Exhibit_B__Electrical_Specifications.pdf
PDF 1 MB Posted
- Attached to
- Cocoa Police Department HVAC Renovations
- Solicitation number
- B-26-12-COC
- Issued by
- Brevard County, Clewiston City, Florida
About this file
This is an Electrical Specifications exhibit for the Cocoa Police Department HVAC Renovations project under the jurisdiction of the City of Cocoa, Florida. The project involves the removal and replacement of three split system DX air conditioning units at the police department facility located at 1226 West King Street, Cocoa, FL 32922. The scope encompasses furnishing and installing three new AC units of appropriate capacity to match or improve upon existing building load requirements, along with all associated electrical work including disconnects, wiring, and connections necessary to power the new units in compliance with current code requirements. Additional deliverables include controls integration with the building automation system or thermostats, HVAC work such as ductwork modifications, refrigerant line sets, and condensate drainage, coordination of any required structural support modifications, testing and balancing to manufacturer specifications, site cleanup, and provision of warranty documentation and as-built information upon project completion. All work shall be performed in accordance with the Construction Plans and applicable codes including EPA refrigerant recovery requirements and the jurisdiction's building standards.
The electrical specifications document outlines the technical requirements and standards that contractors must follow when executing the electrical components of this renovation project. The specifications ensure that all electrical work is brought to current code compliance and integrates properly with the new HVAC equipment. Contractors must coordinate with electrical, controls, and HVAC trades to ensure a complete and functional installation, with all work subject to testing, verification, and inspection to confirm operation meets manufacturer specifications and local regulatory requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
SYMBOL DESCRIPTION
VFD
ELECTRICAL SYMBOL LEGEND
TRANSFORMERT
VARIABLE FREQUENCY DRIVE
NEW (HEAVY, SOLID LINE)
EXISTING TO REMAIN (LIGHT, SOLID LINE)
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
FLEXIBLE CONDUIT
CONDUIT CONTINUED
CONDUIT STUBBED OUT OR UP
CONDUIT TURNING DOWN
CONDUIT TURNING UP
GROUND OR GROUND ROD AS NOTED
CONDUIT EXPOSED
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR
CONDUIT CONCEALED ABOVE CEILING OR IN WALL
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED
30AR
20AF
NF
30AR NON-FUSED DISCONNECT SWITCH, RATING AS NOTED
NF = NON-FUSED
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE
NOTED30/3
0 3R
MCP
AMPERE
RATING
# OF POLES
NEMA STARTER SIZE
FUSED DISCONNECT
BASIC MATERIALS
DEVICE ABBREVIATION TAGS :
CONDUIT SEAL-OFF FITTING
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
3R
3R
AF = AMPERE RATING OF FUSE
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED
CONDUIT HOMERUN TO ELECTRICAL PANEL
EXISTING TO REMAIN ETR
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL
ABBREVIATIONS
ELECTRICAL GENERAL NOTES
10.
11.
12.
13.
14.
COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE.
PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE
REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG
LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR PHASING.
ANY TEMPORARY INTERRUPTION OF POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND
SCHEDULED IN ADVANCE.
COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS (ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL, EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING AND IMPACT FEES.
CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM
INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM DAMAGE OR EXCESSIVE
NOISE THROUGHOUT THE DURATION OF THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR ANY
LOSSES OR ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL CONDITION TO THE SATISFACTION OF THE ARCHITECT/ENGINEER
AND OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE
ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO
PROCEEDING WITH REPAIRS.
COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO BID. CONTRACTOR SHALL
NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET
BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
1.
2.
3.
4.
5.
6.
7.
8.
9.
GENERAL REQUIREMENTS:
THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO
THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP, METHODS
AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL
DIVISIONS AS A WHOLE.
THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF
CONSTRUCTION, METHODS, MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE CONTRACT DOCUMENTS. COORDINATE
EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL, CIVIL AND STRUCTURAL CONTRACT
DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP DRAWINGS AND WORK OF ALL OTHER
DIVISIONS/TRADES.
THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES TO FURNISH AND INSTALL MATERIALS REQUIRED FOR CORRECT INSTALLATION OF A COMPLETE SYSTEM, UNLESS SPECIFICALLY
NOTED OTHERWISE
UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL
TESTING AGENCY
PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE
CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND
WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER.
CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR
THE DURATION OF THIS PROJECT
GUARANTEE ALL MATERIALS AND WORKMANSHIP ARE FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER AND OWNER, UNLESS NOTED OTHERWISE IN DIVISION 1. AT NO ADDITIONAL COSTS, PROVIDE THE CORRECTION OF
ANY DEFECTS INCLUDING REPAIR OR REPLACEMENT.
INCLUDE ALL COSTS ASSOCIATED WITH PERMITS, LICENSES, FEES, INSPECTIONS, TESTING AND
TEMPORARY POWER IN THE BID PRICE, UNLESS NOTED OTHERWISE.
IF HAZARDOUS MATERIALS ARE ENCOUNTERED, COMPLY WITH ALL APPLICABLE RULES, REGULATIONS
AND GUIDELINES CONCERNING REMOVAL, HANDLING, DISPOSAL AND PROTECTION AGAINST
ENVIRONMENTAL EXPOSURE OR POLLUTION. PROVIDE DOCUMENTATION OF SAID COMPLIANCE.
PROVIDE ELECTRONIC SUBMITTALS (PRODUCT DATA & SHOP DRAWINGS) FOR EACH MAJOR COMPONENT
OF THE ELECTRICAL SYSTEM FOR REVIEW BY THE ARCHITECT/ENGINEER AND OWNER. MAJOR
COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO, RACEWAYS, BOXES, WIRE AND CABLE, EQUIPMENT, DEVICES, LIGHT FIXTURES, SWITCHGEAR, PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, FIRE ALARM SYSTEM, ETC. ALL SUBMITTALS ARE TO BE REVIEWED AND APPROVED BY THE CONTRACTOR
FOR CONFORMANCE WITH THE PROJECT REQUIREMENTS PRIOR TO SUBMITTING TO THE
ARCHITECT/ENGINEER. ALLOW A MINIMUM OF TEN (10) BUSINESS DAYS FOR REVIEW BY
ARCHITECT/ENGINEER, UNLESS NOTED OTHERWISE IN DIVISION 1.
THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS
ACCEPTED BY THE ARCHITECT/ENGINEER AND OWNER, THE CONTRACTOR SHALL MAKE ALL
CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND
OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS. WHERE THE
CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST COMPENSATION FROM THE
CONTRACTOR FOR SAID SERVICES.
MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD DOCUMENTS SHALL BE ISSUED TO THE ARCHITECT/ ENGINEER FOR REVIEW AND THEN SUBMITTED TO THE OWNER WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.
PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL ACCEPTANCE.
THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
REQUIRED ROUTINE MAINTENANCE ACTIONS AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME, PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED
SERVICE AGENCY.
INCLUDE ALL COSTS FOR EXCAVATION, SAW CUTTING, DIRECTIONAL BORING, CORE DRILLING, BACKFILLING, SURFACE RESTORATION, REPAIR OF FINISHES, ETC. THAT IS REQUIRED IN ORDER TO MEET
THE PROJECT REQUIREMENTS.
INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR TEMPORARY POWER. ENGINEER OF
RECORD SHALL BE PROVIDED WITH ADDITIONAL COMPENSATION FROM THE CONTRACTOR WHERE
SIGNED & SEALED DRAWINGS ARE REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF
REQUIRED BY THE AHJ FOR THE TEMPORARY POWER.
LOCATE, IDENTIFY, PROTECT AND DOCUMENT ALL UTILITY LINES LOCATED WITHIN THE PROJECT BOUNDARY. FOR LOCATING SITE UTILITIES, CONTACT ALL LOCAL MUNICIPALITIES AND UTILITIES AT LEAST
48 HOURS PRIOR TO DIGGING.
INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES, REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH ALL APPLICABLE STATUTES REGARDING MERCURY- CONTAINING DEVICES, AND WITH ALL LOCAL, STATE AND FEDERAL APPLICABLE GUIDELINES AT THE TIME
OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF ACCEPTED DISPOSAL.
COORDINATION:
VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.) WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE
INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.
VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF
ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND
EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY
ELECTRICAL REQUIRED, UNLESS NOTED OTHERWISE.
THIS PROJECT REQUIRES COORDINATION DRAWINGS BY THE CONTRACTOR. PARTICIPATE IN THE
COORDINATION DRAWING PREPARATION PROCESS AND PROVIDE ALL NECESSARY INFORMATION
REQUIRED TO COORDINATE ALL TRADE INFORMATION.
ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE
COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF
WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.
WHERE WALLS ARE OF TILT-UP OR PRE-CAST CONSTRUCTION, PROVIDE COORDINATION FOR EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED WITHIN SUCH WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE WALLS, PRIOR TO CONSTRUCTION OF
THE WALLS.
LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE
DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH
CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGH-IN TO ENSURE PROPER NEC
CLEARANCES AND APPROPRIATE MOUNTING SURFACE.
REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR
DESIGN, TECHNOLOGY, STRUCTURAL, AND VENDOR EQUIPMENT DRAWINGS FOR RELATED
INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS PART OF THE
WORK.
WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN
WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE
DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE
CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.
CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND/OR SITE AFFECTED BY THIS WORK PRIOR TO SUBMITTING BID PRICE, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT MAY AFFECT EXECUTION OF THE WORK. SUBMISSION OF A BID PRICE SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT AND/OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED THAT COULD HAVE BEEN REASONABLY
OBSERVED WILL NOT BE RECOGNIZED.
WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE
APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DEMOLITION REQUIREMENTS
DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN DASHED LINE TYPE ARE EXISTING TO BE DEMOLISHED; DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN LIGHT (SCREENED) SOLID LINE
TYPE ARE EXISTING TO REMAIN, UNLESS NOTED OTHERWISE.
EXISTING EQUIPMENT, LIGHT FIXTURES AND DEVICES SHOWN ARE BASED ON FIELD SURVEYS AND RECORD DRAWINGS PROVIDED BY THE OWNER, AND ARE NOT NECESSARILY INCLUSIVE OF ALL EXISTING ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND DEVICES WITHIN PROJECT AREAS. IT IS THE INTENT THAT THE DEMOLITION PLANS PROVIDE A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED
ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT
EXISTING CIRCUITING SHOWN IS BASED ON RECORD DRAWINGS AND THE SURVEYED PANEL DIRECTORIES, WHERE THEY WERE AVAILABLE. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE CONDITIONS SHOWN ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT, WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE
THE NEW WORK. FIELD CONDITIONS SHALL GOVERN.
WHERE EXISTING DEVICES ARE INDICATED TO REMAIN OR BE RELOCATED, ARE WITHIN THE SCOPE OF THIS PROJECT AND EXISTING CIRCUITING INFORMATION IS UNAVAILABLE, CONTRACTOR IS TO PROVIDE CIRCUIT TRACING TO IDENTIFY PANEL AND CIRCUIT SERVING THE DEVICE TO AND PROVIDE THAT INFORMATION TO THE ARCHITECT/ENGINEER PRIOR TO ROUTING CONDUITS AND WIRING FOR NEW DEVICES AND EQUIPMENT
WITHIN THE SCOPE OF THIS PROJECT.
WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR MUST EXTEND EXISTING CIRCUITING WHERE
NECESSARY TO MAINTAIN CONTINUITY OF CIRCUIT.
COORDINATE WITH THE OWNER FOR DISPOSAL OF ELECTRICAL ITEMS TO BE DEMOLISHED. OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS SUCH AS COVERPLATES, RECEPTACLES, LIGHT FIXTURES, PANELBOARDS, TRANSFORMERS, ETC. NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND
MATERIALS BEING REMOVED.
WHERE EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT ARE INDICATED TO BE DEMOLISHED, REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO NEAREST JUNCTION BOX TO MAINTAIN CIRCUIT CONTINUITY OF DEVICES AND EQUIPMENT TO REMAIN. WHERE PANELS ARE TO REMAIN, TURN BREAKER TO "OFF" POSITION AND LABEL THE CIRCUIT AS "SPARE" ON THE PANEL DIRECTORY.
ALL AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE PHASING WITH CONSTRUCTION MANAGER AND OWNER PRIOR TO DEMOLITION OF ANY ITEM WHICH MAY RESULT IN
INTERRUPTION OF POWER.
REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED OR
RENOVATED AREA. CAP BOTH ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE CUT.
CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES, UNLESS OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE DONE TO LOGICAL EDGES OF SURFACES AFFECTED AND SHALL MATCH IMMEDIATELY ADJACENT AREAS IN CONSTRUCTION, MATERIAL, FIRE RATING, FINISH AND COLOR.
FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND
OBTAIN CLARIFICATIONS FROM ENGINEER IF NECESSARY.
COORDINATE ALL POWER INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD, AND UTILITY COMPANY (WHERE APPLICABLE) AND DO NOT INTERRUPT POWER WITHOUT WRITTEN PERMISSION.
