This document outlines agency special requirements for a federal bankruptcy courthouse lease solicitation issued by the General Services Administration. Key details include a 15,349 square foot space requirement for the bankruptcy clerk and judges' chambers suites. Specific room requirements and quantities are provided for spaces such as the bankruptcy judge courtroom and associated rooms totaling 4,487 square feet. Technical specifications cover items including acoustic criteria, security measures, lighting levels, and millwork details. Appendices include sample courtroom layouts and a room data sheet section with additional information on finishes, fixtures and equipment for individual room types.

View the file

Other files

File Type Posted
Exhibit A_2026.6.16_L100.pdf PDF
Exhibit B_3516 Solicitation Provisions (Mar. 2026).pdf PDF
Exhibit C_Agency Special Requirements.pdf PDF
Exhibit C2_Adjacency Diagram_v.260616.pdf PDF
Exhibit D Security FSL Level III.pdf PDF
Exhibit G_GSA Form 1217 (Nov. 2016).pdf PDF
Exhibit J_GSAR Representation 552.270-33 (Nov. 2024).pdf PDF
Exhibit C4_Millwork v.260616.pdf PDF
Exhibit E_3517B General Clauses (Apr. 2026).pdf PDF
Exhibit K_ RLP - Broker Project (May 2026).pdf PDF
Exhibit K1_Lease - Broker Project (May 2026).pdf PDF
Exhibit L_ Lease - CA Tax (May 2026).pdf PDF
Exhibit M_DID_Review_Guide.pdf PDF
Request for Lease Proposals (RLP).pdf PDF
Exhibit C1_Room List v.260616.pdf PDF
Exhibit C3_USCDC RDS v.260616.pdf PDF
Exhibit F_Form 1364 Proposal to Lease Space (Jan. 2023).pdf PDF
Exhibit H_Prelease Evaluation Form 12000 (May 2015).pdf PDF
Exhibit I_Seismic Forms A - F with Instructions.pdf PDF
RLP Amendment No 6.pdf PDF
RLP Amendment 5.pdf PDF
RLP Amendment 4.pdf PDF
RLP Amendment 3.pdf PDF
Exhibit E Form 3517B Dec. 2023.pdf PDF
RLP Amendment 2.pdf PDF
Exhibit D Form 3516 Dec. 2023.pdf PDF
RLP Amendment 1.pdf PDF
Exhibit G From 1217.pdf PDF
Exhibit K For Ownership.pdf PDF
Exhibit L FAR-24.pdf PDF
Exhibit E Form 3517.pdf PDF
Exhibit J Wage Determination.pdf PDF
Sensitive Information Notice.pdf PDF
Exhibit A Form L100.pdf PDF
Exhibit B I ASR.pdf PDF
0CA3254 SB RLP.pdf PDF
Exhibit B III ASR.pdf PDF
Exhibit C Security.pdf PDF
Exhibit D Form 3516.pdf PDF
Exhibit F Form 1364.pdf PDF
Exhibit H Form 12000.pdf PDF
Exhibit I Seismic.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AGENCY SPECIAL REQUIREMENTS DOCUMENT

FEDERAL BANKRUPTCY COURTHOUSE – SANTA BARBARA, CA July 13, 2023

INITIALS _____ & _____ LEASE No. __________ Offeror/Gov. Page: 1 Date

CONTENTS

Part A: General Notes………………………………………………………………………………………… Pages 1-5 Part B: Room-by-room Requirements Summary…………………………………………………………….. Page 6-7 Part C: Room Data Sheets Appendix (Excerpt from the 2021 U.S. Court Design Guide)………………...… A-1 thru A-133

PART A

General Notes:

1. The 2021 U.S. Courts Design Guide (hereafter referred to as “Design Guide”) is the definitive requirement for new construction of court required spaces. All room sizes and space allotments for this courthouse and other standards, including, but not limited to room finishes, ceiling heights, millwork requirements, power and data infrastructure, lighting, acoustic criteria, and security, are to be based on the Design Guide. While this document is called a “guide”, it is nevertheless the binding document that is part of, and/or in addition to these Special Requirements. The purpose of these Agency Special Requirements is to provide specific data and information that is unique to this project. However, any items that are not specifically listed in these Agency Special Requirements, but listed in the Design Guide, are still considered requirements that must be provided by the offeror. Any discrepancies between the Design Guide, the Agency Special Requirements Document, and the lease document must be brought to the government’s attention in writing and will be clarified by the court representatives. The most stringent interpretation shall apply unless specifically noted otherwise.

2. Variances to the Design Guide Many of the construction projects conducted in the Judiciary are renovations to existing space. Although the Design Guide applies to these projects, it is understood that some standards in the Design Guide are difficult or impossible to achieve in existing space, particularly in historic buildings. Certain design requirements stated in the Design Guide may be impractical, impossible, or cost-prohibitive to meet because of challenging existing conditions. Stakeholders should discuss these challenges early in the project and determine how to best implement the Design Guide requirements to suit their specific needs and uphold its intent.

3. Space Envelope Flexibility A total space envelope for the Bankruptcy lease has been calculated using appropriate circulation factors, allowances for support-type spaces, and the space standards described in the Design Guide. The Courts have the flexibility to configure space within the envelope to meet their local needs.

4. Circulation - This building requires multiple separate circulation paths, including 1) restricted circulation for judges connecting the judicial parking to chambers and courtrooms and 2) public circulation leading from the security screening station at the building entry to the public offices of each agency in the building and to the courtrooms and other public spaces. Careful consideration must be made to incorporate these separate circulation paths with code required exit pathways. Required public exits from the courtroom cannot exit into the restricted corridors. Refer to the Design Guide for additional information.

5. Circulation Factors Court circulation areas are calculated using the Multiplier for the Circulation Factor for each division provided in the 2021 Design Guide. The area for circulation is added to the individual areas identified in the room-by-room summary requirements to obtain the overall tenant areas listed in the lease. The following table clarifies the circulation factors used.

RLP NO. 0CA3254 Lessor: ________ Government: ________ Exhibit B-II, Agency Requirements

INITIALS _____ & _____ LEASE No. __________ Offeror/Gov. Page: 2 Date

PART A

General Notes: (Continued)

6. As space is planned out per the program requirements, it is important to note that space calculations must be measured in net square footage (NSF), from surface of wall to surface of wall for each enclosed area/office within the suite. This differs from the standard BOMA usable calculation of measuring space from center of wall to center of wall. Flexibility is required so that sufficient circulation and the extra allowance for walls are included in the total square footage. A written description of this variance is available from GSA. A test-fit layout showing that program requirements will fit within the space proposed will be required to be submitted for review, however, this test-fit will not be considered the final design. The test fit drawing is to show the net square footages of each room.

7. All Court areas of the building must have perimeter demising walls (slab-to-slab) for separation from other tenants or government agencies.

