Exhibit_B__Electrical_Specifications.pdf

PDF 1 MB Posted

Attached to
Cocoa Police Department HVAC Renovations
Solicitation number
B-26-12-COC
Issued by
Brevard County, Clewiston City, Florida

About this file

This is an Electrical Specifications exhibit for the Cocoa Police Department HVAC Renovations project under the jurisdiction of the City of Cocoa, Florida. The project involves the removal and replacement of three split system DX air conditioning units at the police department facility located at 1226 West King Street, Cocoa, FL 32922. The scope encompasses furnishing and installing three new AC units of appropriate capacity to match or improve upon existing building load requirements, along with all associated electrical work including disconnects, wiring, and connections necessary to power the new units in compliance with current code requirements. Additional deliverables include controls integration with the building automation system or thermostats, HVAC work such as ductwork modifications, refrigerant line sets, and condensate drainage, coordination of any required structural support modifications, testing and balancing to manufacturer specifications, site cleanup, and provision of warranty documentation and as-built information upon project completion. All work shall be performed in accordance with the Construction Plans and applicable codes including EPA refrigerant recovery requirements and the jurisdiction's building standards.

The electrical specifications document outlines the technical requirements and standards that contractors must follow when executing the electrical components of this renovation project. The specifications ensure that all electrical work is brought to current code compliance and integrates properly with the new HVAC equipment. Contractors must coordinate with electrical, controls, and HVAC trades to ensure a complete and functional installation, with all work subject to testing, verification, and inspection to confirm operation meets manufacturer specifications and local regulatory requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

UP

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

SYMBOL DESCRIPTION

VFD

ELECTRICAL SYMBOL LEGEND

TRANSFORMERT

VARIABLE FREQUENCY DRIVE

NEW (HEAVY, SOLID LINE)

EXISTING TO REMAIN (LIGHT, SOLID LINE)

EXISTING TO BE REMOVED (HEAVY, DASHED LINE)

FLEXIBLE CONDUIT

CONDUIT CONTINUED

CONDUIT STUBBED OUT OR UP

CONDUIT TURNING DOWN

CONDUIT TURNING UP

GROUND OR GROUND ROD AS NOTED

CONDUIT EXPOSED

CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR

CONDUIT CONCEALED ABOVE CEILING OR IN WALL

BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED

30AR

20AF

NF

30AR NON-FUSED DISCONNECT SWITCH, RATING AS NOTED

NF = NON-FUSED

AR = AMPERE RATING OF SWITCH

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE

NOTED30/3

0 3R

MCP

AMPERE

RATING

# OF POLES

NEMA STARTER SIZE

FUSED DISCONNECT

BASIC MATERIALS

DEVICE ABBREVIATION TAGS :

CONDUIT SEAL-OFF FITTING

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

3R

3R

AF = AMPERE RATING OF FUSE

AR = AMPERE RATING OF SWITCH

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED

CONDUIT HOMERUN TO ELECTRICAL PANEL

EXISTING TO REMAIN ETR

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL

ABBREVIATIONS

ELECTRICAL GENERAL NOTES

10.

11.

12.

13.

14.

COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE.

PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE

REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG

LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR PHASING.

ANY TEMPORARY INTERRUPTION OF POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND

SCHEDULED IN ADVANCE.

COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS (ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL, EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING AND IMPACT FEES.

CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM

INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM DAMAGE OR EXCESSIVE

NOISE THROUGHOUT THE DURATION OF THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR ANY

LOSSES OR ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL CONDITION TO THE SATISFACTION OF THE ARCHITECT/ENGINEER

AND OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE

ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO BID. CONTRACTOR SHALL

NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET

BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

1.

2.

3.

4.

5.

6.

7.

8.

9.

GENERAL REQUIREMENTS:

THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO

THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP, METHODS

AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL

DIVISIONS AS A WHOLE.

THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF

CONSTRUCTION, METHODS, MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE CONTRACT DOCUMENTS. COORDINATE

EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL, CIVIL AND STRUCTURAL CONTRACT

DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP DRAWINGS AND WORK OF ALL OTHER

DIVISIONS/TRADES.

THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES TO FURNISH AND INSTALL MATERIALS REQUIRED FOR CORRECT INSTALLATION OF A COMPLETE SYSTEM, UNLESS SPECIFICALLY

NOTED OTHERWISE

UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL

TESTING AGENCY

PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE

CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND

WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER.

CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR

THE DURATION OF THIS PROJECT

GUARANTEE ALL MATERIALS AND WORKMANSHIP ARE FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER AND OWNER, UNLESS NOTED OTHERWISE IN DIVISION 1. AT NO ADDITIONAL COSTS, PROVIDE THE CORRECTION OF

ANY DEFECTS INCLUDING REPAIR OR REPLACEMENT.

INCLUDE ALL COSTS ASSOCIATED WITH PERMITS, LICENSES, FEES, INSPECTIONS, TESTING AND

TEMPORARY POWER IN THE BID PRICE, UNLESS NOTED OTHERWISE.

IF HAZARDOUS MATERIALS ARE ENCOUNTERED, COMPLY WITH ALL APPLICABLE RULES, REGULATIONS

AND GUIDELINES CONCERNING REMOVAL, HANDLING, DISPOSAL AND PROTECTION AGAINST

ENVIRONMENTAL EXPOSURE OR POLLUTION. PROVIDE DOCUMENTATION OF SAID COMPLIANCE.

PROVIDE ELECTRONIC SUBMITTALS (PRODUCT DATA & SHOP DRAWINGS) FOR EACH MAJOR COMPONENT

OF THE ELECTRICAL SYSTEM FOR REVIEW BY THE ARCHITECT/ENGINEER AND OWNER. MAJOR

COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO, RACEWAYS, BOXES, WIRE AND CABLE, EQUIPMENT, DEVICES, LIGHT FIXTURES, SWITCHGEAR, PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, FIRE ALARM SYSTEM, ETC. ALL SUBMITTALS ARE TO BE REVIEWED AND APPROVED BY THE CONTRACTOR

FOR CONFORMANCE WITH THE PROJECT REQUIREMENTS PRIOR TO SUBMITTING TO THE

ARCHITECT/ENGINEER. ALLOW A MINIMUM OF TEN (10) BUSINESS DAYS FOR REVIEW BY

ARCHITECT/ENGINEER, UNLESS NOTED OTHERWISE IN DIVISION 1.

THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS

ACCEPTED BY THE ARCHITECT/ENGINEER AND OWNER, THE CONTRACTOR SHALL MAKE ALL

CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND

OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS. WHERE THE

CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST COMPENSATION FROM THE

CONTRACTOR FOR SAID SERVICES.

MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD DOCUMENTS SHALL BE ISSUED TO THE ARCHITECT/ ENGINEER FOR REVIEW AND THEN SUBMITTED TO THE OWNER WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.

PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL ACCEPTANCE.

THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE.

REQUIRED ROUTINE MAINTENANCE ACTIONS AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME, PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED

SERVICE AGENCY.

INCLUDE ALL COSTS FOR EXCAVATION, SAW CUTTING, DIRECTIONAL BORING, CORE DRILLING, BACKFILLING, SURFACE RESTORATION, REPAIR OF FINISHES, ETC. THAT IS REQUIRED IN ORDER TO MEET

THE PROJECT REQUIREMENTS.

INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR TEMPORARY POWER. ENGINEER OF

RECORD SHALL BE PROVIDED WITH ADDITIONAL COMPENSATION FROM THE CONTRACTOR WHERE

SIGNED & SEALED DRAWINGS ARE REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF

REQUIRED BY THE AHJ FOR THE TEMPORARY POWER.

LOCATE, IDENTIFY, PROTECT AND DOCUMENT ALL UTILITY LINES LOCATED WITHIN THE PROJECT BOUNDARY. FOR LOCATING SITE UTILITIES, CONTACT ALL LOCAL MUNICIPALITIES AND UTILITIES AT LEAST

48 HOURS PRIOR TO DIGGING.

INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES, REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH ALL APPLICABLE STATUTES REGARDING MERCURY- CONTAINING DEVICES, AND WITH ALL LOCAL, STATE AND FEDERAL APPLICABLE GUIDELINES AT THE TIME

OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF ACCEPTED DISPOSAL.

COORDINATION:

VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.) WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE

INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.

VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF

ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND

EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY

ELECTRICAL REQUIRED, UNLESS NOTED OTHERWISE.

THIS PROJECT REQUIRES COORDINATION DRAWINGS BY THE CONTRACTOR. PARTICIPATE IN THE

COORDINATION DRAWING PREPARATION PROCESS AND PROVIDE ALL NECESSARY INFORMATION

REQUIRED TO COORDINATE ALL TRADE INFORMATION.

ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE

COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF

WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.

WHERE WALLS ARE OF TILT-UP OR PRE-CAST CONSTRUCTION, PROVIDE COORDINATION FOR EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED WITHIN SUCH WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE WALLS, PRIOR TO CONSTRUCTION OF

THE WALLS.

LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE

DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH

CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGH-IN TO ENSURE PROPER NEC

CLEARANCES AND APPROPRIATE MOUNTING SURFACE.

REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR

DESIGN, TECHNOLOGY, STRUCTURAL, AND VENDOR EQUIPMENT DRAWINGS FOR RELATED

INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS PART OF THE

WORK.

WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN

WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE

DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE

CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND/OR SITE AFFECTED BY THIS WORK PRIOR TO SUBMITTING BID PRICE, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT MAY AFFECT EXECUTION OF THE WORK. SUBMISSION OF A BID PRICE SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT AND/OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED THAT COULD HAVE BEEN REASONABLY

OBSERVED WILL NOT BE RECOGNIZED.

WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE

APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

DEMOLITION REQUIREMENTS

DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN DASHED LINE TYPE ARE EXISTING TO BE DEMOLISHED; DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN LIGHT (SCREENED) SOLID LINE

TYPE ARE EXISTING TO REMAIN, UNLESS NOTED OTHERWISE.

EXISTING EQUIPMENT, LIGHT FIXTURES AND DEVICES SHOWN ARE BASED ON FIELD SURVEYS AND RECORD DRAWINGS PROVIDED BY THE OWNER, AND ARE NOT NECESSARILY INCLUSIVE OF ALL EXISTING ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND DEVICES WITHIN PROJECT AREAS. IT IS THE INTENT THAT THE DEMOLITION PLANS PROVIDE A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED

ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT

EXISTING CIRCUITING SHOWN IS BASED ON RECORD DRAWINGS AND THE SURVEYED PANEL DIRECTORIES, WHERE THEY WERE AVAILABLE. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE CONDITIONS SHOWN ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT, WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE

THE NEW WORK. FIELD CONDITIONS SHALL GOVERN.

WHERE EXISTING DEVICES ARE INDICATED TO REMAIN OR BE RELOCATED, ARE WITHIN THE SCOPE OF THIS PROJECT AND EXISTING CIRCUITING INFORMATION IS UNAVAILABLE, CONTRACTOR IS TO PROVIDE CIRCUIT TRACING TO IDENTIFY PANEL AND CIRCUIT SERVING THE DEVICE TO AND PROVIDE THAT INFORMATION TO THE ARCHITECT/ENGINEER PRIOR TO ROUTING CONDUITS AND WIRING FOR NEW DEVICES AND EQUIPMENT

WITHIN THE SCOPE OF THIS PROJECT.

WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR MUST EXTEND EXISTING CIRCUITING WHERE

NECESSARY TO MAINTAIN CONTINUITY OF CIRCUIT.

COORDINATE WITH THE OWNER FOR DISPOSAL OF ELECTRICAL ITEMS TO BE DEMOLISHED. OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS SUCH AS COVERPLATES, RECEPTACLES, LIGHT FIXTURES, PANELBOARDS, TRANSFORMERS, ETC. NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND

MATERIALS BEING REMOVED.

WHERE EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT ARE INDICATED TO BE DEMOLISHED, REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO NEAREST JUNCTION BOX TO MAINTAIN CIRCUIT CONTINUITY OF DEVICES AND EQUIPMENT TO REMAIN. WHERE PANELS ARE TO REMAIN, TURN BREAKER TO "OFF" POSITION AND LABEL THE CIRCUIT AS "SPARE" ON THE PANEL DIRECTORY.

ALL AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE PHASING WITH CONSTRUCTION MANAGER AND OWNER PRIOR TO DEMOLITION OF ANY ITEM WHICH MAY RESULT IN

INTERRUPTION OF POWER.

REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED OR

RENOVATED AREA. CAP BOTH ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE CUT.

CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES, UNLESS OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE DONE TO LOGICAL EDGES OF SURFACES AFFECTED AND SHALL MATCH IMMEDIATELY ADJACENT AREAS IN CONSTRUCTION, MATERIAL, FIRE RATING, FINISH AND COLOR.

FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND

OBTAIN CLARIFICATIONS FROM ENGINEER IF NECESSARY.

COORDINATE ALL POWER INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD, AND UTILITY COMPANY (WHERE APPLICABLE) AND DO NOT INTERRUPT POWER WITHOUT WRITTEN PERMISSION.

