

FOR 120V AND LOW VOLTAGE WIRING REQUIREMENTS.

NOTE: PROVISIONS FOR PROPER FIELD WIRING MUST BE

COORDINATED WITH ELECTRICAL CONTRACTOR.

2. WHEN LOCATING THE SWITCH AND CONTROL

PANEL PLEASE REFER TO THE WINDOWMASTER

WCC AND ACTUATOR INSTALLATION INSTRUCTION PACKET

FOR WIRE SIZING AND DISTANCE LIMITATIONS. ( FOUND AT

WWW.WINDOWMASTER.COM )

3. COMPONENT LOCATIONS TO BE DETERMINED BY OTHERS.

4. CONTROL PANEL TO BE INSTALLED IN COMPLIANCE WITH

NFPA 70 AND LOCAL CODES.

The design shown on the above illustration has been prepared on the basis of limited information available to WindowMaster International A/S and is merely a preliminary suggestion for the system design, including the positioning of the motors and the motor brackets. A design must always be adapted to meet the requirements and circumstances of each specific project. It is up to the customer and/or its advisors, in each specific case, to secure that the final design is suitable and will enable the system to function properly and otherwise meet the requirements and circumstances of the specific project and applicable laws and regulations. Consequently, WindowMaster International A/S assumes no liability for any loss to the customer, which derives directly or indirectly from the use of the design shown on the above illustration, nor assumes WindowMaster International A/S any liability for the final design. This illustration is the property of WindowMaster International A/S and must not be copied without the prior permission from WindowMaster International A/S. For safety reasons opening restrictions must be fitted on bottom-hung windows.

NOTE:

GENERAL NOTES :

1. THESE CONTROLS WILL OPEN THE VENT FOR AN APPROX. CHAIN

STROKE OF 9 7/8" AND AN APPROX. CLEAR OPENING OF 6 3/8".

2. DENOTES ITEMS SUPPLIED WITH ACTUATOR.

3. ALL ELEVATIONS ARE VIEWED FROM THE INSIDE.

4. VENTS MUST MOVE FREELY -FINGER TIP- OPERATION FOR EASE OF

OPERATION. HINGES SHOULD BE ZERO FRICTION & SUPPLIED WITH

LOOSE RIVETS.

5. PLEASE REFER TO ALL INDIVIDUAL PRODUCT DATA SHEETS FOR

TECHNICAL REQUIREMENTS AND LIMITS OF HARDWARE.

(ALSO FOUND AT WWW.WINDOWMASTER.COM)

6. WARNING : KEEP HANDS / CHILDREN AWAY WHILE OPERATING

WINDOWS.

SANTA CRUZ LIBRARY

PGC EXTERIOR SCOPE

CLEARLINE OPERATORS

(DOES NOT INCLUDE TENANT IMPROVEMENT SCOPE)

**ARCHITECT TO PROVIDE HIGHLIGHTED ELEVATIONS

FROM CURTAINWALL SHOP DRAWINGS, SHOWING WIRE

ROUTING THROUGH CURTAINWALL VERTICALS, AND

TERMINATION POINTS WHERE T.I. WILL PICK UP FROM

THERE.

***ALL ITEMS NOT LISTED (IE CONTROL PANELS ETC.) WILL BE BY

TENANT IMPROVEMENT CONTRACTOR.

CONTROL PANEL DIAGRAMS INCLUDED IN THIS SUBMITTAL ARE

ONLY FOR FUTURE USE BY T.I.

**ARCHITECT, PLEASE CONFIRM VENT

CLEAR OPENING DIMENSION. (4"?)

TOS: GC to coordinate.

DannyNguyenPham

CUSTOMER

ORDER NO.

ARCHITECT

WINDOW MFR.

DATE :DWN BY : REVISED :

AS NOTED

SCALE

OF 6

SHEET NO.

PROJECT:

PACIFIC GLAZING CONTRACTORS

OBE ZS-2750

SANTA CRUZ

MHE 02-20-2026

P.O. BOX 1368 - NORTH WALES, PENNSYLVANIA 19454

DOWNTOWN LIBRARY

Fresh Air. Fresh People.

WINDOWMASTER JOB NO. / WINDOWMASTER QUOTE NO.

300606

PO#

1 04-13-2026

The design shown on the above illustration has been prepared on the basis of limited information available to WindowMaster International A/S and is merely a preliminary suggestion for the system design, including the positioning of the motors and the motor brackets. A design must always be adapted to meet the requirements and circumstances of each specific project. It is up to the customer and/or its advisors, in each specific case, to secure that the final design is suitable and will enable the system to function properly and otherwise meet the requirements and circumstances of the specific project and applicable laws and regulations. Consequently, WindowMaster International A/S assumes no liability for any loss to the customer, which derives directly or indirectly from the use of the design shown on the above illustration, nor assumes WindowMaster International A/S any liability for the final design. This illustration is the property of WindowMaster International A/S and must not be copied without the prior permission from WindowMaster International A/S. For safety reasons opening restrictions must be fitted on bottom-hung windows.

NOTE:

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-1 FOR WIRING

(18) ACTUATORS CONTROLLED BY (1) SWITCHREFER TO WCC-2 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-3 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-4 FOR WIRING

(16) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-5 FOR WIRING

DannyNguyenPham

ARCHITECT

WINDOW MFR.

DATE :DWN BY : REVISED :

AS NOTED

SCALE

OF 6

SHEET NO.

PROJECT:

PACIFIC GLAZING CONTRACTORS

OBE ZS-2750

SANTA CRUZ

MHE 02-20-2026

P.O. BOX 1368 - NORTH WALES, PENNSYLVANIA 19454

DOWNTOWN LIBRARY

Fresh Air. Fresh People.