8. Acoustical Performance. An acoustical engineer is to be retained to confirm that the proposed design, including all finishes, wall, door, and ceiling constructions and HVAC elements, conform to the specific criteria listed for each room in the Design Guide.

Partitions. STC requirements for special function rooms are shown in PART B: Room-by-Room Requirements Summary. Where two different wall types are specified for adjacent rooms, the higher STC wall is to be used. Note that final wall type assignments are to be coordinated with applicable codes.

Doors. Where doors are a part of sound-locks, the doors should include an industry standard sound seal gasketing package including an overlapping astragal seal. Doors in STC 45 walls (and higher) are to be provided with hardware, including, but not limited to, seals, gaskets, and astragals that provide an STC rating for the door no less than 5 points lower than that of the adjacent wall. In walls that require a higher acoustic performance based on the Design Guide criteria, consult an acoustic engineer on appropriate door and hardware specifications.

9. Millwork:

Funding Responsibilities All costs for millwork including the movable attorney/prosecutor lectern and attorney/litigant tables, should be funded out of the construction project. This does not include the evidence presentation cart. Coordinate the purchase of the evidence cart with the furniture acquisition plan (FAP). Coordinate infrastructure requirements for all millwork and furniture even that which is not provided as part of the construction funding as part of the base building scope. Any movable items included below should be constructed to ensure continuity of veneer type, stain, and style.

Materials Requirements Millwork for courtrooms, courtroom associated spaces, and judges’ chambers suites (including wall paneling, base and trim, custom wood doors and frames, bookcases, cabinets, and worksurfaces) should be constructed to AWI standards for premium-grade millwork. The millwork in all other courthouse spaces should be constructed to AWI standards for custom-grade millwork unless noted otherwise. All millwork to be shop finished from a single source.

Doors All courtroom and chamber doors are to be hardwood-veneer solid-core doors unless security requirements for a particular entry cannot be achieved with this type of door. Where wood doors are specified, they should be finished with stain and a clear sealer. Use AWI premium-grade solid hardwood door jambs, stops, and casings. Doors should be coordinated with USMS security requirements.

Bookshelves in Chambers Bankruptcy Chambers are allowed 10 fixed bookcases with adjustable shelving. The location and quantity (within allowable limit) of bookshelves is at the discretion of the judge. Shelving shall be affixed to the wall, and the wood shall match or complement the architectural trim. One fixed bookshelf is three linear feet wide by 10 inches deep.

INITIALS _____ & _____ LEASE No. __________ Offeror/Gov. Page: 3 Date

PART A:

General Notes (Continued)

Service Units Service units should be standard-size plastic-laminate or wood upper and lower wall-mounted cabinets and solid surface countertops with an integral sink of a durable material. Intermediate shelves should be provided in upper and lower cabinets. Adjacent to the sink, one drawer minimum should be provided for food preparation utensils and other supplies. Units should be laid out to accommodate some or all of the following: a microwave oven, a sink, a coffeemaker, under-counter lights, and a refrigerator. A wall-mounted shelving unit above the sink area to accommodate the microwave oven may be provided as an option.

10. HVAC - Each enclosed room to be provided with a separate supply and return. The server/telecommunications room, USMS control room, and audiovisual equipment rack rooms or closets shall have continuous 24/7 cooling with separate package units. HVAC system to be zoned to allow for independent operation of chambers area and courtroom area outside of regular business hours while also minimizing the cost of overtime utility usage. All other areas to be zoned and designed per the code and LEASE standards unless noted otherwise. All court-occupied areas share the following mechanical design criteria unless otherwise specified:

Temperature. Summer indoor design temperature should be maintained at 75 degrees Fahrenheit (24 degrees Celsius), during occupied conditions and should be maintained at 80 degrees Fahrenheit (26.5 degrees Celsius) during unoccupied conditions. Winter indoor design temperature should be at 72 degrees Fahrenheit (22 degrees Celsius) during occupied conditions and should be maintained at 65 degrees Fahrenheit (18.5 degrees Celsius) during unoccupied conditions.

Humidity. Summer design humidity should be maintained at 50 percent during occupied conditions and should be maintained at 45 percent during unoccupied conditions. Winter design humidity should be maintained at 30 percent in occupied mode.

Dewpoint. The indoor dew point temperature during occupied or unoccupied conditions should be limited to 55 degrees Fahrenheit (12.8 degrees Celsius).

Outdoor Air Design Criteria. Refer to GSA PBS P-100.

Ventilation. The minimum outdoor air volume to be provided should be in accordance with the ASHRAE 62.1 adopted by the GSA PBS P-100 standards. Also refer to room data sheets for air changes per hour.

11. Electrical – Lessor will be responsible for providing housekeeping and utility outlets within the space which will be in addition to tenant required outlets. Locations of these outlets to be approved by court representatives during the design phase. All receptacle power shall be 20amp service unless otherwise required for tenant equipment. Junction boxes shall be provided for modular systems furniture, security equipment, and AV equipment as required and connected to building power source.

12. Server Rooms, Telecommunication and USMS Control Rooms A secured-entrance room is required to house equipment from telecommunications and data service providers and the demarcation point. The main telecommunications room should be centrally located to maintain recommended cabling distances and may include a cross-connect for an adjacent equipment distribution area. Card readers should be utilized to track those entering the telecommunications rooms. Space requirements should provide flexibility for future improvements to the telecommunications system.

These spaces require supplemental 24/7 cooling to provide proper air-conditioning while the main building mechanical systems are shut down. Additionally, server rooms should be on emergency power systems to prevent a lapse in service.

(Refer to consolidated emergency power requirements in the GSA section of the RLP.) The smoke and heat sensor activation should be integrated into the building's fire and life safety system.

Server rooms should be designed to maintain the following temperature and humidity conditions: Temperature: 18-27° C (64-81° F) dry bulb. Maximum relative humidity: 60 percent Minimum dew point: 5.5° C (42° F). Maximum dew point: 15° C (59° F).

INITIALS _____ & _____ LEASE No. __________ Offeror/Gov. Page: 4 Date

PART A:

General Notes (Continued)

13. Lighting - the layout of light fixtures should take into consideration the location of furniture, shelves, bookcases, and equipment and must meet minimum Design Guide footcandle criteria. Building standard light fixtures are acceptable in most areas except as noted otherwise on the room-by-room requirements summary and/or in the Appendix individual room attribute sheets.

14. Telecommunications – The court will provide a telecommunications design consultant (RCDD) to develop a network cabling design for court spaces only based on final space layouts and outlet locations. The lessors design team will be requested to provide electronic files of floor backgrounds for the RCDD’s use in preparing cabling design drawings. The lessor will be requested to obtain cost proposals from qualified subcontractors for cabling installation and associated work based on the design consultants design/bid cabling package. Separate funding will be provided by the courts for cabling installation.