PROVIDE A MINIMUM OF ONE WEEK'S WRITTEN NOTIFICATION PRIOR TO WHEN POWER IS DESIRED TO BE INTERRUPTED. CONTRACTOR SHALL INVESTIGATE AND IDENTIFY ALL LOADS TO BE AFFECTED BY THE REQUESTED INTERRUPTION. CONTRACTOR SHALL SUBMIT WRITTEN SEQUENCE OF STEPS FOR EACH SHUTDOWN ALONG WITH THE ESTIMATED INTERRUPTION DURATIONS. MAKE ARRANGEMENTS TO MAINTAIN POWER TO ALL EXISTING NECESSARY LIGHTING, DEVICES AND EQUIPMENT AS NEEDED AND REQUESTED BY
THE OWNER PRIOR TO COMMENCEMENT OF WORK.
EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.
INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS DIAGRAMMATIC IN NATURE. FIELD VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ALL ELECTRICAL ITEMS SCHEDULED TO BE
DEMOLISHED AND PERFORM THE WORK AS INTENDED AND DEPICTED ON THE DRAWINGS.
UPDATE ALL EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS NECESSARY TO
REFLECT FINAL AS-BUILT CONDITIONS AT THE END OF CONSTRUCTION.
STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED AREA.
NOTIFY OWNER WHEN ITEMS ARE READY TO BE REMOVED.
ALL CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER SPACES. ENSURE THAT ALL CONDUITS, NEW OR EXISTING WITHIN THE PROJECT AREA ARE PROPERLY SUPPORTED IN ACCORDANCE
WITH THE NEC.
REMOVE ALL ABANDONED WIRING AND CONDUIT THAT IS WITHIN THE PROJECT AREA PRIOR TO THE END
OF CONSTRUCTION.
1.
2.
3.
4.
5.
6.
APPLICABLE CODES:
ALL WORK UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE AND IN ACCORDANCE
WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING CODES AND STANDARDS INCLUDING
THE REGULATIONS OF GOVERNING LOCAL, STATE, COUNTY AND OTHER APPLICABLE CODES.
REFER TO SPECIFICATIONS FOR ADDITIONAL CODE REQUIREMENTS:
BUILDING CODES:
FLORIDA BUILDING CODE, 8TH EDITION (2023)
FLORIDA ENERGY CONSERVATION CODE, 8TH EDITION (2023)
FLORIDA FIRE PREVENTION CODE, 8TH EDITION (2023)
ADDITIONAL CODES, STANDARDS, AND REQUIREMENTS
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA).
REQUIREMENTS OF LOCAL POWER COMPANY.
THE AMERICANS WITH DISABILITIES ACT (ADA).
OWNER'S PUBLISHED DESIGN STANDARDS.
ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE LISTED BY A
NATIONALLY RECOGNIZED TESTING LAB, AS DEFINED BY OSHA. WHERE NO LABELING OR
LISTING SERVICE IS AVAILABLE FOR CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE
SUBMITTED TO VALIDATE THAT EQUIPMENT MEETS OF EXCEEDS AVAILABLE STANDARDS.
NATIONAL FIRE PROTECTION (NFPA) STANDARDS:
NFPA 70, 2020 EDITION, NATIONAL ELECTRICAL CODE®.
NFPA 72, 2019 EDITION, NATIONAL FIRE ALARM AND SIGNALING CODE.
NFPA 90A, 2018 EDITION, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND
VENTILATING SYSTEMS.
NFPA 90B, 2018 EDITION, STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND
AIR-CONDITIONING SYSTEMS.
NFPA 101, 2021 EDITION, LIFE SAFETY CODE®.
APPLICABLE CODES
ELECTRICAL DEMOLITION NOTES
A/C AIR CONDITIONING
AC ALTERNATING CURRENT
ABV CLG ABOVE CEILING
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AMP AMPERE
AT AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BRKR OR BKR BREAKER
C CONDUIT OR RACEWAY
CKT CIRCUIT
CB CIRCUIT BREAKER
CLG CEILING
CO CONDUIT OR RACEWAY ONLY
COAX COAXIAL CABLE
COND CONDUCTOR
CU COPPER
DEG DEGREE
DF DEMAND FACTOR
DISC DISCONNECT
DISC SW DISCONNECT SWITCH
EMT ELECTRIC METALLIC TUBING
EOL END OF LINE
EOR ENGINEER OF RECORD
ETR EXISTING TO REMAIN
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FATC FIRE ALARM TERMINAL CABINET
FBC FLORIDA BUILDING CODE
FLA FULL LOAD AMPERES
FT FEET
GF GROUND FAULT
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND, G GROUND
HP HORSEPOWER
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
IMC INTERMEDIATE METAL CONDUIT
IN INCHES
IT INSTANTANEOUS TRIP
JB OR J-BOX JUNCTION BOX
KCMIL ONE THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOURS
LBS POUNDS
LED LIGHT EMITTING DIODE
LP LIGHTNING PROTECTION
LT LIGHT
LTG LIGHTING
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND
LSIA LONG TIME, SHORT TIME, INSTANTANEOUS, ALARM
LSI LONG TIME, SHORT TIME, INSTANTANEOUS
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MDP MAIN SERVICE DISTRIBUTION PANEL
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SERVICE SWITCHBOARD
MTD MOUNTED
MTG MOUNTING
MTR MOTOR
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NF NON-FUSED
NL NON-LINEAR
OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
P POLE
PB PULLBOX
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE
PWR POWER
REC, RECEPT RECEPTACLE
RGS, GRC RIGID GALVANIZED STEEL CONDUIT
RLA RUNNING LOAD AMPERES
RMS ROOT-MEAN-SQUARE
RPM REVOLUTIONS PER MINUTE
SCA SHORT CIRCUIT AMPERES
SD SMOKE DETECTOR
SEC SECONDARY
S/N SOLID NEUTRAL
SPD SURGE PROTECTIVE DEVICE
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
SS STAINLESS STEEL
SST SOLID STATE TRIP
STD SHORT TIME TRIP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TVEC TELEVISION EQUIPMENT CABINET
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UL UNDERWRITERS LABORATORIES
UTIL UTILITY
V VOLT
VA VOLTAMPERE
VAR VOLT AMPERE REACTIVE
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
XFR TRANSFER
IDENTIFICATION:
EQUIPMENT:
EQUIPMENT IDENTIFICATION SHALL BE MADE USING ENGRAVED LAMINATED
PHENOLIC OR MICARTA PLATES (INDENTED TAPE LABELS WILL NOT BE
PERMITTED). CHARACTERS SHALL BE WHITE ON A BLACK BACKGROUND AND
1/4" HIGH MINIMUM. PLATES SHALL BE SECURED TO THE PANELS BY MEANS
OF SCREWS OR METAL PRESSURE PINS. CEMENT, BY ITSELF, WILL NOT
ACCEPTABLE. ALL NAMEPLATES SHALL BE MOUNTED ON THE OUTSIDE
SURFACE OF THE PIECE OF EQUIPMENT. INDIVIDUALLY ENCLOSED SAFETY
SWITCHES, CIRCUIT BREAKERS, AND MOTOR STARTERS, PULL BOXES,
CONTROL CABINETS AND OTHER SUCH ITEMS SHALL BE IDENTIFIED
INDICATING LOAD, ELECTRICAL CHARACTERISTICS, AND SOURCE.