WINDOWMASTER JOB NO. / WINDOWMASTER QUOTE NO.

300606

PO#

1 04-13-2026

The design shown on the above illustration has been prepared on the basis of limited information available to WindowMaster International A/S and is merely a preliminary suggestion for the system design, including the positioning of the motors and the motor brackets. A design must always be adapted to meet the requirements and circumstances of each specific project. It is up to the customer and/or its advisors, in each specific case, to secure that the final design is suitable and will enable the system to function properly and otherwise meet the requirements and circumstances of the specific project and applicable laws and regulations. Consequently, WindowMaster International A/S assumes no liability for any loss to the customer, which derives directly or indirectly from the use of the design shown on the above illustration, nor assumes WindowMaster International A/S any liability for the final design. This illustration is the property of WindowMaster International A/S and must not be copied without the prior permission from WindowMaster International A/S. For safety reasons opening restrictions must be fitted on bottom-hung windows.

NOTE:

(8) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-6 FOR WIRING

(ITEM #12 - WCC 310 P 0202 UL)

(16) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-7 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-8 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-9 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-10 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-11 FOR WIRING

(20) ACTUATORS CONTROLLED BY (1) SWITCH

REFER TO WCC-12 FOR WIRING

DannyNguyenPham

S3X1 1 2 3

1 2 3

X2

X3 1 2 3

1 2 3

X4

X5 1 2 3

1 2 3

X6

X7 1 2 3

1 2 3

X8

X9 1 2 3

1 2 3

X10

WCA 3KI

S2 X1

X2

X3

X4

WCA 3M8

X.1 X.2 X.3 M

X.1 X.2 X.3 M

X.1 X.2 X.3 M

X.1 X.2 X.3 M

J5F4F3F2F1 F5 F6 F7 F8

X1

X2

X3

X4

X5

X6

X7

X8

X9

X10

F2F1

X7

X8

J9

SW1 USB

Dev

X3 1 2 3

1 2 3

X4

X5 1 2 3

1 2 3

X6

X7 1 2

1 2

X8

1 2 3

1 2 3

X9 4 5 6

4 5 6

X10 24V

X11 1 2 3

1.1 1.2 1.3S1X1 M M

2.1 2.2 2.3 X2 M M

U

SB

BA!

24V ups

W 24V0V 0VS

TOUCH

SCREEN

U

L1

S4X1

LN

S4X2-

GND

U

L1

S4X1

LN

S4X2-

+V +V

+V -V

-V -V

S3X1 1 2 3

1 2 3

X2

X3 1 2 3

1 2 3

X4

X5 1 2 3

1 2 3

X6

X7 1 2 3

1 2 3

X8

X9 1 2 3

1 2 3

X10

WCA 3KI

S2 X1

X2

X3

X4

WCA 3M8

X.1 X.2 X.3 M

X.1 X.2 X.3 M

X.1 X.2 X.3 M

X.1 X.2 X.3 M

J5F4F3F2F1 F5 F6 F7 F8

HRPG-600-24

AC INPUT: 100-240VAC 8.5A

DC OUTPUT: +24V--- 27A

50/60Hz

N

L

X1

X2

X3

X4

X5

X6

X7

X8

X9

X10

F2F1

X7

X8

J9

SW1 USB

Dev

X3 1 2 3

1 2 3

X4

X5 1 2 3

1 2 3

X6

X7 1 2

1 2

X8

1 2 3

1 2 3

X9 4 5 6

4 5 6

X10 24V

X11 1 2 3

1.1 1.2 1.3S1X1 M M

2.1 2.2 2.3 X2 M M

U

SB

BA!

24V ups

W 24V0V 0VS

TOUCH

SCREEN

GND

CONTROL PANEL POWER SUPPLY

ENLARGED DETAIL

CONTROL PANEL

WCC 320 P 0612 UL

-0V

+24V

SYNC/DATA

RELATED ELEVATIONS

DATE :DWN BY : REVISED :

SHEET NO.

PROJECT:

WIRING EXAMPLE - ITEM #3 (WCC 320 P 0612 UL)

MHE 02-20-2026

P.O. BOX 1368 - NORTH WALES, PENNSYLVANIA 19454

Fresh Air. Fresh People.

NOT TO SCALE

SCALEWCC-(x)

WIRING DIAGRAM

PAGE #

ITEM # 1 ( WMX 804 - 1G 250 UL )

ETHERNET 2

ETHERNET 1

WINDOWMASTER JOB NO. / WINDOWMASTER QUOTE NO.

300606

GENERAL NOTES:

-WCC MOTOR CONTROL PANELS COME WITH FACTORY DEFAULT PROGRAMMING, AND ARE

NOT CONFIGURED WITH PROJECT SPECIFIC PARAMETERS.

*ALL WCC MOTOR CONTROLLERS HAVE TO BE PROJECT SPECIFIC CONFIGURED ONSITE BY

THE CUSTOMER OR CONTROLS CONTRACTOR AFTER INSTALLATION.

(WCC MOTOR CONTROLLER IS DELIVERED FACTORY STANDARD, AND IS NOT DELIVERED

WITH PROJECT SPECIFIC MOTOR LINES, MOTOR GROUPS, INPUTS AND OUTPUTS. CONFIGURATION

TO BE COMPLETED BY OTHERS.)

-5 DEGREE OR HIGHER DIFFERENTIAL REQUIRED (THERMOSTAT).

-REFER TO WCC 310 & WCC 320 INSTALLATION PACKET FOR ALL TECHNICAL INFORMATION.