PROVIDE A MINIMUM OF ONE WEEK'S WRITTEN NOTIFICATION PRIOR TO WHEN POWER IS DESIRED TO BE INTERRUPTED. CONTRACTOR SHALL INVESTIGATE AND IDENTIFY ALL LOADS TO BE AFFECTED BY THE REQUESTED INTERRUPTION. CONTRACTOR SHALL SUBMIT WRITTEN SEQUENCE OF STEPS FOR EACH SHUTDOWN ALONG WITH THE ESTIMATED INTERRUPTION DURATIONS. MAKE ARRANGEMENTS TO MAINTAIN POWER TO ALL EXISTING NECESSARY LIGHTING, DEVICES AND EQUIPMENT AS NEEDED AND REQUESTED BY

THE OWNER PRIOR TO COMMENCEMENT OF WORK.

EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.

INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS DIAGRAMMATIC IN NATURE. FIELD VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ALL ELECTRICAL ITEMS SCHEDULED TO BE

DEMOLISHED AND PERFORM THE WORK AS INTENDED AND DEPICTED ON THE DRAWINGS.

UPDATE ALL EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS NECESSARY TO

REFLECT FINAL AS-BUILT CONDITIONS AT THE END OF CONSTRUCTION.

STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED AREA.

NOTIFY OWNER WHEN ITEMS ARE READY TO BE REMOVED.

ALL CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER SPACES. ENSURE THAT ALL CONDUITS, NEW OR EXISTING WITHIN THE PROJECT AREA ARE PROPERLY SUPPORTED IN ACCORDANCE

WITH THE NEC.

REMOVE ALL ABANDONED WIRING AND CONDUIT THAT IS WITHIN THE PROJECT AREA PRIOR TO THE END

OF CONSTRUCTION.

1.

2.

3.

4.

5.

6.

APPLICABLE CODES:

ALL WORK UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE AND IN ACCORDANCE

WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING CODES AND STANDARDS INCLUDING

THE REGULATIONS OF GOVERNING LOCAL, STATE, COUNTY AND OTHER APPLICABLE CODES.

REFER TO SPECIFICATIONS FOR ADDITIONAL CODE REQUIREMENTS:

BUILDING CODES:

FLORIDA BUILDING CODE, 8TH EDITION (2023)

FLORIDA ENERGY CONSERVATION CODE, 8TH EDITION (2023)

FLORIDA FIRE PREVENTION CODE, 8TH EDITION (2023)

ADDITIONAL CODES, STANDARDS, AND REQUIREMENTS

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).

INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA).

REQUIREMENTS OF LOCAL POWER COMPANY.

THE AMERICANS WITH DISABILITIES ACT (ADA).

OWNER'S PUBLISHED DESIGN STANDARDS.

ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE LISTED BY A

NATIONALLY RECOGNIZED TESTING LAB, AS DEFINED BY OSHA. WHERE NO LABELING OR

LISTING SERVICE IS AVAILABLE FOR CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE

SUBMITTED TO VALIDATE THAT EQUIPMENT MEETS OF EXCEEDS AVAILABLE STANDARDS.

NATIONAL FIRE PROTECTION (NFPA) STANDARDS:

NFPA 70, 2020 EDITION, NATIONAL ELECTRICAL CODE®.

NFPA 72, 2019 EDITION, NATIONAL FIRE ALARM AND SIGNALING CODE.

NFPA 90A, 2018 EDITION, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND

VENTILATING SYSTEMS.

NFPA 90B, 2018 EDITION, STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND

AIR-CONDITIONING SYSTEMS.

NFPA 101, 2021 EDITION, LIFE SAFETY CODE®.

APPLICABLE CODES

ELECTRICAL DEMOLITION NOTES

A/C AIR CONDITIONING

AC ALTERNATING CURRENT

ABV CLG ABOVE CEILING

AF AMPERE FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

AMP AMPERE

AT AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BRKR OR BKR BREAKER

C CONDUIT OR RACEWAY

CKT CIRCUIT

CB CIRCUIT BREAKER

CLG CEILING

CO CONDUIT OR RACEWAY ONLY

COAX COAXIAL CABLE

COND CONDUCTOR

CU COPPER

DEG DEGREE

DF DEMAND FACTOR

DISC DISCONNECT

DISC SW DISCONNECT SWITCH

EMT ELECTRIC METALLIC TUBING

EOL END OF LINE

EOR ENGINEER OF RECORD

ETR EXISTING TO REMAIN

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FATC FIRE ALARM TERMINAL CABINET