The lessor’s design team is responsible for the construction infrastructure for cable distribution into the project construction documents. The infrastructure will include conduit within walls, back boxes, pull strings and distribution pathways (cable trays and/or j-hooks) from telecommunication rooms to outlet locations dispersed across court occupied spaces. The pathway design shall conform with EIA/TIA standards. The quantity of estimated telephone/data drops are included in the following room descriptions.

15. Public Address system – As part of the Tenant Improvement Allowance, the Lessor shall install a Public Address ("PA") system for roughly 16,000 SF of occupied space for Bankruptcy. The PA system must have the ability to attach multiple microphones to an input from the Lobby and the CSO Control room. The PA system may be powered by battery back-up or tied into emergency power, whichever is the least expensive and least disruptive method to enable emergency service.

The PA system must include the following, but not limited to power, speakers, cabling (or wireless), head end equipment, software, amplification as required by the system. The Lessor shall coordinate training for the tenants.

16. Audio/visual AV systems – The court will provide an AV design consultant to develop the design solutions for AV systems for court spaces. The bankruptcy courtroom and its associated support spaces will be the primary AV locations.

The court AV design consultant will provide to the lessor’s design team, design intent drawings and narrative of the required infrastructure to support the specific equipment design planned. It is the responsibility of the lessor to incorporate those infrastructure requirements into the construction documents for the project. The infrastructure will consist of conduits, recessed floor boxes, outlet boxes, raceways, speaker backboxes, pull strings and similar items to support the installation of AV equipment.

Separately, the AV design consultant will prepare an equipment design which will be shared with the lessor for coordination and information. The court intends to separately contract for the installation of AV equipment and complete the installation with a government vendor near around the substantial completion of the courtroom and other spaces. The room and station descriptions include a description of anticipated AV components, which will be finalized with the courts AV designers design documents and coordination with the lessor’s design team.

17. Security – The U.S. Marshals Service (USMS) is responsible for all security related aspects of the design and equipment.

The USMS will note locations of security equipment on the final space plan. The equipment will require conduit, boxes, pull string and electrical to be provided by the Lessor. The USMS will contract out to a separate vendor for the purchase and installation of the equipment. Equipment noted in the room attribute sheets is for infrastructure information only and will need to be coordinated with the USMS during design. Refer to Design Guide, Chapter 16, for additional guidance.

Door Hardware/Security – Unless otherwise noted, all doors are to be provided with a mortised lockset. Refer to the Design Guide for clarification of lockset types between rooms. Access control is to be provided where required per USMS Publication 64 - Requirements and Specifications for Special Purpose and Support Space Manual, Volume 3 and as noted in this document.

Parking – Secure parking must be provided for designated use by the judge. Ideally such parking would be located

INITIALS _____ & _____ LEASE No. __________ Offeror/Gov. Page: 5 Date

PART A:

General Notes (Continued) within a separated walled enclosure with continuous USMS security camera coverage. Additionally, this space should have a direct secure connection to the judge’s elevator (if one exists). However, as such arrangements are not always possible in commercial parking lots; the separate enclosure may be waived, provided the parking remains structured and reserved. Outdoor fenced parking may be considered if no structured parking exists. In all cases, the government reserves the right to install a security camera to monitor the area and to determine if the proposed parking provides an acceptable level of safety.

Judge’s elevator – Per the Design Guide and the USMS Publication 64, a separate elevator is to be provided for the judge’s secure path of travel from the secure parking area to the chambers. Ideally, a separate elevator will be allocated for this use. However, in an existing commercial tenancy, this may not be feasible. In that case, alternate operational accommodation augmented with security cameras, will be determined during the design of the facility by the government representatives.

18. Signage Signage at the building entry. A building directory should be located near the main public entrance. The directory should contain a diagram listing all the major building components. This directory, which may be integrated into an information booth or kiosk, should be located in an area seen by members of the public after they have been screened.

Floor Directories. Smaller directories should be provided in each elevator lobby with information about the various occupants of that floor. Arrows should be grouped in similar directions to facilitate communication.

Courtroom Entry Signage - All signs outside courtroom doors should be of uniform appearance. The courtroom numbering system should be displayed at the top and in the largest font size.

Regulatory Signage

Room Identification signage

19. Adjacencies – Refer to diagrams in the Design Guide for general guidance on adjacencies between rooms within each division. Where special conditions exist, refer to the individual adjacency notes in the room descriptions.

20. All tenant spaces to be provided with building standard window coverings.

21. Schedule – The offeror’s architect will incorporate the design and review periods required by the government’s audio-visual and telecommunications design consultants into the overall design and documentation schedule to allow for timely and thorough coordination of these components with the rest of the design. The offeror’s contractor shall incorporate the installation of government provided audio-visual equipment and security equipment into the schedule in order to allow timely installation of equipment.

PART B: ROOM-BY-ROOM REQUIREMENTS SUMMARY

Court Shared Support Space 1123 Bankruptcy Clerk 7037 Bankruptcy Judge Chambers Suites 2702 Bankruptcy Judge Courtroom, Associated Spaces 4487

15349

Other

QTY.

USF

Space Std.

USF

Circ.

Factor

TOT. SF/

Space Type

Floor Finish Wall Finish Ceiling STC Door Power/

Data Special Outlets

Mech/ Plmbg.

Equipm't Special Requirements or Planning Info.

COURT SHARED SUPPORT SPACE

Attorney Work Room 0 0 0 0.35 0 CPT PT ACT 45 Rated Multi-purpose 1 200 200 0.35 270 LVT PT ACT 45 Rated Add CFM Lactation Room 1 75 75 0.35 101 CPT PT ACT sink mini-refrigerator NIC IT Work Room/Help Desk 1 150 150 0.35 203 non-static PT ACT (6) double duplex, 3 dedicated circuits Telecommunications Rooms 1 120 120 0.25 150 non-static PT ACT Plywood all walls Server Room (may be shared w/Telcom) 1 320 320 0.25 400 non-static & PT ACT Plywood all walls

1123 raised floor

BANKRUPTCY JUDGES CHAMBER SUITES

a Judge's Chambers Office 1 400 400 0.2 480 CPT/wood base chair rail ACT/DW 55 Rated sep.zone CPT pad, shelving per USCDG. Sep. Zone for off hours