-PLEASE REFER TO THE WCC MOTOR CONTROL PANEL INSTALLATION INSTRUCTION PACKET

AND THE ACTUATOR PRODUCT DATA SHEET FOR WIRE SIZING AND TYPE AND DISTANCE

LIMITATIONS. (THESE CAN BE FOUND AT WWW.WINDOWMASTER.COM)

-ALL WMU & WMX ACTUATORS COME WITH MOTORLINK TECHNOLOGY, FUNCTIONAL WHEN

COMBINED WITH A WINDOWMASTER WCC MOTOR CONTROLLER.

*PROGRAMMING OF ALL CONTROLLERS IS REQUIRED ON SITE.

(NOT BY WINDOWMASTER CLEARLINE INC. - **SEE GENERAL NOTES**)

S1X2 A2

CONTROLLED BY

(S1X3) off on

D

IP

S w itc h

C on ne ct io n

Te rm in al s

R el ay

LED

S1X10

THE 10KΩ RESISTOR MUST BE MOVED FROM THE

RAIN SENSOR CONNECTION POINT ON THE WCC

CONTROL PANEL AND INSTALLED ON THE RAIN

SENSOR BRIDGING THE SWITCHING TERMINALS.

S1X10.6 S1X10.5

S1X10.3 S1X10.1

LEVEL 3

ACTUATOR 2

S1 X2

S1 X1

S2 X1

S2 X2

T O

S1 X2

-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

AC INPUT

120V AC, 60 Hz

(85-264V AC, 47-64Hz)

(NOT TO SCALE: REFERENCE ONLY)

ITEM # 1

( WMX 804 )

-0V

+24VSYNC/DATA

W

G

BR

(SYNC/DATA)

(+24V)

(-0V)

WMX 804 - Comes with 1.9m (6') cable pigtail.

LEVEL 4

S1X3

S2 X3

S2 X4

LOW VOLTAGE

LINES

SANTA CRUZ DOWNTOWN LIBRARY

S1 X4

S3 X1

S3 X2

S3 X3

S3

X4SWITCH INPUTS

ACTUATOR INPUTS

EXAMPLE SWITCH WIRING

EXAMPLE ACTUATOR WIRING

WIND & RAIN SENSOR WIRING - WCC-1

WIND & RAIN SENSOR WIRING - ALL OTHER WCC

S1X10.5 S1X10.6

CONNECTION OF

RAIN SENSOR SIGNAL

FROM WCC-1

S1X10

CONNECTION OF RAIN

SENSOR TO ALL OTHER WCC

S1X10.6 S1X10.5

INSTALL FIELD BUS CARD HERE.

GENTLY INSTALL PINS OF THE FIELDBUS

CARD INTO THE MAIN CARD.

WCA 3FB

BACnet IP

WLA 330 01

(WIND & RAIN SENSOR)

SWITCH

342 1

FRONT VIEW

OFF

CLOSE

OPEN

KEY ENTERS LOCK

TEETH ON SIDE

REAR VIEW

P/N 2354 - 3 POSITION KEY SWITCH

MOMENTARY CONTACT - SPRING RETURN TO CENTER

KEY REMOVAL CENTER ONLY

O

PE

N

C

LO

SE

C O

M M

O N

S1 X

3.

S1 X

3.

S1 X

3.

Solid State Output For Transmission Of Fault Signal

· 9.1 Fault - Open Contact = Fault, closed contact = OK

· 9.2 Fault - Open Contact = Fault, closed contact = OK

Solid state output for transmission of fault signal A fault must last at minimum of 20 seconds before the relay will indicate a fault.

Data:

Max Voltage: 30Vp (peak) Max Output: 150 mA Typical On-Resistance: 4.7 Ω Max On-Resistance: 8 Ω Max Switching Speed: 2 ms

Two Free Configurable Solid State Outputs

· 9.3 Output A

· 9.4 Output A

· 9.5 Output B

· 9.6 Output B

Data:

Max Voltage: 30Vp (peak) Max Output: 150 mA Typical On-Resistance: 4.7 Ω Max On-Resistance: 8 Ω Max Switching Speed: 2 ms

SOLID STATE OUTPUTS:

1 2 3 4 5 6

S1X9

Further Information is available in the WCC Installation Instructions on pages 16, 17, 29, & 30

See Appendix for detailed explanation of all configurable items.

CTS / BMS / GLT - Signal Max. 30V AC / DC 150mA

ACTUATOR 1-0V

SYNC/COMM. S1X 2.2

S1X 2.3

S1X 2.1

ACTUATOR 3

S1X2 A2

SWITCH 'SW1'

(S1X3)

ACTUATOR 4

T O

S1 X2 -0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

MAXIMUM OF 4 ACTUATORS PER MOTORLINE

ACTUATOR 2-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

ACTUATOR 1-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

REFER TO MATRIX FOR MOTORLINE GROUPING

1 04-13-2026

FOR REFERENCE ONLY-

CONTROL PANELS, WIND & RAIL

SENSORS & PROGRAMING ARE

NOT PROVIDED BY PGC/EXTERIOR

CONTRACT SCOPE. THESE WILL

BE BY TENANT IMPROVEMENT

CONTRACTS.

DannyNguyenPham

F2F1

X7

X8

J9

SW1 USB

Dev

X3 1 2 3

1 2 3

X4

X5 1 2 3

1 2 3

X6

X7 1 2

1 2

X8

1 2 3

1 2 3

X9 4 5 6

4 5 6

X10 24V

X11 1 2 3

1.1 1.2 1.3S1X1 M M

2.1 2.2 2.3 X2 M M

U

SB

BA!