JUNCTION BOX IDENTIFICATION:
EACH JUNCTION BOX COVER SHALL BE LABELED WITH A PERMANENT "MAGIC"
MARKER OR OTHER MEANS TO IDENTIFY THE CIRCUITS WITHIN. FOR
EXAMPLE, A JUNCTION BOX CONTAINING LIGHTING CIRCUITS 21, 23, 25 FROM
PANEL L2A WOULD BE LABELED "L2A-21,23,25". TELEPHONE JUNCTION BOXES
SHALL BE LABELED "T". FIRE ALARM AND OTHER SYSTEM JUNCTION BOXES
SHALL BE LABELED ACCORDINGLY.
RECEPTACLE IDENTIFICATION:
ALL RECEPTACLES SHALL BE PROVIDED WITH 3/16" ENGRAVED AND
"FILLED-IN" LETTERING INDICATING PANEL BOARD AND CIRCUIT NUMBER
"WHERE FED FROM" FOR ALL RECEPTACLES.
JUNCTION BOXES:
ALL JUNCTION BOXES AND PULL BOXES SHALL BE SIZED PER N.E.C.
REQUIREMENTS AND BE OF THE PROPER NEMA CLASSIFICATION FOR THE
LOCATIONS WHERE THEY ARE INSTALLED. WHERE BOXES OCCUR ABOVE
OTHER THAN LIFT-OUT CEILINGS, ACCESS PANELS MUST BE PROVIDED.
CONDUIT AND FITTINGS:
ALL INTERIOR CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT).
ALL EXTERIOR CONDUIT SHALL BE RIGID METAL CONDUIT (RMC).
FITTINGS FOR ELECTRICAL METALLIC TUBING SHALL BE STEEL SET SCREW
OR COMPRESSION TYPE. DIE CAST FITTINGS OR CONNECTORS WILL NOT BE
ACCEPTABLE. EMT CONNECTORS TO BE SIMILAR TO T&B "INSULINE" WITH
COMPLETELY INSULATED THROATS. (FIELD APPLIED INSULATED THROATS
ARE NOT ACCEPTABLE).
CONDUITS BUSHINGS SHALL BE METALLIC WITH INSULATED THROATS.
INSULATING GROUNDING TYPE BUSHINGS SHALL BE PROVIDED WHERE
REQUIRED UNDER 'GROUNDING'.
CONDUITS SHOWN ROUTED OVERHEAD MAY NOT BE INSTALLED IN OR
BELOW SLABS OR IN WALLS.
NOT MORE THAN THREE CIRCUITS MAY BE INSTALLED IN ANY ONE CONDUIT
UNLESS OTHERWISE INDICATED.
ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED ON THE
DRAWINGS. EXPOSED CONDUIT WILL BE PERMITTED ONLY AS SHOWN ON THE
DRAWINGS. EXPOSED CONDUIT SHALL BE RUN PARALLEL WITH OR AT RIGHT
ANGLES TO THE BUILDING WALLS. ALL EMPTY CONDUITS SHALL BE PROVIDED
WITH A PLASTIC OR NYLON FISH WIRE.
EXPOSED CONNECTIONS TO MOTORS AND EQUIPMENT FROM OVERHEAD
CONDUITS SHALL CONSIST OF VERTICAL CONDUIT (MINIMUM SIZE 1") FROM
TYPE "LL" OR "LR" UNILET TO FLOOR FLANGE. CONNECTION TO EQUIPMENT
SHALL BE WITH FLEXIBLE METAL CONDUIT FROM TYPE FDT BOXES LOCATED
IN THE VERTICAL CONDUIT.
FLEXIBLE CONDUIT IN ALL AREAS OTHER THAN CEILING PLENUM SUBJECT TO
MOISTURE SHALL BE LIQUID-TIGHT FLEXIBLE CONDUIT. ALL ELECTRICAL
CONNECTIONS TO VIBRATION ISOLATED EQUIPMENT SHALL BE MADE WITH
FLEXIBLE CONDUIT.
GENERAL:
THE INSTALLATION SHALL COMPLY WITH ALL LOCAL LAWS AND
ORDINANCES APPLICABLE TO ELECTRICAL INSTALLATIONS, AND WITH
THE REGULATIONS OF THE NFPA WHERE SUCH REGULATIONS DO NOT
CONFLICT WITH THOSE LAWS. OBTAIN ALL PERMITS REQUIRED.
MANUFACTURERS DRAWINGS AND DATA:
SUBMIT TO THE ENGINEER FOR APPROVAL FIVE (5) COPIES OF THE
COMPLETE LIST OF ALL ELECTRICAL MATERIALS WHICH ARE PROPOSED
TO BE FURNISHED FOR THIS PROJECT. AS A MINIMUM THE
SUBMITTAL SHALL INCLUDE PANELBOARDS, A.I.C. OF BREAKERS
INSTALLED, LIGHT FIXTURES, BALLASTS, AND LAMPS.
STANDARD OF MATERIALS AND WORKMANSHIP:
ALL MATERIALS, EQUIPMENT AND APPARATUS COVERED BY THIS
SPECIFICATION SHALL BE NEW, OF CURRENT MANUFACTURE AND
SHALL BEAR THE SEAL OF APPROVAL OF THE UNDERWRITERS
LABORATORIES. ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE
MANNER AND SHALL PRESENT A NEAT AND MECHANICAL APPEARANCE
WHEN COMPLETED.
STORAGE OF MATERIALS:
THE CONTRACTOR SHALL PROVIDE SUITABLE STORAGE FACILITIES FOR
ALL MATERIAL FURNISHED BY HIM UNDER THIS CONTRACT. ALL ITEMS
TO BE INSTALLED MUST BE FREE OF RUST AND DIRT.
FIREPROOFING:
ALL CONDUIT AND BOXES PASSING THROUGH OR INSTALLED WITHIN
FIRE WALLS AND SMOKE WALLS SHALL BE INSTALLED SO AS TO
MAINTAIN THE INTEGRITY OF THE WALL THROUGH WHICH IT PASSES.
BOXES TO BE INSTALLED WITH 1/8" OF WALL SURFACE.
TESTING:
AT THE COMPLETION OF THE WORK, A THOROUGH TEST SHALL BE
MADE IN THE PRESENCE OF THE ENGINEER OR HIS REPRESENTATIVE,
AND THE ENTIRE SYSTEM SHALL BE SHOWN TO BE IN PERFECT
WORKING CONDITION AS INTENDED BY THESE SPECIFICATIONS.