Other: Infrastructure for Speaker interconnect with Courtroom b Judge's Private Toilet 1 56 56 0.2 67 CT CT/PT DW 55 Rated GFI Fixtures Fan Mirror, Light Sconces, Accessories c Vestibule 1 50 50 0.2 60 CPT/wood base PT/wallcovering ACT 55 Rated d Reception Area 1 100 100 0.2 120 CPT/wood base PT/wallcovering ACT 40 Rated e Coat Closet 1 10 10 0.2 12 CPT/wood base PT ACT Shelf and Pole, Additional shelving f Judicial Assistant Work Space 1 120 120 0.2 144 CPT/wood base PT/wallcovering ACT 40 Rated g Filing Room 1 60 60 0.2 72 VCT or LVT PT ACT h Printer/Copier/Fax Area 1 60 60 0.2 72 VCT or LVT PT ACT Dedicated outlets for equipment i Storage 1 80 80 0.2 96 VCT or LVT PT ACT j Service Unit 1 20 20 0.2 24 VCT or LVT PT ACT Sink Disposer Kitch. App.NIC, Full stone backsplash, Stone countertops

Conference/Reference Room 1 240 240 0.2 288 CPT/wood base PT/wallcovering ACT 55 Rated 4 floor outlets Recessed Wall Box for IT/AV/Monitor

Law Clerk Office 1 150 150 0.2 180 CPT/wood base PT ACT 45 Rated Visiting Judges' Chambers Suite 1 906 906 0.2 1087 a-j a-j a-j 55 Rated Suite similar to spaces a-j

2,702 COURTROOM, ASSOC. SPACES and JURY FACILITIES

Courtroom 1 1,800 1800 0.35 2430 CPT/wood base Wood/Fabric/PT/ ACT/DW 60 Rated Wallcovering

Soundlock 1 80 80 0.25 100 CPT/wood base Wood/PT DW 60 Rated

Attorney/Witness Room 2 150 300 0.35 405 CPT/wood base PT ACT 60 Rated Public Waiting Area 1 400 400 0.35 540 CPT/wood base Chair rail/PT/ wallcovering

ACT/DW

Equipment Storage Room 1 100 100 0.35 135 VCT or LVT PT ACT Exhibits Storage 1 50 50 0.35 68 VCT or LVT PT ACT Staff Toilets 2 56 112 0.35 151 VCT or LVT PT ACT 55 Rated GFI Privacy lock with occupancy indicators Mediation Room 1 150 150 0.35 203 CPT PT ACT 55 Rated infrastructure for AV Direct access from Courtroom to judges circulation Court Reporter 0 150 0 0.35 0 CPT PT ACT Shared Work Room 1 100 100 0.35 135 CPT PT ACT 40 Rated Transcriber/Typist Workstation 1 48 48 0.35 65 CPT PT ACT

Infrastructure for security screening equipment, public directory monitor and

Size and Quantity Finishes Systems/Equipmt.

Refer to US Court Design Guide for sample layout of bench, rails and seating. Spectator seating for 60 Finishes include wood and fabric wall panels, wood benches, jury and spectator rails and gates. 2-4" high access flooring in courtroom well area for cable and conduit raceways. Access flooring shall extend under all courtroom components providing cable and conduit access back to the telecom/A/V control racks. Provide vision panels in d

Floor outlets, Cable ways for presentation technology in bench, rails and courtroom well. Speaker system. Virtual judge monitor (requires millwork modifications with lift).

Other: CPT is broadloom, Crown moldings, Wall covering above chair rail and laminate below.

Other: Accent/Decorative lighting

Other: Sidelight or Vision panel in door

Other: 6"x 18" impact-resist glass window for doors into Crtrm. Use Magistrate Courtroom layout example in the Appendix. This Courtroom will include a jury box.

Supp. AC for telecom and server room may be shared

Coord infrastructure req. with District IT staff.

RLP NO. 0CA3254

Lessor: ________ Government: ________ Exhibit B-II, Agency Requirements

PART B: ROOM-BY-ROOM REQUIREMENTS SUMMARY

Other

QTY.

USF

Space Std.

USF

Circ.

Factor

TOT. SF/

Space Type

Floor Finish Wall Finish Ceiling STC Door Power/

Data Special Outlets

Mech/ Plmbg.

Equipm't Special Requirements or Planning Info.

Size and Quantity Finishes Systems/Equipmt.

Public/Attorney Coat Closet 1 20 20 0.35 27 CPT PT ACT Shelf & pole, co-ord additional shelving req. during design Audiovisual Equipment Room 1 120 120 0.35 162 VCT or LVT PT ACT

3,280 4420

BANKRUPTCY CLERK

Clerk of Court Visiting Office 1 150 150 0.32 198 CPT PT ACT 40 Rated Chief Deputy Clerk 1 180 180 0.32 238 CPT PT ACT 40 Rated Manager 1 180 180 0.32 238 CPT PT ACT 40 Rated First-Line Supervisors 1 180 180 0.32 238 CPT PT ACT 40 Rated Prof., Admin and Line Positions 1 150 150 0.32 198 CPT PT ACT 40 Rated Executive Secretary/Reception Area 0 0 0 0.32 0 First-Line Spvsr. 2 96 192 0.32 253 CPT PT ACT Deputy Clerk 8 64 512 0.32 676 CPT PT ACT Courtroom Deputy 1 150 150 0.32 198 CPT PT ACT 40 Rated

Bulk Storage 1 210 210 0.25 263 VCT or LVT PT ACT Archival Storage 1 150 150 0.25 188 VCT or LVT PT ACT

Public Scanning & Pay Copier 1 118 118 0.32 156 VCT or LVT PT ACT Queuing Area 1 150 150 0.32 198 VCT or LVT PT ACT Public Cntr./Clerk/Cashier Stations 1 200 200 0.32 264 LVT/CPT PT ACT 4 "L" shape plam stations/hi-lo cabinets/glass. Sim to A-16 Records Exam/Public Fax/Computer 1 105 105 0.32 139 LVT PT ACT

Evidence Vault 1 80 80 0.32 106 VCT or LVT PT ACT Deck to deck partitions enclose the room Equipment Storage 1 50 50 0.32 66 VCT or LVT PT ACT Work Area 1 210 210 0.32 277 VCT or LVT PT ACT 40 Rated High Volume Copier Area 0 0 0 0.32 0 VCT or LVT PT ACT Medium Volume Copier Area 1 80 80 0.32 106 VCT or LVT PT ACT 40 Rated 20A ded. Dedicated Circuits for equipment Low Volume Copier Area 0 0 0 0.32 0 VCT or LVT PT ACT Mail Work Area 1 100 100 0.32 132 VCT or LVT PT ACT 40 Rated Plam work counters all walls, Mail sorter slots Printer/Copier/Fax Area 1 60 60 0.32 79 VCT or LVT PT ACT 20A ded. Dedicated Circuits for equipment Safe 1 20 20 0.32 26 VCT or LVT PT ACT Shredder 1 25 25 0.32 33 VCT or LVT PT ACT Supplies 1 50 50 0.32 66 VCT or LVT PT ACT Staff Breakroom 1 200 200 0.32 264 VCT or LVT PT ACT 40 Rated GFI Sink Disposer Kitch. App.NIC, Plam Cabinets, Tile Back splash, solid surface countertops, waterliner for tenant provided refrigerator, dedicated circuits for appliances