24V ups

W 24V0V 0VS

TOUCH

SCREEN

U

L1

S4X1

LN

S4X2-

GND

U

L1

S4X1

LN

S4X2-

+V +V

+V -V

-V -V

HRPG-600-24

AC INPUT: 100-240VAC 8.5A

DC OUTPUT: +24V--- 27A

50/60Hz

N

L

F2F1

X7

X8

J9

SW1 USB

Dev

X3 1 2 3

1 2 3

X4

X5 1 2 3

1 2 3

X6

X7 1 2

1 2

X8

1 2 3

1 2 3

X9 4 5 6

4 5 6

X10 24V

X11 1 2 3

1.1 1.2 1.3S1X1 M M

2.1 2.2 2.3 X2 M M

U

SB

BA!

24V ups

W 24V0V 0VS

TOUCH

SCREEN

GND

CONTROL PANEL POWER SUPPLY

ENLARGED DETAIL

CONTROL PANEL

WCC 310 P 0202 UL

-0V

+24V

SYNC/DATA

RELATED ELEVATIONS

DATE :DWN BY : REVISED :

SHEET NO.

PROJECT:

WIRING EXAMPLE - ITEM #12 (WCC 310 P 0202 UL)

MHE 02-20-2026

P.O. BOX 1368 - NORTH WALES, PENNSYLVANIA 19454

Fresh Air. Fresh People.

NOT TO SCALE

SCALEWCC-(x)

WIRING DIAGRAM

PAGE #

ITEM # 1 ( WMX 804 - 1G 250 UL )

ETHERNET 2

ETHERNET 1

WINDOWMASTER JOB NO. / WINDOWMASTER QUOTE NO.

300606

GENERAL NOTES:

-WCC MOTOR CONTROL PANELS COME WITH FACTORY DEFAULT PROGRAMMING, AND ARE

NOT CONFIGURED WITH PROJECT SPECIFIC PARAMETERS.

*ALL WCC MOTOR CONTROLLERS HAVE TO BE PROJECT SPECIFIC CONFIGURED ONSITE BY

THE CUSTOMER OR CONTROLS CONTRACTOR AFTER INSTALLATION.

(WCC MOTOR CONTROLLER IS DELIVERED FACTORY STANDARD, AND IS NOT DELIVERED

WITH PROJECT SPECIFIC MOTOR LINES, MOTOR GROUPS, INPUTS AND OUTPUTS. CONFIGURATION

TO BE COMPLETED BY OTHERS.)

-5 DEGREE OR HIGHER DIFFERENTIAL REQUIRED (THERMOSTAT).

-REFER TO WCC 310 & WCC 320 INSTALLATION PACKET FOR ALL TECHNICAL INFORMATION.

-PLEASE REFER TO THE WCC MOTOR CONTROL PANEL INSTALLATION INSTRUCTION PACKET

AND THE ACTUATOR PRODUCT DATA SHEET FOR WIRE SIZING AND TYPE AND DISTANCE

LIMITATIONS. (THESE CAN BE FOUND AT WWW.WINDOWMASTER.COM)

-ALL WMU & WMX ACTUATORS COME WITH MOTORLINK TECHNOLOGY, FUNCTIONAL WHEN

COMBINED WITH A WINDOWMASTER WCC MOTOR CONTROLLER.

*PROGRAMMING OF ALL CONTROLLERS IS REQUIRED ON SITE.

(NOT BY WINDOWMASTER CLEARLINE INC. - **SEE GENERAL NOTES**)

S1X2 A2

CONTROLLED BY

(S1X3)

ACTUATOR 2

S1 X2

S1 X1

T O

S1 X2

-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

AC INPUT

120V AC, 60 Hz

(85-264V AC, 47-64Hz)

(NOT TO SCALE: REFERENCE ONLY)

ITEM # 1

( WMX 804 )

-0V

+24VSYNC/DATA

W

G

BR

(SYNC/DATA)

(+24V)

(-0V)

WMX 804 - Comes with 1.9m (6') cable pigtail.

LEVEL 4

S1X3

LOW VOLTAGE

LINES

SANTA CRUZ DOWNTOWN LIBRARY

S1

X4 SWITCH INPUT

ACTUATOR INPUTS

EXAMPLE SWITCH WIRING

EXAMPLE ACTUATOR WIRING

WIND & RAIN SENSOR WIRING - ALL OTHER WCC

S1X10.5 S1X10.6

CONNECTION OF

RAIN SENSOR SIGNAL

FROM WCC-1

INSTALL FIELD BUS CARD HERE.

GENTLY INSTALL PINS OF THE FIELDBUS

CARD INTO THE MAIN CARD.

WCA 3FB

BACnet IP

SWITCH

342 1

FRONT VIEW

OFF

CLOSE

OPEN

KEY ENTERS LOCK

TEETH ON SIDE

REAR VIEW

P/N 2354 - 3 POSITION KEY SWITCH

MOMENTARY CONTACT - SPRING RETURN TO CENTER

KEY REMOVAL CENTER ONLY

O

PE

N

C

LO

SE

C O

M M

O N

S1 X

3.

S1 X

3.

S1 X

3.

Solid State Output For Transmission Of Fault Signal

· 9.1 Fault - Open Contact = Fault, closed contact = OK

· 9.2 Fault - Open Contact = Fault, closed contact = OK

Solid state output for transmission of fault signal A fault must last at minimum of 20 seconds before the relay will indicate a fault.