GUARANTEE:
THE CONTRACTOR SHALL LEAVE THE ENTIRE ELECTRICAL SYSTEM
INSTALLED BY HIM UNDER THIS CONTRACT IN PROPER WORKING
ORDER AND SHALL REPLACE, WITHOUT ADDITIONAL CHARGE, ALL WORK
OR MATERIAL WHICH MAY DEVELOP DEFECTS, ORDINARY WEAR AND
TEAR OR DAMAGE RESULTING FROM IMPROPER HANDLING EXCEPTED,
WITHIN A PERIOD OF ONE YEAR FROM THE DATE OF FINAL TESTING
AND ACCEPTANCE BY THE ENGINEER. BALLASTS SHALL BE INCLUDED
BUT LAMPS SHALL BE EXCLUDED.
CONDUCTORS:
ALL CONDUCTORS SHALL BE COPPER OF NOT LESS THAN
NINETY-EIGHT PERCENT (98%) CONDUCTIVITY, WITH NEC TYPE
THHN/THWN, 600 VOLT INSULATION. CONDUCTORS NO. 12 THROUGH
NO. 10 MAY BE SOLID OR STRANDED AND NO. 8 AND LARGER SHALL
BE STRANDED. NO CONDUCTORS SMALLER THAN NO. 12 SHALL BE
USED EXCEPT AS OTHERWISE NOTED. CONTROL CONDUCTORS SHALL
BE NO. 14. MC CABLE IS NOT PERMITTED.
NEUTRAL WIRES SHALL BE PIGTAILED TO RECEPTACLES SO THAT
RECEPTACLE CAN BE REMOVED FOR REPLACEMENT WITHOUT THE
NEUTRAL CONNECTION TO OTHER RECEPTACLES ON THE CIRCUIT
BEING DISCONNECTED. WHEN STRANDED WIRE IS USED FOR
RECEPTACLE AND LIGHTING CIRCUIT, CONNECTIONS TO THE DEVICES
SHALL BE MADE USING VINYL INSULATED "STAKON" CONNECTOR
TERMINALS.
CABLE AND WIRE SPLICES:
THE MATERIALS SHALL BE COMPATIBLE WITH THE CONDUCTORS,
INSULATIONS AND PROTECTIVE JACKETS OF THE RESPECTIVE CABLES
AND WIRES.
FOR CONDUCTOR SIZED NO. 6 AWG OR LARGER: SPLICES IN
CONDUCTORS SHALL BE MADE WITH INDENTER, CRIMP CONNECTORS
AND COMPRESSION TOOLS OR WITH BOLTED CLAMP TYPE
CONNECTORS TO INSURE A SATISFACTORY MECHANICAL AND
ELECTRICAL JOINT.
PANELBOARDS: (NEW BREAKERS)
INTERRUPTING RATINGS SHALL MATCH EXISTING PANELS TO MAINTAIN
FULLY RATED STATUS. BRANCH CIRCUIT PROTECTION DEVICES SHALL
BE MOLDED CASE CIRCUIT BREAKERS BOLT-0N TYPE. PANELS SHALL
BE FULLY RATED.
NEW TYPED DIRECTORY CARDS SHALL BE FURNISHED IN EACH PANEL.
WIRING DEVICES:
WALL SWITCHES:
ALL SWITCHES SHALL BE FLUSH ENCLOSED TYPE, SPECIFICATION
GRADE, RATED AT 20 AMPERES, 120/277 VOLTS, ALTERNATING
CURRENT ONLY, AND QUIET OPERATION. COLOR OF ALL DEVICES
SHALL BE IVORY.
MOTOR SWITCHES:
WITH INHERENT THERMAL OVERLOAD PROTECTION SHALL BE SQUARE
D, TYPE F FOR FLUSH OR SURFACE MOUNTING AS REQUIRED BY THE
LOCATION OF THE UNIT. UNITS SHALL BE FURNISHED WITH PILOT
LIGHTS AS INDICATED.
RECEPTACLES:
GROUNDING TYPE DUPLEX RECEPTACLE, RATED 20 AMPERES, 125
VOLTS, 2 WIRE, 3 POLE WITH GROUNDED SHUNT (YOKE PERMANENTLY
GROUNDED TO THIRD CLIP).
OTHER RECEPTACLES LISTED ON THE DRAWINGS SHALL BE
SPECIFICATION GRADE RECEPTACLES. ALL RECEPTACLES SHALL BE
IVORY IN COLOR.
DEVICES PLATES:
ALL PLATES FOR SWITCH, RECEPTACLES AND TELEPHONE OUTLETS
LOCATED IN FINISHED WALLS SHALL BE SMOOTH THERMOPLASTIC.
COLOR TO MATCH DEVICE. ALL PLATES FOR OUTLETS LOCATED ON
UNFINISHED WALL OR ON CONDULET TYPE FITTINGS SHALL BE ZINC
COATED SHEET METAL WITH ROUNDED OR BEVELED EDGES.
ACCEPTABLE MANUFACTURERS: HUBBELL, LEVITON, P&S.
OUTLET BOXES:
SWITCH AND RECEPTACLE OUTLET BOXES SHALL BE FOUR INCH (4")
SQUARE OR FOUR AND ELEVEN SIXTEENTHS INCH (4-11/16") A
MINIMUM OF 1-1/2" DEEP WITH SWITCH RING AS REQUIRE OR GANG
BOXES A MINIMUM OF 2" DEEP WHEN MORE THAN TWO DEVICES
MOUNT UNDER A COMMON COVER.
WALL TELEPHONE OUTLETS SHALL BE FOUR INCH (4") SQUARE BOXES
WITH STANDARD SWITCH COVERS AND TELEPHONE COVER PLATES.
LOCATION OF OUTLETS:
THE APPROXIMATE LOCATIONS OF OUTLETS, ETC. ARE SHOWN ON THE
DRAWINGS. THE EXACT LOCATIONS SHALL BE DETERMINED AT THE
BUILDING. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTE
THE LOCATIONS AND HEIGHTS OF CABINETS, ETC. BEFORE THE
INSTALLATION OF OUTLETS.
SAFETY SWITCHES:
SAFETY SWITCHES SHALL BE "HD" (HEAVY DUTY) UNLESS NOTED
OTHERWISE, FUSED OR NON-FUSIBLE AS INDICATED WITH NUMBER OF
POLES AS SHOWN OR REQUIRED. SAFETY SWITCHES FOR EQUIPMENT
MAY BE NON-FUSED ONLY IF EQUIPMENT IS UL TESTED WITH CIRCUIT
BREAKER PROTECTION. DISCONNECT SWITCHES SHALL BE PROVIDED
FOR ALL MOTORS.