Coat Closet 1 20 20 0.32 26 LVT or CPT PT ACT Shelf & Pole Staff Toilets 4 56 224 0.32 296 VCT or LVT or CT PT DW 55 Rated GFI Fixtures Fan Mirror, Light feature, Accessories Secured Records Storage 1 9 9 0.32 12 VCT or LVT PT ACT Active Records Storage 30 9 270 0.32 356 VCT or LVT PT ACT Inactive Records Storage 45 9 405 0.32 535 VCT or LVT PT ACT Exhibits Storage Room 1 100 100 0.32 132 VCT or LVT PT ACT Financial Vault 1 150 150 0.32 198 VCT or LVT PT ACT Computer Training Room 1 200 200 0.32 264 CPT PT ACT 55 Rated 4 floor outlets Recessed Wall Box for IT/AV/Monitor Conference Room 1 300 300 0.32 396 CPT PT ACT 55 Rated 4 floor outlets Recessed Wall Box for IT/AV/Monitor Transfer Box Storage 1 50 50 0.32 66 VCT or LVT PT ACT (FAC ID) Room 1 120 120 0.32 158 CPT PT ACT

7,037

RLP NO. 0CA3254

Lessor: ________ Government: ________ Exhibit B-II, Agency Requirements

U.S. Courts Design Guide | Revised 2021 A-1

APPENDIX: ROOM DATA SHEETSA The following room data sheets (RDSs) are a compilation of information contained in the Design Guide that identify spatial and programmatic requirements by space type. For simplification and clarity purposes, some spaces have been combined into a single RDS.

General Courthouse Spaces Chapter 4 Courtrooms Chapter 5 Jury Assembly Suite Chapter 6 Judges’ Chambers Suites Chapter 7 Court Library Spaces Chapter 8 Associated Appeals Clerks’ Office Spaces Chapter 9 Associated Probation and Pretrial Services Office Spaces Chapter 10 Associated Other Court Unit Office Spaces Chapter 11 Shared Support Spaces

Topics:

Space and Facilities Appendix B-261

U.S. Courts Design Guide | Revised 2021 A-2Room Data Sheets |

Definitions, Legends and Symbols

Security Definitions

• Public 1 - Unscreened Public Access

• Public 2 - Screened Public Access

• Public 3 - Screened Public Access, Locked When Not in Use

• Restricted 1 - Restricted Access, Uncontrolled

• Restricted 2 - Restricted Access, Remote Access Control

• Restricted 3 - Restricted Access, Direct Access Control/Key Lock

• Restricted 4 - Restricted Access, Counter/Window Service

• P - Privacy Lock

• Secure 1 - Secure Access, Authorized Staff

• Secure 2 - Secure Access, Prisoner/Security Staff

Symbols

Handicap Spectator Seating

5’-0” Wheelchair Turning Radius

General Notes:

• The graphics on the RDS are not to scale and are for illustrative purposes only.

• The RDS are meant to be used as a guideline. It is essential that the user obtain additional information from the court, the General Services Administration (GSA), and other participants and users to tailor the design response to the specific court requirements.

• The RDS should be used in conjunction with other facility design standards including but not limited to: The U.S. Courts Design Reference Manual and applicable GSA

PBS P-100.

• The interpretation and application of the information provided in the RDS into specific design solutions will require the overall review & confirmation of the design by the court, the Administrative Office of the U.S. Courts (AOUSC), the GSA, and the United States Marshals Service (USMS).

• The design architect is responsible for the coordination and conformance with the Design Guide, and all applicable laws, codes regulations, and governmental facility standards.

• Finishes indicated on the RDS show a range of acceptable finishes per space;

however, this list should not be considered comprehensive. Final finish selection should be determined by the design architect and project stakeholders.

• Fixtures, furniture, and equipment (FFE) requirements should be determined on a project-to-project basis to satisfy the local needs. FFE shown on the graphics is notional and should not be considered comprehensive.

• Furniture, accessories, and equipment indicated with an asterisk (*) is funded by

GSA.

• Furniture shown in the RDS are general guidelines of potential layouts. Final furniture design and procurement will be determined by individual project requirements.

Space and Facilities Appendix B-262

RLP NO. 0CA3254 Lessor: ________ Government: ________ Exhibit B-II, Agency Requirements https://www.gsa.gov/real-estate/design-construction/engineering-and-architecture/facilities-standards-p100-overview https://www.gsa.gov/real-estate/design-construction/engineering-and-architecture/facilities-standards-p100-overview

U.S. Courts Design Guide | Revised 2021 A-3 Room Data Sheets|

Finish Legend Finish Legend (cont.)

Room Data Sheet Space Nomenclature

The space nomenclature is used for the General Courthouse Spaces section and denotes a space type followed by a square footage for the space. The remaining Room Data Sheet sections are chapter specific and are noted with the corresponding chapter.

Abbreviation Material

ACP Acoustical Ceiling Panel or Tile

AWP Acoustical Wall Panel

CPT Carpet

CR Chair Rail

CT Ceramic Tile

FWC Fabric Wall Covering

GL Glass

GWB Gypsum Wall Board

MTL Metal

PLAS Plaster

PLY Plywood on MTL Studs

PNT-1 Latex paint with eggshell finish. Preferred Finish, unless noted otherwise.

PNT-2 Latex paint with semi-gloss finish. To be used in wet areas such as service units and restroom wet walls.

PNT-3 Water-based catalyzed epoxy or equivalent. To be used for the urinalysis lab.

RAF Raised Access Floor

ST Stone

SVT Solid/Premium Vinyl Tile

SV Sheet Vinyl

TZ Terrazzo

VCT Vinyl Composition Tile

V/RB Vinyl/Rubber Base

Abbreviation Space Type

CR Conference Room

OS Office Support (Shared space ie., Copier, Printer, Faxes)

PO Private Office

REC Reception

SL Soundlock

ST Storage

SU Service Unit

VT Vault

WS Workstation

Abbreviation Material

WD Wood

WD Wainscot Wood Wainscot

Space and Facilities Appendix B-263

U.S. Courts Design Guide | Revised 2021 A-4Room Data Sheets |

This page intentionally left blank.