Data:

Max Voltage: 30Vp (peak) Max Output: 150 mA Typical On-Resistance: 4.7 Ω Max On-Resistance: 8 Ω Max Switching Speed: 2 ms

Two Free Configurable Solid State Outputs

· 9.3 Output A

· 9.4 Output A

· 9.5 Output B

· 9.6 Output B

Data:

Max Voltage: 30Vp (peak) Max Output: 150 mA Typical On-Resistance: 4.7 Ω Max On-Resistance: 8 Ω Max Switching Speed: 2 ms

SOLID STATE OUTPUTS:

1 2 3 4 5 6

S1X9

Further Information is available in the WCC Installation Instructions on pages 16, 17, 29, & 30

See Appendix for detailed explanation of all configurable items.

CTS / BMS / GLT - Signal Max. 30V AC / DC 150mA

ACTUATOR 1-0V

SYNC/COMM. S1X 2.2

S1X 2.3

S1X 2.1

ACTUATOR 3

S1X2 A2

SWITCH 'SW1'

(S1X3)

ACTUATOR 4

T O

S1 X2 -0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

MAXIMUM OF 4 ACTUATORS PER MOTORLINE

ACTUATOR 2-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

ACTUATOR 1-0V

+24V

SYNC/COMM.

S1X 2.1 S1X 2.2 S1X 2.3

REFER TO MATRIX FOR MOTORLINE GROUPING

1 04-13-2026

FOR REFERENCE ONLY-

CONTROL PANELS, WIND & RAIL

SENSORS & PROGRAMING ARE

NOT PROVIDED BY PGC/EXTERIOR

CONTRACT SCOPE. THESE WILL

BE BY TENANT IMPROVEMENT

CONTRACTS.

DannyNguyenPham

ARCHITECT

WINDOW MFR.

DATE :DWN BY : REVISED :

AS NOTED

SCALE

OF 6

SHEET NO.

PROJECT:

PACIFIC GLAZING CONTRACTORS

OBE ZS-2750

SANTA CRUZ

MHE 02-20-2026

P.O. BOX 1368 - NORTH WALES, PENNSYLVANIA 19454

DOWNTOWN LIBRARY

Fresh Air. Fresh People.

WINDOWMASTER JOB NO. / WINDOWMASTER QUOTE NO.

300606

PO#

1 04-13-2026

The design shown on the above illustration has been prepared on the basis of limited information available to WindowMaster International A/S and is merely a preliminary suggestion for the system design, including the positioning of the motors and the motor brackets. A design must always be adapted to meet the requirements and circumstances of each specific project. It is up to the customer and/or its advisors, in each specific case, to secure that the final design is suitable and will enable the system to function properly and otherwise meet the requirements and circumstances of the specific project and applicable laws and regulations. Consequently, WindowMaster International A/S assumes no liability for any loss to the customer, which derives directly or indirectly from the use of the design shown on the above illustration, nor assumes WindowMaster International A/S any liability for the final design. This illustration is the property of WindowMaster International A/S and must not be copied without the prior permission from WindowMaster International A/S. For safety reasons opening restrictions must be fitted on bottom-hung windows.

NOTE:

DannyNguyenPham

WindowMaster 10-31-24 087516.13 - 1 Motorized Window Actuators - WindowMaster Clearline

SECTION 087516.13

MOTORIZED WINDOW ACTUATORS - WINDOWMASTER CLEARLINE

PART 2 PRODUCTS

1.01 MANUFACTURERS

A. Basis of Design: WindowMaster Clearline, Inc; www.windowmaster.com/#sle.

1.02 MOTORIZED WINDOW ACTUATOR CONTROL SYSTEM

A. Scope of Work:

1. Provide complete window system, including motorized window actuators with low-voltage pigtails, actuator brackets, chain brackets, motor control panels, fieldbus communications cards, outdoor weather station with wind or wind/rain sensor, key or rocker switches, setup switch, and accessories. See appropriate window section in Division 8 - Openings.

2. See Division 26 - Electrical for 120 V power requirements for window actuator motor control panels, and low-voltage cable requirements for motor control panels, window actuators, outdoor weather station with wind or wind/rain sensor, key or rocker switches, setup switch, and accessories; includes conductors sized for voltage drop, connectors, junction boxes, electrical enclosures, fuses, final connections, and setup.

B. Motorized Window Actuators:

1. Basis of Design: WindowMaster WMX/WMU/WMB Series mounted with

WindowMaster brackets.

2. Provide motorized window actuators with quantity and type recommended by manufacturer for window dimensions, weight, glass thickness, and opening direction/movement for long-term maintenance-free operation; minimum of one motorized actuator per operable window.

3. Finish: Standard color, unless otherwise indicated.

4. Nominal Voltage: 24 VDC, 10 percent ripple maximum.

5. Open Circuit Voltage: Up to 36 VDC.

6. Actuator Max Stroke: From 1.9 inches (50 mm) to 39.4 inches (1000 mm).

7. Traction Force: From 100 to 1,500 N.

8. Locking Force: Up to 3,000 N.

9. Power: Up to 24 W.

10. Current Consumption: 0.5 to 5 A per actuator.

C. Motorized Window Actuator System Performance:

1. Basis of Design: WindowMaster MotorLink actuators and motor control panels.

2. Programmable 24 VDC, with digital two-way communication technology.

3. Suitable for surface or concealed mounting for comfort or heat and smoke ventilation applications.

4. Provide reverse function to prolong life of weather seal.

5. Programmable for modification of tractive force and pressure for closing forces, subject to factors including hinges, window type, and application.

6. Actuator Position Feedback: Provide two-way communication with control panel for feedback to control software on exact position, for precision of opening to accuracy of one millimeter, and control, with security indication for open windows.

7. Three Speed Operation:

a. Provide two-way communication with control panel for operation at slow speed when in automatic mode, reducing potential impact or disturbances to occupants.

b. Enable actuators to operate at faster speed when activated by manual keypads to provide immediate visual response to user.

c. Operate at full speed in event of alarm signal for intense rain, snow, and wind or security and safety concerns.