ACCEPTABLE MANUFACTURERS: SQ-D, GE, SIEMENS.
GROUNDING:
IN GENERAL A GROUND WIRE SHALL BE INSTALLED IN EVERY
CONDUIT. THE CONDUIT INSTALLATION ITSELF SHALL SERVE AS AN
ADDITIONAL GROUNDING MEANS.
WHERE CONDUITS TERMINATE WITHOUT MECHANICAL CONNECTION (I.E.
LOCKNUTS AND BUSHINGS) TO PANELBOARDS, AND FOR ALL
TERMINATIONS OF CONDUIT WITH #4 OR LARGER; AND FOR ALL SIZES
OF METALLIC CONDUIT (RIGID OR FLEXIBLE) TERMINATING IN
CONCENTRIC KNOCKOUTS, THE FOLLOWING PROCEDURE SHALL BE
FOLLOWED: EACH CONDUIT SHALL BE PROVIDED WITH AN INSULATING
GROUND BUSHING AND EACH BUSHING CONNECTED WITH A BARE
COPPER CONDUCTOR TO THE GROUND BUS IN THE ELECTRICAL
EQUIPMENT. THE GROUND CONDUCTOR SHALL BE IN ACCORDANCE
WITH THE ARTICLE OF GROUNDING OF NEC.
HANGERS AND SUPPORTS:
STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-4, FACTORY-
FABRICATED COMPONENTS FOR FIELD ASSEMBLY. METALLIC COATINGS:
HOT-DIP GALVANIZE AFTER FABRICATION. PAINTED COATINGS:
MANUFACTURER'S STANDARD PAINTING COATING.
RACEWAY AND CABLE SUPPORTS: AS DESCRIBED IN NECA 1 AND NECA
101.
CONDUIT AND CABLE SUPPORT DEVICES: STEEL HANGERS, CLAMPS, AND
ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY
OR CABLE TO BE SUPPORTED.
MOUNTING, ANCHORING AND ATTACHMENT COMPONENTS: POWDER-
ACTUATED FASTENERS, MECHANICAL EXPANSION ANCHORS AND
CONCRETE INSERTS, AS APPLICABLE FOR SURFACE ATTACHMENT.
EXECUTION: COMPLY WITH NECA 1 AND 101 FOR APPLICATION OF
HANGERS AND SUPPORTS. SPACE SUPPORTS AS REQUIRED BY NFPA 70.
TOUCH UP PAINTING AS REQUIRED.
ELECTRICAL SPECIFICATIONS
S = SUPPLY
R = RETURN
DUCT SMOKE DETECTORS
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
N.T.S.
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL
SYMBOLS, LEGEND,
NOTES AND INDEX
E-001
01266083
ELECTRICAL DRAWING INDEX
SHEET DESCRIPTION
E-001 ELECTRICAL SYMBOLS, LEGEND, NOTES AND INDEX
E-101D ELECTRICAL DEMOLITION PLAN - LEVEL 1
E-102D ELECTRICAL DEMOLITION PLAN - LEVEL 2
E-101 ELECTRICAL PLAN - LEVEL 1
E-102 ELECTRICAL PLAN - LEVEL 2
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL ONE-LINE DIAGRAM AND PANEL SCHEDULES
No. Date Description
TELE/COM
MEN
MECHANICAL
ELEV.
EQUIP
LOBBY
HM
NOT IN SCOPE
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
1/8" = 1'-0"
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL
DEMOLITION PLAN -
LEVEL 1
E-101D
01266083
GENERAL NOTES:
LAYOUT IS BASED UPON NON-INVASIVE FIELD INVESTIGATION AND LIMITED EXISTING AS-BUILTS.
CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES BETWEEN THIS
LAYOUT AND FIELD CONDITIONS.
ALL CIRCUITS ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
REWORK EXISTING CONDUIT AND CONDUCTORS WHERE NECESSARY TO
MAINTAIN CONTINUITY OF ELECTRICAL SYSTEMS.
DE-ENERGIZE, DETACH, AND REMOVE ALL ELECTRICAL ITEMS INDICATED BY DASHED LINES UNLESS OTHERWISE NOTED. EXISTING TO REMAIN ITEMS ARE INDICATED BY HALF-TONE LINES UNLESS
OTHERWISE NOTED.
A.
B.
C.
SHEET NOTES:
DEINSTALL AND REMOVE EXISTING DISCONNECT. RETAIN EXISTING CONDUIT AND CONDUCTORS FOR
NEW UNIT.
1.
1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - LEVEL 1
No. Date Description
TRUE
NORTH
STAIR
STAIR
MECH
FIRST FLOOR
OPEN TO
IN
SI
D E
FA
C
E O
F
ST
U D
30"x48"
REFUGE
AREA OF
FIRST FLOOR
OPEN TO
IN
SI
D E
FA
C
E O
F
ST
U D
30"x48"
REFUGE
AREA OF
NOT IN SCOPE
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
1/8" = 1'-0"
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL
DEMOLITION PLAN -
LEVEL 2
E-102D
01266083
GENERAL NOTES:
LAYOUT IS BASED UPON NON-INVASIVE FIELD INVESTIGATION AND LIMITED EXISTING AS-BUILTS.
CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES BETWEEN THIS
LAYOUT AND FIELD CONDITIONS.
ALL CIRCUITS ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
REWORK EXISTING CONDUIT AND CONDUCTORS WHERE NECESSARY TO
MAINTAIN CONTINUITY OF ELECTRICAL SYSTEMS.
DE-ENERGIZE, DETACH, AND REMOVE ALL ELECTRICAL ITEMS INDICATED BY DASHED LINES UNLESS OTHERWISE NOTED. EXISTING TO REMAIN ITEMS ARE INDICATED BY HALF-TONE LINES UNLESS
OTHERWISE NOTED.
A.
B.
C.
SHEET NOTES:
DEINSTALL AND REMOVE EXISTING DISCONNECT. RETAIN EXISTING CONDUIT AND CONDUCTORS FOR
NEW UNIT.
1.
1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - LEVEL 2
No. Date Description
TELE/COM
MEN
MECHANICAL
ELEV.
EQUIP
LOBBY
HM
HM-20,22,24
CU-1
CU-2
HM-2,4,6
HM-8,10,12
AHU-1
AHU-2S
S
S
S
HDP-14,16,18
HDP-8,10,123
CU-4
NOT IN SCOPE
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
1/8" = 1'-0"
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL PLAN -
LEVEL 1
E-101
01266083
GENERAL NOTES:
NEW ITEMS PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR ARE INDICATED BY BOLD LINES.A.
SHEET NOTES:
PROVIDE 60 AMP (FUSED @ 40A) NEMA 3R DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE
REUSED.