Space and Facilities Appendix B-264

U.S. Courts Design Guide | Revised 2021 A-5 Room Data Sheets|

General Courthouse Spaces Space and Ceiling Requirements

Reception/Waiting, per person 15 NSF (1.4 Nm2) Minimum Area Required 150 NSF (13.9 Nm2)

Architectural:

General Requirements:

Security Level: Public 3, Restricted 1, 4 Adjacent to: Public & Restricted Circulation, Counter Ceiling Height: 10’-0” Acoustics NIC 25 - Normal

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

PUBLIC

CIRCULATION

COUNTER

RESTRICTED

CIRCULATION

REC - 15

Space and Facilities Appendix B-265

U.S. Courts Design Guide | Revised 2021 A-6Room Data Sheets |

Space and Ceiling Requirements

Reception/Waiting Area 105 NSF (9.8 Nm2)

Architectural:

General Requirements:

Security Level: Public 3, Restricted 1, 4 Adjacent to: Public & Restricted Circulation, Counter Ceiling Height: 10’-0” Acoustics NIC 25 - Normal

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

REC - 105

PUBLIC

CIRCULATION

COUNTER

RESTRICTED

CIRCULATION

Space and Facilities Appendix B-266

U.S. Courts Design Guide | Revised 2021 A-7 Room Data Sheets|

Space and Ceiling Requirements

Reception/Waiting Area 150 NSF (14 Nm2)

Architectural:

General Requirements:

Security Level: Public 3, Restricted 1, 4 Adjacent to: Public & Restricted Circulation, Counter Ceiling Height: 10’-0” Acoustics NIC 25 - Normal

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

REC - 150

PUBLIC

CIRCULATION

COUNTER

RESTRICTED

CIRCULATION

Space and Facilities Appendix B-267

U.S. Courts Design Guide | Revised 2021 A-8Room Data Sheets |

Space and Ceiling Requirements

Soundlock 50 NSF (4.6 Nm2) Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0” Acoustics NIC 55-60 - Confidential

Finishes:

Wall: PNT-1 Floor: CPT, WD Base: WD, V/RB Ceiling: ACP, PNT-1

Building Systems:

Illumination:

Horizontal: 30-40 fc Vertical: 5-10 fc Lighting Control: No

SL - 50

4' - 0" MINRESTRICTED

CIRCULATION

Space and Facilities Appendix B-268

U.S. Courts Design Guide | Revised 2021 A-9 Room Data Sheets|

Space and Ceiling Requirements

Soundlock 80 NSF (7.4 Nm2)

Architectural:

General Requirements:

Security Level: Public 3 Ceiling Height: 10’-0” Acoustics NIC 55-60 - Confidential

Finishes:

Wall: WD, ST, MTL, AWP, PLAS, PNT-1 Floor: CPT, WD Base: WD, V/RB Ceiling: WD, MTL, ACP, PNT-1

Building Systems:

Illumination:

Horizontal: 30-40 fc Vertical: 5-10 fc Lighting Control: Yes

4'-0" MIN

SL - 80

Space and Facilities Appendix B-269

U.S. Courts Design Guide | Revised 2021 A-10Room Data Sheets |

Space and Ceiling Requirements

Storage, per shelf unit 9 NSF (0.84 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0”

Finishes:

Wall: Varies (based on location) Floor: Varies (based on location) Base: Varies (based on location) Ceiling: Varies (based on location)

ST - 09

3' - 0"

3'

0"

Legend:

File Cabinets1

Space and Facilities Appendix B-270

U.S. Courts Design Guide | Revised 2021 A-11 Room Data Sheets|

Space and Ceiling Requirements

Coat Closet 20 NSF (1.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1 Ceiling Height: 10’-0”

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP, PNT-1

Space Notes:

1. Provide three linear inches of coats space (75mm) per juror (jury facilities).

ST - 20

10' - 0"

2'

0"

Space and Facilities Appendix B-271

U.S. Courts Design Guide | Revised 2021 A-12Room Data Sheets |

10' - 0"

5'

0"

General Courthouse Spaces Space and Ceiling Requirements

Storage 50 NSF (4.7 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0”

Finishes:

Wall: PNT-1 Floor: VCT Base: V/RB Ceiling: ACP

Legend:

Shelves

ST - 50

Space and Facilities Appendix B-272

U.S. Courts Design Guide | Revised 2021 A-13 Room Data Sheets|

8'

0"

General Courthouse Spaces Space and Ceiling Requirements

Storage 80 NSF (7.4 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0”

Finishes:

Wall: PNT-1 Floor: VCT Base: V/RB Ceiling: ACP

Fixtures, Furniture, and Equipment (FFE)

• Shelves: Open shelves 18” (450 mm) deep on 2-3 walls, movable or fixed

Legend:

Shelves

ST - 80

Space and Facilities Appendix B-273

U.S. Courts Design Guide | Revised 2021 A-14Room Data Sheets |

10' - 0"

Storage Room 100 NSF (9.3 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0”

Finishes:

Wall: PNT-1 Floor: VCT Base: V/RB Ceiling: ACP

Fixtures, Furniture, and Equipment (FFE)

• Shelves: Open shelves 18” (450 mm) deep on 2-3 walls, movable or fixed

Legend:

Movable Shelves

General Courthouse Spaces Space and Ceiling Requirements

ST - 100

Space and Facilities Appendix B-274

U.S. Courts Design Guide | Revised 2021 A-15 Room Data Sheets|

General Courthouse Spaces Space and Ceiling Requirements

ST - 150

Storage Room 150 NSF (13.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0”

Finishes:

Wall: PNT-1 Floor: VCT Base: V/RB Ceiling: ACP

Fixtures, Furniture, and Equipment (FFE)

• Shelves: Open shelves 18” (450 mm) deep on 2-3 walls, movable or fixed

Legend:

Movable Shelves1

Space and Facilities Appendix B-275

U.S. Courts Design Guide | Revised 2021 A-16Room Data Sheets |

5' - 0"

6'

0"

1'

0"2'

0"

3'

0"

General Courthouse Spaces Space and Ceiling Requirements

Counter Workstations 45 NSF (4.2 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 4 Adjacent to: Reception/Waiting

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

Millwork:

• Durable work surface with a divider to the floor below. Accommodate computer monitor, keyboard, and mouse at staff side of counter.

• Where ballistic and break-resistant glass is provided, counter should accommodate document-size deal tray transaction opening for each station.