8. Pressure Safety Function:

a. Capable of monitoring for entrapment on windows by communication via microprocessors installed within actuator and by monitoring, in real-time, electrical current being drawn and precise position of window to accuracy of less

DannyNguyenPham

WindowMaster 10-31-24 087516.13 - 2 Motorized Window Actuators -than one millimeter.

b. Detect if object becomes trapped in leading edge of window and prevent it from closing by monitoring current being drawn and reversing actuator to release obstruction.

c. Pressure Safety Sensitivity: Adjustable, to account for variable closing force of actuator combined with size and weight of window, configuration of window and its hinges, and rigidity of profile itself. Enables monitor and adjustment of overall performance and sensitivity of system as required during life of building.

9. Fault Indication: Provide two-way communication with control panel for feedback to control software on window status and early indication of errors with actuator operation or wiring.

10. Synchronization Function:

a. Actuators to operate fully synchronized, without external synchronization module.

b. Support synchronization of up to four actuators on one window depending on window dimensions.

c. Actuators communicate directly and adjust speed to operate in synchronization.

D. Motor Control Panels:

1. Listed and labeled as complying with UL 325.

2. Input Voltage: 120 VAC.

3. Output Voltage: 24 VDC.

END OF SECTION

DannyNguyenPham

WindowMaster 10-31-24 230924 - 1 Natural Ventilation System -

SECTION 230924

NATURAL VENTILATION SYSTEM - WINDOWMASTER CLEARLINE

PART 2 PRODUCTS

1.01 MANUFACTURERS

A. Basis of Design: WindowMaster Clearline, Inc; NV Embedded;

www.windowmaster.com/control-systems/natural-and-mixed-mode-ventilation/nv-embedded/#sle.

B. Source Limitations: Obtain natural ventilation system components, including motorized window actuators, controls, weather stations, indoor sensors, occupant override key or rocker switches, and cloud-based data system from single manufacturer.

1.02 NATURAL VENTILATION SYSTEM (NVS)

A. Provide design, labor, materials, tools, equipment, services, and transportation necessary for complete natural ventilation system.

B. Delegated Design: Engage qualified Natural Ventilation System Provider to design turnkey natural ventilation system, including, but not limited to, window actuators, motor control panels, cabling, hardware, and accessories.

C. System Description:

1. Provide indoor climate control system capable of being adapted to individual building and user requirements; embed software and functionality of automated natural ventilation into controller.

a. Comply with ASHRAE Std 55 and ASHRAE Std 62.1.

b. Provide stable and comfortable indoor climate for building occupants with automatic operation of motorized window vents based on system control algorithms and inputs:

1) Indoor temperature, CO2, and humidity sensors in each room/zone.

2) Wind direction/speed, rain, and outdoor temperature from weather station on roof.

3) Building OCCUPIED, UNOCCUPIED SECURED, or UNOCCUPIED status.

c. Provide demand drive system that modulates for seasonal changes, and changes from winter pulse/mode to trickle ventilation and night cooling mode during summer.

2. Scope of Work:

a. See appropriate window section in Division 8 - Openings and 087516.13 for complete window system, including motorized window actuators with low-voltage pigtails, actuator brackets, chain brackets, motor control panels, fieldbus communications cards, outdoor weather station with wind or wind/rain sensor, key or rocker switches, setup switch, and accessories.

b. NVS Provider to provide sensor/keypad, outdoor weather station, outdoor wind and rain sensor, and USB for cloud access with sequence of operations, app, facilities dashboard, and cloud data trending. See "Hardware" below.

c. See Division 26 - Electrical for 120 V power requirements for window actuator motor control panels, and low-voltage cable requirements for motor control panels, window actuators, outdoor weather station with wind or wind/rain sensor, key or rocker switches, setup switch, and accessories; includes conductors sized for voltage drop, connectors, junction boxes, electrical enclosures, fuses, final connections, and setup.

d. Owner to provide equipment and IP network connection used for cloud-based system operation in building as required.

D. Motorized Window Actuator System Performance:

1. See Section 087516.13 for additional requirements.

2. Basis of Design: WindowMaster MotorLink actuators and motor control panels.

3. Programmable 24 VDC, with digital two-way communication technology.

4. Suitable for surface or concealed mounting for comfort or heat and smoke ventilation applications.

DannyNguyenPham Text Box

FOR REFERENCE ONLY-CONTROL

PANELS, WIND & RAILSENSORS & PROGRAMING ARE

NOT PROVIDED BY PGC/EXTERIOR CONTRACT SCOPE. THESE WILL BE BY TENANT IMPROVEMENT CONTRACTS.

DannyNguyenPham

WindowMaster 10-31-24 230924 - 2 Natural Ventilation System -

5. Provide reverse function to prolong life of weather seal.

6. Programmable for modification of tractive force and pressure for closing forces, subject to factors including hinges, window type, and application.

7. Actuator Position Feedback: Provide two-way communication with control panel for feedback to control software on exact position, for precision of opening to accuracy of one millimeter, and control, with security indication for open windows.

8. Three Speed Operation:

a. Provide two-way communication with control panel for operation at slow speed when in automatic mode, reducing potential impact or disturbances to occupants.

b. Enable actuators to operate at faster speed when activated by manual keypads to provide immediate visual response to user.

c. Operate at full speed in event of alarm signal for intense rain, snow, and wind or security and safety concerns.