PROVIDE 60 AMP (FUSED @ 50A) NEMA 3R DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE
REUSED.
PROVIDE 100 AMP (FUSED @ 80A) NEMA 1 DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE
REUSED.
EXISTING 120V UV LIGHT CIRCUIT TO BE REUSED.
EXISTING DUCT DETECTORS TO BE REUSED.
1.
2.
3.
4.
5.
1/8" = 1'-0"1 ELECTRICAL PLAN - LEVEL 1
No. Date Description
STAIR
STAIR
MECH
FIRST FLOOR
OPEN TO
IN
SI
D E
FA
C
E O
F
ST
U D
30"x48"
REFUGE
AREA OF
FIRST FLOOR
OPEN TO
IN
SI
D E
FA
C
E O
F
ST
U D
30"x48"
REFUGE
AREA OF
AHU-4
S
S
HDP-31,33,35
NOT IN SCOPE
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
1/8" = 1'-0"
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL PLAN -
LEVEL 2
E-102
01266083
GENERAL NOTES:
NEW ITEMS PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR ARE INDICATED BY BOLD LINES.A.
SHEET NOTES:
PROVIDE 100 AMP (FUSED @ 80A) NEMA 1 DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE
REUSED.
EXISTING 120V UV LIGHT CIRCUIT TO BE REUSED.
EXISTING DUCT DETECTORS TO BE REUSED.
1.
2.
3.
1/8" = 1'-0"1 ELECTRICAL PLAN - LEVEL 2
No. Date Description
1MOUNTING HEIGHTS
No Scale
No Scale
PANELBOARD NAMEPLATE
TYPICAL 120/208V PANELBOARD
TYPICAL 277/480V PANELBOARD
PANEL "XXXX"
120/208V, 3∅∅, 4W
FED FROM PANEL "XXXX"
VIA T-XXX
FED FROM PANEL "XXXX"
277/480V, 3∅∅, 4W
PANEL "XXX"
1/16" THICK WHITE PLASTIC
WITH COLORED FACE PER
SPECIFICATIONS
PANELBOARD NAME
TYPICAL EQUIPMENT
AHU-X
480V, 3∅∅
FED FROM "NDH1-4"
AHU-X
480V, 3∅∅
FED FROM "NDH1-4"
WHITE PLASTIC WITH COLORED FACE PER
SPECIFICATIONS
ADHESIVE BACKING WHEN
INSTALLED
IN CONDITIONED SPACES
EQUIPMENT VOLTAGE
EQUIPMENT NAME
FASTEN WITH BRASS SCREWS
WHEN LOCATED IN NON-
CONDITIONED OR
EXTERIOR SPACES
No Scale
EQUIPMENT NAMEPLATE
F
EXIT
F
VC
W
CL
80"
48"
90"
48"
AFF
18"
AFF
36"
TELE. OUTLET
42" A.F.F. W/ 36" COUNTER,
39" A.F.F. W/ 30" COUNTER,
48" A.F.F. WITHOUT COUNTER
78" MAX.
TO TOP DEVICE
OR AS NOTED ON PLANS
PANELBOARD
DUPLEX RECEPTACLE
CENTERED OVER DOOR
(WHERE APPLICABLE)
CLOCK OUTLET FIRE SPEAKER & LIGHT
80" AFF FROM BOTTOM OF DEVICE
REMOTE TEST
VOLUME CONTROL
FA PULL
STATION
SWITCH
RECEPTACLE
TELE. OUTLET
FINISHED FLOOR
SPECIAL POWER OUTLET
CL
CL
CL
CL
CL
1MOUNTING HEIGHTS
No Scale
No Scale
PANELBOARD NAMEPLATE
TYPICAL 120/208V PANELBOARD
TYPICAL 277/480V PANELBOARD
PANEL "XXXX"
120/208V, 3∅∅, 4W
FED FROM PANEL "XXXX"
VIA T-XXX
FED FROM PANEL "XXXX"
277/480V, 3∅∅, 4W
PANEL "XXX"
1/16" THICK WHITE PLASTIC
WITH COLORED FACE PER
SPECIFICATIONS
1/4" HIGH LETTERING FOR
PANELBOARD NAME
1/8" HIGH LETTERING FOR
REMAINING TEXT
PANELBOARD NAME
PANELBOARD VOLTAGE
PANELBOARD SOURCE
TYPICAL EQUIPMENT
AHU-X
480V, 3∅∅
FED FROM "NDH1-4"
AHU-X
480V, 3∅∅
FED FROM "NDH1-4"
1/4" HIGH LETTERING FOR
PANELBOARD NAME
1/8" HIGH LETTERING FOR
REMAINING TEXT
FASTEN WITH BRASS SCREWS
WHEN LOCATED IN NON-
CONDITIONED OR
EXTERIOR SPACES
EQUIPMENT SOURCE
(PANEL & CIRCUIT)
No Scale
EQUIPMENT NAMEPLATE
F
F
VC
W
CL
80"
48"
90"
48"
AFF
18"
6" AFC
AFF
36"
TELE. OUTLET
42" A.F.F. W/ 36" COUNTER,
39" A.F.F. W/ 30" COUNTER,
48" A.F.F. WITHOUT COUNTER
78" MAX.
TO TOP DEVICE
OR AS NOTED ON PLANS
WALL MOUNTED LIGHT FIXTURES
AS NOTED ON PLANS
PANELBOARD
DUPLEX RECEPTACLE
CENTERED OVER DOOR
(WHERE APPLICABLE)
CENTERED BETWEEN
DOOR & CEILING
(COORDINATE WITH
ARCHITECT)
CLOCK OUTLET FIRE SPEAKER & LIGHT
80" AFF FROM BOTTOM OF DEVICE
REMOTE TEST
VOLUME CONTROL
FA PULL
STATION
SWITCH
RECEPTACLE
TELE. OUTLET
FINISHED FLOOR
SPECIAL POWER OUTLET
CL
CL
CL
CL
CL
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
N.T.S.