Public Queuing Area Legend:

Transaction Tray

Security Glazing with Natural Voice Communication

Cash Drawer

WS - 45

Space and Facilities Appendix B-276

U.S. Courts Design Guide | Revised 2021 A-17 Room Data Sheets|

6' - 0"

8'

0"

Workstation 48 NSF (4.5 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1

Finishes:

Wall: Varies (based on location) Floor: Varies (based on location) Base: Varies (based on location) Ceiling: Varies (based on location)

Fixtures, Furniture, and Equipment (FFE)

• 6’ x 8’ systems furniture workstation

• Chair

Legend:

Systems Furniture

Chair

General Courthouse Spaces Space and Ceiling Requirements

WS - 48

Space and Facilities Appendix B-277

U.S. Courts Design Guide | Revised 2021 A-18Room Data Sheets |

Space and Ceiling Requirements

8' - 0"

8'

0"

Legend:

Systems Furniture

Chair

WS - 64

Workstation 64 NSF (5.8 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1

Finishes:

Wall: Varies (based on location) Floor: Varies (based on location) Base: Varies (based on location) Ceiling: Varies (based on location)

Fixtures, Furniture, and Equipment (FFE)

• 8’ x 8’ systems furniture workstation

• Chair

Building Systems:

Security:

• Security intercom (associated chamber space)

• Duress alarm (associated chamber space)

• CCV monitor (associated chamber space)

• Remote door - release mechanism (associated chamber space)

Space and Facilities Appendix B-278

U.S. Courts Design Guide | Revised 2021 A-19 Room Data Sheets|

8' - 0"

General Courthouse Spaces Space and Ceiling Requirements

Workstation 96 NSF (8.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1

Finishes:

Wall: Varies (based on location) Floor: Varies (based on location) Base: Varies (based on location) Ceiling: Varies (based on location)

Fixtures, Furniture, and Equipment (FFE)

• 8’ x 12’ systems furniture workstation

• Chair

Legend:

Systems Furniture

Chair

WS - 96

Space and Facilities Appendix B-279

U.S. Courts Design Guide | Revised 2021 A-20Room Data Sheets |

Space and Ceiling Requirements

Executive Secretary 170 NSF (15.8 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1 Adjacent to: Unit Executive Private Office

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

Building Systems:

Security:

• Duress alarm

Fixtures, Furniture, and Equipment (FFE)

• 6’ x 8’ systems furniture workstation

• Chair

10' - 0"

UNIT EXECUTIVE

PRIVATE OFFICE

WS - 170

Legend:

Systems Furniture

Chair

Duress Alarm

Space and Facilities Appendix B-280

U.S. Courts Design Guide | Revised 2021 A-21 Room Data Sheets|

Space and Ceiling Requirements

Private Office 100 NSF (9.3 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1 Ceiling Height: 9’-0” Acoustics NIC 35 - Normal

Finishes:

Wall: PNT-1, CR (Judge’s Chambers Suite) Floor: CPT Base: V/RB Ceiling: ACP

10' - 0"

Legend:

Desk

Chair

PO - 100

Space and Facilities Appendix B-281

U.S. Courts Design Guide | Revised 2021 A-22Room Data Sheets |

Space and Ceiling Requirements

Private Office 120 NSF (13.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 1 Adjacent to:

Ceiling Height: 9’-0” Acoustics NIC 35 - Normal (Probation and Pretrial Services Offices)

Finishes:

Wall: PNT-1, CR (Judge’s Chambers Suite) Floor: CPT Base: V/RB Ceiling: ACP

10' - 0"

Legend:

Desk

Chair

PO - 120

Space and Facilities Appendix B-282

U.S. Courts Design Guide | Revised 2021 A-23 Room Data Sheets|

Private Office 150 NSF (13.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 9’-0” Acoustics NIC 35 - Normal (Probation and Pretrial Services Offices)

NIC 40 - Normal (Court of Appeals Clerks’ Offices) NIC 55 - Confidential (Federal Public Defender’s Trial

Preparation)

Finishes:

Wall: PNT-1, CR (Judge’s Chambers Suite) Floor: CPT Base: V/RB Ceiling: ACP

Building Systems:

Security:

• CCV monitor (law clerk office)

• Duress alarm (law clerk office, professional staff)

• Security intercom (law clerk office)

• Remote door - release mechanism (law clerk office)

10' - 0"

General Courthouse Spaces Space and Ceiling Requirements

Legend:

Desk

Chair

File Cabinet

PO - 150

Space and Facilities Appendix B-283

U.S. Courts Design Guide | Revised 2021 A-24Room Data Sheets |

12' - 0"

General Courthouse Spaces Space and Ceiling Requirements

Private Office 180 NSF (16.7 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 9’-0” Acoustics NIC 35 - Normal (Probation and Pretrial Services Offices)

NIC 40 - Normal (Court of Appeals Clerks’ Offices) NIC 55 - Confidential (Pre-Argument/Conference Attorney)

Finishes:

Wall: PNT-1, CR (Judge’s Chambers Suite) Floor: CPT Base: V/RB Ceiling: ACP

Building Systems:

Security:

• Duress alarm (deputy circuit librarian)

PO - 180

Legend:

Desk

Chair

File Cabinet

Space and Facilities Appendix B-284

U.S. Courts Design Guide | Revised 2021 A-25 Room Data Sheets|

Space and Ceiling Requirements

Private Office 240 NSF (22.3 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 9’-0” Acoustics NIC 35 - Normal (Probation and Pretrial Services Offices)

NIC 40 - Normal (Court of Appeals Clerks’ Offices) NIC 55 - Confidential (Pre-Argument/Conference Attorney and Bankruptcy Administrator)

Finishes:

Wall: PNT-1, CR (Judge’s Chambers Suite) Floor: CPT Base: V/RB Ceiling: ACP

Building Systems:

Security:

• Duress alarm (circuit librarian)

17' - 0"

Legend:

Desk

Chair

File Cabinet

Table

Duress Alarm

1 4

2 5

PO - 240

Space and Facilities Appendix B-285

U.S. Courts Design Guide | Revised 2021 A-26Room Data Sheets |

Space and Ceiling Requirements

Safe or Vault 20 NSF (1.6 Nm2)

Architectural:

Finishes:

Wall: Varies (based on location) Floor: Varies (based on location) Base: Varies (based on location) Ceiling: Varies (based on location)

Space Notes:

1. Partition construction:

• Slab to slab, (2) layers 5/8” type X GWB both sides, 3-5/8” 18-GA steel studs 16” o.c

• Maximum security steel mesh (ASM.50-13F) provided on the inner side of wall board

• Security screen attached to floor slab and structure above, welded together on studs to form a continuous barrier against entry

2. Door construction:

• UL-labeled class B, 18-gauge, metal fire doors constructed with 14-gauge hardware reinforcements

• 16-gauge steel frames with three hinges, high quality, three-tumbler combination lock to secure the door for after-hours protection

• Key lock to be provided for business hours after the alarm has been turned off and combination lock is dialed in., emergency egress hardware

3. Reference GSA PBS P-100 for HVAC, telecom, fire alarm, data, and security system requirements

VT - 20

5' - 0"

4'

0"

5' - 0"

4'

0"

Legend:

Under-Counter Safe

Standalone Safe

Space and Facilities Appendix B-286

U.S. Courts Design Guide | Revised 2021 A-27 Room Data Sheets|

Space and Ceiling Requirements

Vault 80 NSF (7.4 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Adjacent to: Restricted Corridor Ceiling Height: 9’-0”

Finishes:

Wall: PNT-1 Floor: VCT Base: V/RB Ceiling: PNT-1

Building Systems:

Life Safety:

Fire Rating: 2 hour partition

Security:

Duress Alarm: Yes

Space Notes:

1. Partition construction:

• Slab to slab, (2) layers 5/8” type X GWB both sides, 3-5/8” 18-GA steel studs 16” o.c

• Maximum security steel mesh (ASM.50-13F) provided on the inner side of wall board

• Security screen attached to floor slab and structure above, welded together on studs to form a continuous barrier against entry

2. Door construction:

• UL-labeled class B, 18-gauge, metal fire doors constructed with 14-gauge hardware reinforcements

• 16-gauge steel frames with three hinges, high quality, three-tumbler combination lock to secure the door for after hours protection

• Key lock to be provided for business hours after the alarm has been turned off and combination lock is dialed in., emergency egress hardware

3. Reference GSA PBS P-100 for HVAC, telecom, fire alarm, data, and security system requirements

VT - 80

GENERAL COURTHOUSE SPACES - VAULT 80 SF

8' - 0"

Space and Facilities Appendix B-287

U.S. Courts Design Guide | Revised 2021 A-28Room Data Sheets |

Space and Ceiling Requirements

Vault 150 NSF (14 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Adjacent to: Restricted Corridor Ceiling Height: 9’-0”

Finishes:

Wall: PNT-1 Floor: VCT Base: V/RB Ceiling: ACP

Building Systems:

Security:

Duress Alarm: Yes

Space Notes:

1. Partition construction:

• Slab to slab, (2) layers 5/8” type X GWB both sides, 3-5/8” 18-GA steel studs 16” o.c, 2-hour rated wall

• Maximum security steel mesh (ASM.50-13F) provided on the inner side of wall board

• Security screen attached to floor slab and structure above, welded together on studs to form a contiguous barrier against entry

2. Door construction:

• UL-labeled class B, 18-gauge, metal fire doors constructed with 14-gauge hardware reinforcements

• 16-gauge steel frames with three hinges, high quality, three-tumbler combination lock to secure the door for after hours protection

• Key lock to be provided for business hours after the alarm has been turned off and combination lock is dialed in., emergency egress hardware

3. Reference GSA PBS P-100 for HVAC, telecom, fire alarm, data, and security system requirements

VT - 150

15' - 0"

Space and Facilities Appendix B-288

U.S. Courts Design Guide | Revised 2021 A-29 Room Data Sheets|

Space and Ceiling Requirements

Conference Room 300 NSF (27.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0” Acoustics NIC 55 - Confidential

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

Building Systems:

Illumination:

Horizontal: 30-50 fc Vertical: 10-15 fc Lighting Control: Yes Emergency Lighting: Yes

Mechanical:

Air Changes: 8/hour

Space Notes:

1. Conference room for meetings with fewer than 20 occupants.

15' - 0"

Legend:

Table

Chairs

Credenza

Monitor

CR - 300

Space and Facilities Appendix B-289

U.S. Courts Design Guide | Revised 2021 A-30Room Data Sheets |

Space and Ceiling Requirements

Conference Room 400 NSF (37.2 Nm2)

Architectural:

General Requirements:

Security Level: Restricted 3 Ceiling Height: 10’-0” Acoustics NIC 55 - Confidential

Finishes:

Wall: PNT-1 Floor: CPT Base: V/RB Ceiling: ACP

Building Systems:

Illumination:

Horizontal: 30-50 fc Vertical: 10-15 fc Lighting Control: Yes Emergency Lighting: Yes

Mechanical:

Air Changes: 8/hour

Space Notes:

1. Conference room for meeting with more than 20 or more occupants.

17' - 0"

Legend:

Table

Chairs

Credenza

Monitor

CR - 400

Space and Facilities Appendix B-290

U.S. Courts Design Guide | Revised 2021 A-31 Room Data Sheets|

Space and Ceiling Requirements

Service Unit 20 NSF (1.9 Nm2)

Architectural:

General Requirements:

Security Level: Restricted Corridor Ceiling Height: 10’-0”

Finishes:

Wall: PNT-2 Floor: VCT Base: V/RB Ceiling: ACP

Building Systems:

Illumination:

Horizontal: 20-30 fc Vertical: 5-10 fc Lighting Control: Yes

Fixtures, Furniture, and Equipment (FFE)

• (1) Optional full-size refrigerator for jurors who bring their own food (jury facilities).

Space Notes:

1. Accommodate a sink, a microwave, a coffeemaker, and potentially vending machines.

Legend:

Full-Size Refrigerator

Sink

Microwave

Coffeemaker

SU - 20

Space and Facilities Appendix B-291

U.S. Courts Design Guide | Revised 2021 A-32Room Data Sheets |

General Courthouse Spaces Space and Ceiling Requirements

Service Unit 100 NSF (9.3 Nm2)

Architectural:

General Requirements:

Security Level: Restricted Corridor Ceiling Height: 10’-0”

Finishes:

Wall: PNT-2 Floor: VCT Base: V/RB Ceiling: ACP

Building Systems:

Illumination:

Horizontal: 20-30 fc Vertical: 5-10 fc Lighting Control: Yes

Fixtures, Furniture, and Equipment (FFE) -(1) Optional full-size refrigerator

Space Notes:

1. Accommodate a sink, a microwave, a coffeemaker, and potentially vending machines.

Legend:

Full-Size Refrigerator

Sink

Microwave

Coffeemaker

SU - 100

Space and Facilities Appendix B-292

U.S. Courts Design Guide | Revised 2021 A-33 Room Data Sheets|

Space and Ceiling Requirements

Staff Break Room 200 Min-600 Max NSF (18.6-55.8 Nm2)

Architectural:

General Requirements:

Adjacent to: Restricted Corridor Ceiling Height: 10’-0”

Finishes:

Wall: PNT-2 Floor: VCT Base: V/RB Ceiling: ACP

Building Systems:

Illumination:

Horizontal: 20-30 fc Vertical: 5-10 fc Lighting Control: Yes

Space Notes:

1. Allocate 25 NSF (2.32 Nm2) for every three staff members, plus 20 NSF (1.9 Nm2) for a service unit.

2. Accommodate a sink, a microwave, a coffeemaker, and potentially vending machines.

Legend:

Full-size refrigerator

Sink

Microwave

Coffeemaker

SU - 200

Space and Facilities Appendix B-293

U.S. Courts Design Guide | Revised 2021 A-34Room Data Sheets |

Printer/Copier/Fax Area 60 NSF (5.6 Nm2) Shredder 25 NSF (2.3 Nm2)

Architectural:

General Requirements:

Adjacent to: Workstations

Finishes:

Wall: Varies (based on location) Floor: Varies (based on location) Base: Varies (based on location) Ceiling: Varies (based on location)

Genera…