9. Pressure Safety Function:

a. Capable of monitoring for entrapment on windows by communication via microprocessors installed within actuator and by monitoring, in real-time, electrical current being drawn and precise position of window to accuracy of less than one millimeter.

b. Detect if object becomes trapped in leading edge of window and prevent it from closing by monitoring current being drawn and reversing actuator to release obstruction.

c. Pressure Safety Sensitivity: Adjustable, to account for variable closing force of actuator combined with size and weight of window, configuration of window and its hinges, and rigidity of profile itself. Enables monitor and adjustment of overall performance and sensitivity of system as required during life of building.

10. Fault Indication: Provide two-way communication with control panel for feedback to control software on window status and early indication of errors with actuator operation or wiring.

11. Synchronization Function:

a. Actuators to operate fully synchronized, without external synchronization module.

b. Support synchronization of up to four actuators on one window depending on window dimensions.

c. Actuators communicate directly and adjust speed to operate in synchronization.

E. Hardware:

1. WindowMaster Model WWS 100 NV Embedded indoor room temperature/CO2/humidity sensor and keypad.

a. Quantity: Minimum of one per zone.

b. Location: Outlined in system drawings by NVS provider.

2. WindowMaster Model WOT 100 outdoor temperature sensor.

a. Quantity: One.

3. WindowMaster NVE Dongle USB dongle for cloud access; NV Embedded control sequence, algorithms to control automated windows and login access to Cloud solution.

a. Quantity: One per motor control panel.

F. Cloud Access/Software:

1. Provide three years of cloud-based data system access to Owner.

2. Provide dashboard access to edit zoning set-points and overview of system for facilities team via cloud data, available for iOS, Android, and computer browser.

3. Tablet, smart phone, and/or computer to be provided by Owner.

4. Provide individual zoning feedback for building occupants on real-time temperature, CO2, and relative humidity reading via app, upon approval of facilities maintenance team, along with intermittent override of zone’s automatic windows.

PART 3 EXECUTION

END OF SECTION

DannyNguyenPham Text Box

FOR REFERENCE ONLY-CONTROL

PANELS, WIND & RAILSENSORS & PROGRAMING ARE

NOT PROVIDED BY PGC/EXTERIOR CONTRACT SCOPE. THESE WILL BE BY TENANT IMPROVEMENT CONTRACTS.

DannyNguyenPham

Description

� designed for surface mounting
� for comfort ventilation
� to be used with all window types
� to be used together with ±24V control units or control units

with MotorLink®

� can be used together with espagnolette WMB
� external safety edge can be connected directly to the

actuator (actuator version ’E’)

� available with and without UL certification:

Europe: order without UL certification USA / Canada: order with UL certification (version UL)

� synchronization of up to four window actuators – no need for an external synchronization module

� genuine position feedback and three speeds when using control unit with MotorLink®

� soft close
� built-in electronic load switch-off/end stop
� electronic actuator with micro controller
� the actuator has an integrated reverse function to ensure a

prolonged life span of the window gaskets

� easy mounting

Actuator variants The actuator is available in four different versions:

single actuator (-1), double actuator (-2), triple actuator (-3) and quad actuator (-4).

The synchro actuators (-2, -3 and -4) are equipped with a patented synchronization function, in which the actuators communicate directly with each other, which ensures the actuators operate at exactly the same speed and position.

On large windows up to four actuators can be mounted on the same window – with no need for an external synchronization module.

Pressure safety function The risk of entrapment is reduced as the actuators are programmed to reverse if they encounter obstacles when closing. The set points determining when the actuators are to reverse are individually adjustable.

WMX 504 / 504 UL / 804 / 804 UL

Chain actuator

Version 17 Actuators

1.41

Natural ventilation

±24V control MotorLink® UL certification

– Actuators

Version S Version E

White, RAL 9010

Black, RAL 9005 Grey, RAL 9006

DannyNguyenPham

Technical specifications

Locking force 3000N

Permitted short pressure load when chain has run to end stop

100N

Short pressure capacity on motor Max. 150N (e.g. at the beginning of opening: sticky gasket, ice, wind speed)

Chain opening 1 15/16’’ – 9 13/16’’ increments of 25/64’’, maximum opening depends on the window construction

Opening speed 0.276 in/s (programmable 0.118 in/s up to 0.374 in/s)

Sound pressure level ≤33 dBA (operational speed: 1/8” in/s), ≤43 dBASE (operational speed: 3/8” in/s)

Window types Window types and sizes must be agreed with the window supplier and WindowMaster

Window width Min. 1’ 2 3/8”, maximum width depends on the window construction and the number of window actuators

Window height Min. 1’ 3/8’’ / 1’ 3 3/4’’ ( see installation suggestions 1 and 3), maximum height depends on the window construction and the number of window actuators

Nominal voltage 24 VDC (max. 10% ripple)

Voltage 20 - 36 VDC

Max. open-circuit voltage Max. 36 VDC

Current consumption WMX 504 / 504 UL: max. 0.5A WMX 804 / 804 UL: max. 1.0A

Operating condition +23°F – +113°F, max. 90% relative humidity (not condensing)

Switch-on-duration ED 40% (max. 4min. per 10min)

Material Lacquered zinc housing with 0.39’’ zinc cromate passivated steel chain and a 6’ 51/64’’ 3-core 22AWG cable with fast-in/fast-on connectors for connection to the extension cable WLL

WMX 504 / 804: 6’ 51/64’’ grey silicone cable

WMX 504 UL / 804 UL: 6’ 51/64’’ UL listed/recognized cable in grey (grey actuator) or white (white actuator)

Colour Aluminium (RAL 9006), white (RAL 9010) and black (RAL 9005). Other RAL colours available at additional price

Size 1’ 1 1/16’’ x 1 1/8’’ x 1 5/8’’ (W x H x D)

Weight 2.2 lbs

IP rating IP20 – when surface mounted / IP32 – when concealed

Certification Actuators with “U” in the article no. are UL certified accordingly to UL 325 and CAN/CSA-22.2 No. 247-14 and is supplied with UL approved cables UL STYLE 2464

SHE test WMX 504 / 504 UL / 804 UL: not SHE tested

WMX 804*: �tested in accordance with DIN 18232-3, section 3.6 (30 minutes at 572°F) *The construction of the actuator is identical with WMX 802, which has passed the SHE test

Life span Tested with 10,000 opening and closing movements

Delivery includes Actuator with 6 51/64’’ cable with fast in/fast out connector for WLL cable

To be ordered separately Brackets and WLL extension cable

Note We reserve the right to make technical changes

Opening speeds One speed:

Actuators connected to ±24 VDC control units (e.g. WUC) can be run with one speed – see the following page for opening speed.