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL
DETAILS
E-501
01266083
ELEVATOR AHU-2 AHU-1
EXISTING
PANEL
"H1A"
EXISTING
SWITCHBOARD "HDP"
EXISTING
PANEL
"H2A"
EXISTING
PANEL
"L1A"
EXISTING PANEL "LMDP"
EXISTING
PANEL
"C1A" EXISTING
PANEL "C2A"
EXISTING
PANEL
"L2A"
EXISTING
PANEL "HE1"
EXISTING
PANEL "HE2"
EXISTING GENERATOR
EXISTING
PANEL
"LM"
EXISTING
"FACP"
EXISTING
PANEL
"HM"
EXISTING
PANEL "ER2"
UPS
TX-1
J
M
800A, 65,000
277/480V, 3PH, 4W
800AF
800AT
3P3P 100AT
100AF 3P 400AF
300AT
LSIG
ST EPO
FPL
METER
277/480V
LIGHTING PANEL
FIRST FLOOR SECOND FLOOR
LIGHTING PANEL
277/480V
277/480
277/480-120/208V
120/208V
RECEPTACLE
PANEL
225AT
250AF3P
FIRST FLOOR
PANEL
3P
RECEPTACLE
COMPUTER
120/208V
FIRST FLOOR
SECOND FLOOR
120/208V
COMPUTER
RECEPTACLE
3P
PANEL
SECOND FLOOR
3P
PANEL
RECEPTACLE
120/208V
FIRST FLOOR
PANEL
EMERGENCY
277/480V
3P
3P
277/480V
EMERGENCY
PANEL
SECOND FLOOR
ST800AF
800AT
G CONTROL AND
PROTECTION SYSTEM
GENERATOR
ANNUNCIATOR
3P
60AT
100AF3P
SS
SURGE
SUPPRESSOR
100AT
100AF
100AT
100AF250AF
225AT
120/208V
MECHANICAL
EQUIPMENT
3P
PANEL
FIRST FLOOR
SUPPRESSOR
SURGESS
100AT
100AF3P 3P 100AF
100AT
80A/3P 3P 250AF
225AT
277/480V
EQUIPMENT
MECHANICAL
PANEL
FIRST FLOOR
AUTOMATIC
TRANSFER
LSIG
800AT
800AF
3P
100AT
100AF
100AT
100AF
120/208V. 3PH, 4W
600A, 22,000 AIC
600AT
600AF
250AF
225AT
LSIG
60AT
100AF
3P
3P
SPACE SPACE
225KVA
3P
SPARE SPACE SPACE
250AF 250AF
SPARE
3P
SPACE
22,000 AIC20A
1P
2P
SPACE
225AT
250AF 100AF
100AT3P
EPO
LOCATED IN
ELECTRICAL RM.
SECOND FLOOR
PANEL
UPS
120/208V
60AT
100AF
AND
BYPASS
SWITCH
250AF3P
SPARE SPACE
EXISTING GENERATOR FOR
BUILDING
80A/3P 1 1
NEW WORK
AHU-4
80A/3P
2 2 2
"HDP" LOAD CALCULATION
EXISTING LOAD
- REMOVED LOAD
+ ADDED LOAD (INCLUDING "HM")
CALCULATED TOTAL LOAD
292.7 kVA
239.1 kVA
254.4 kVA
308.0 kVA
370.5 AMPS @
277/480V, 3PH, 4W
7370 Cabot Ct, Suite 103 Melbourne, FL 32940
P 321.636.0274 www.tlc-engineers.com
© Copyright 2026 TLC Engineering Solutions, Inc.
TLC Project No.:
COA 15
Seal
Drawing No.:
Scale:
Revisions:
Drawing Title:
Approved By:
Issue Date:
Project No.:
Drawn By:
Consultants:
PERMIT SET
N.T.S.
7/
/2
:3 0:
P
M C
:\R ev it
L oc al s\
_C oc oa
C ity
P ol ic e
D ep t H
VA
C R en o_
M
EP
_R
_L uk e.
Ad am sD
5C 5E
.rv t
C O
C O
A C
IT
Y
PO
LI
C E
D
EP
T H
VA
C
R
EN
O
K
IN
G S
T.
C
O C
O A, F L
01266083
07/22/2026
JDH
MMH
ELECTRICAL
ONE-LINE DIAGRAM
AND PANEL
SCHEDULES
E-601
01266083
12" = 1'-0"1 ELECTRICAL ONE-LINE
1: UTILIZE EXISTING BREAKER IN EXISTING PANELBOARD
2: PROVIDE NEW BREAKER IN EXISTING PANELBOARD.
KEYNOTES (KN):
TOTAL DEMAND CURRENT (A): 195
TOTAL DEMAND LOAD (KVA): 162.094
HVAC 126494 VA 100.00% 126494 VA TOTAL CONNECTED LOAD (KVA): 162.094
EQUIPMENT 35600 VA 100.00% 35600 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD PANEL TOTALS
CONNECTED PHASE AMPS (A) 195.059 195.059 195.059
CONNECTED PHASE LOAD (KVA) 54.031 54.031 54.031
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 SPACE -- 1 -- -- 1 -- SPACE 40
37 SPACE -- 1 -- -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- 1 -- SPACE 32
29 SPACE -- 1 -- -- 1 -- SPACE 30
27 SPACE -- 1 -- -- 1 -- SPACE 28
25 SPACE -- 1 -- -- 1 -- SPACE 26
23 SPACE -- 1 -- 7.702 24
21 SPACE -- 1 -- 7.702 22
19 SPACE -- 1 -- 7.702
3 40 CU-4
17 1.667 10.200 18 15 1.667 10.200 16
EXIST. LOAD 20 3
1.667 10.200
3 45 EXIST. CU-3
11 17.200 7.702 12 9 17.200 7.702 10
EXIST. AHU-3 70 3
17.200 7.702
3 40 CU-2
5 0.000 9.561 6 3 0.000 9.561 4
SPARE 30 3
0.000 9.561
3 50 CU-1
KN CKT CIRCUIT DESCRIPTION TRIP(A) P A (KVA) B (KVA) C (KVA) P TRIP(A) CIRCUIT DESCRIPTION CKT KN SUPPLY FROM: HDP ENCLOSURE: NEMA 1 MAX. HEIGHT BUSING: NO MAINS TYPE: MLO RATING: 225 A
LOCATION: TELE/COM 114 MOUNTING: SURFACE DIST. / PHASE / WIRES: 480Y/277V / 3 / 4 K.A.I.C. RATING: 65 FEED THRU: NO
NAME: HM EXISTING
SHEET NOTES:
PROVIDE NEW BREAKER IN EXISTING PANELBOARD.
PROVIDE 3#3, 1#8 GND IN EXISTING 1-1/2" C. EXTEND AND REWORK CONDUIT, AS REQUIRED.
1.
2.
| E-001 - ELECTRICAL SYMBOLS, LEGEND, NOTES AND INDEX |
| E-101D - ELECTRICAL DEMOLITION PLAN - LEVEL 1 |
| E-102D - ELECTRICAL DEMOLITION PLAN - LEVEL 2 |
| E-101 - ELECTRICAL PLAN - LEVEL 1 |
| E-102 - ELECTRICAL PLAN - LEVEL 2 |
| E-501 - ELECTRICAL DETAILS |
| E-601 - ELECTRICAL ONE-LINE DIAGRAM AND PANEL SCHEDULES |
File details come from the government source that posted it. Updated .