Three speeds:

Actuators connected to control units with MotorLink® (e.g. WCC) can be run with three different speeds:

�automatically control speed – actuators run slowly and almost soundlessly.

�manual control speed – actuators run faster and more audibly.

�H&S and safety control speed – actuators run fastest. H&S control always has highest priority.

DannyNguyenPham

Product code composition (actuator supplied in sealed plastic packaging)

WMX 504

WMX 804

n x xxx x x 3

Product version: 3

Certification: 0 = CE, U = CE + UL

Actuator hardware version: S = standard, E = with connection for pressure safety strip (E: not UL actuator)

Chain opening: 1 15/16’’ – 9 13/16’’ increments of 25/64’’ (050 = 25/64’’)

Colour: G = grey, W = white

Actuator variant: 1= single, 2 = double, 3 = triple, 4 = quad

Explanation of product code structure

WMX 504-2G070E 03 � WMX 504 actuator, double synchronisation, grey, 2 3/4’’ chain opening, with connection for pressure safety strips, with CE certification, product version 3 dBA 10

Whisper Moderate rainfall

Normal conversation

Traffic noise Jackhammer Boeing 747

120WMX 504 / 804

≤33 dBA

Items Chain stroke [ft. and in.]

Length (L) [ft. and in.] UL Item no. Item no. with entrapment connection

Single actuator

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 504-1#xxx**S *** WMX 504-1#xxx**E

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 804-1*xxx**S *** WMX 804-1*xxx**E

Double actuator

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 504-2#xxx**S *** WMX 504-2#xxx**E

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 804-2*xxx**S *** WMX 804-2*xxx**E

Triple actuator

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 504-3#xxx**S *** WMX 504-3#xxx**E

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 804-3*xxx**S *** WMX 804-3*xxx**E

Quad actuator

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 504-4#xxx**S *** WMX 504-4#xxx**E

1 15/16’’– 9 13/16’’ 1’ 1 1/16” X WMX 804-4*xxx**S *** WMX 804-4*xxx**E

# G = Grey, RAL 9006; W = White, RAL 9010.

* G = Grey, RAL 9006; W = White, RAL 9010; B = Black, RAL 9005.

** 1 15/16’’ – 9 13/16’’, in increments of 25/64’’ (050 = 25/64’’) *** The actuator can be supplied with certification according to UL 325 See also the table ’Product code composition’ for further details as well as determination of final item no.

The sound pressure level was measured externally by The Danish Technological Institute. The measurements have been carried out in a large regular room size 7 x 14 x 2.4 m (W x L x H) with the ceiling covered with a standard sound absorbent material. The A-weighted sound pressure levels have been measured at a distance of 1 meter away from the surface of the actuators and at the height of 1.6 meters from the floor.# The actuators were not installed on any window profile nor added any load. The full opening and full closing sound of the actuators have been measured and the result represents the average of the measurements.

DannyNguyenPham

Brackets Item no.

Chain bracket with tight-fitting bolt, WMX, for sash or frame WAB 801

Chain bracket with split, for sash or frame WAB 860

Chain bracket for wooden windows, for sash WAB 867

Angle bracket for actuator, aluminium RAL 9006 WAB 804 0101

Angle bracket for actuator, white RAL 9010 WAB 804 1101

Z bracket for actuator WMX 504/804/526/826. Sash min. 2’ 7 1/2’’ WAB 805

Z bracket for actuator WMX 804 – for windows with offset sash min. 19/32’’ WAB 807

See separate product sheets for further information.

Installation suggestion 1 - Inward opening

WAB 804 0101

WAB 801

Installation suggestion 2 - Outward opening

WAB 804 0101

WAB 801

/1

6"

3/

5/

3/ 8"

1/ 4"

1/

2 1/16"

M in

. 1

/1

6'

/1

6"

3/

5/

3/ 8"

1/ 4"

1/

2 1/16"

DannyNguyenPham

WMX 504 / 504 UL / 804 / 804 UL

Chain actuator

©WindowMaster 2003, 2023 ®WindowMaster is a registered trademark used under license by WindowMaster International A/S windowmaster.com

All dimensions are originally in metric units and converted into imperial units.

For exact measurements please refer to documentation with metric values.

Installation suggestion 4 - Outward opening

WAB 801

Installation suggestion 3 - Inward opening

WAB 805

WAB 801

1/

1/2" 1/2" 1 3/16"

5/ 8" 11

/1 6"

/1 6"

3/

3/

8"

/1 6"

2 1/2"

M in

. 1 ' 3

/4

1' 1 1/16''

1 5/8''

1 1/8''

Fo rc e [N

Pressure force Traction force

WMX 804

WMX 504

WMX 804 UL

WMX 504 UL

Stroke

9 13/16''

7 7/8''

3 15/16''

Not delivered by WindowMaster

DannyNguyenPham