FBC FLORIDA BUILDING CODE

FLA FULL LOAD AMPERES

FT FEET

GF GROUND FAULT

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GND, G GROUND

HP HORSEPOWER

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS

IMC INTERMEDIATE METAL CONDUIT

IN INCHES

IT INSTANTANEOUS TRIP

JB OR J-BOX JUNCTION BOX

KCMIL ONE THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT AMPERES

KW KILOWATT

KWH KILOWATT HOURS

LBS POUNDS

LED LIGHT EMITTING DIODE

LP LIGHTNING PROTECTION

LT LIGHT

LTG LIGHTING

LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND

LSIA LONG TIME, SHORT TIME, INSTANTANEOUS, ALARM

LSI LONG TIME, SHORT TIME, INSTANTANEOUS

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MDP MAIN SERVICE DISTRIBUTION PANEL

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MSB MAIN SERVICE SWITCHBOARD

MTD MOUNTED

MTG MOUNTING

MTR MOTOR

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NF NON-FUSED

NL NON-LINEAR

OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION

P POLE

PB PULLBOX

PF POWER FACTOR

PNL PANEL

PRI PRIMARY

PVC POLYVINYL CHLORIDE

PWR POWER

REC, RECEPT RECEPTACLE

RGS, GRC RIGID GALVANIZED STEEL CONDUIT

RLA RUNNING LOAD AMPERES

RMS ROOT-MEAN-SQUARE

RPM REVOLUTIONS PER MINUTE

SCA SHORT CIRCUIT AMPERES

SD SMOKE DETECTOR

SEC SECONDARY

S/N SOLID NEUTRAL

SPD SURGE PROTECTIVE DEVICE

SPKR SPEAKER

SPST SINGLE POLE SINGLE THROW

SS STAINLESS STEEL

SST SOLID STATE TRIP

STD SHORT TIME TRIP

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TVEC TELEVISION EQUIPMENT CABINET

TYP TYPICAL

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

UL UNDERWRITERS LABORATORIES

UTIL UTILITY

V VOLT

VA VOLTAMPERE

VAR VOLT AMPERE REACTIVE

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

W WIRE

WP WEATHER PROOF

XFMR TRANSFORMER

XFR TRANSFER

IDENTIFICATION:

EQUIPMENT:

EQUIPMENT IDENTIFICATION SHALL BE MADE USING ENGRAVED LAMINATED

PHENOLIC OR MICARTA PLATES (INDENTED TAPE LABELS WILL NOT BE

PERMITTED). CHARACTERS SHALL BE WHITE ON A BLACK BACKGROUND AND

1/4" HIGH MINIMUM. PLATES SHALL BE SECURED TO THE PANELS BY MEANS

OF SCREWS OR METAL PRESSURE PINS. CEMENT, BY ITSELF, WILL NOT

ACCEPTABLE. ALL NAMEPLATES SHALL BE MOUNTED ON THE OUTSIDE

SURFACE OF THE PIECE OF EQUIPMENT. INDIVIDUALLY ENCLOSED SAFETY

SWITCHES, CIRCUIT BREAKERS, AND MOTOR STARTERS, PULL BOXES,

CONTROL CABINETS AND OTHER SUCH ITEMS SHALL BE IDENTIFIED

INDICATING LOAD, ELECTRICAL CHARACTERISTICS, AND SOURCE.

JUNCTION BOX IDENTIFICATION:

EACH JUNCTION BOX COVER SHALL BE LABELED WITH A PERMANENT "MAGIC"

MARKER OR OTHER MEANS TO IDENTIFY THE CIRCUITS WITHIN. FOR

EXAMPLE, A JUNCTION BOX CONTAINING LIGHTING CIRCUITS 21, 23, 25 FROM

PANEL L2A WOULD BE LABELED "L2A-21,23,25". TELEPHONE JUNCTION BOXES

SHALL BE LABELED "T". FIRE ALARM AND OTHER SYSTEM JUNCTION BOXES

SHALL BE LABELED ACCORDINGLY.

RECEPTACLE IDENTIFICATION:

ALL RECEPTACLES SHALL BE PROVIDED WITH 3/16" ENGRAVED AND

"FILLED-IN" LETTERING INDICATING PANEL BOARD AND CIRCUIT NUMBER

"WHERE FED FROM" FOR ALL RECEPTACLES.

JUNCTION BOXES:

ALL JUNCTION BOXES AND PULL BOXES SHALL BE SIZED PER N.E.C.

REQUIREMENTS AND BE OF THE PROPER NEMA CLASSIFICATION FOR THE

LOCATIONS WHERE THEY ARE INSTALLED. WHERE BOXES OCCUR ABOVE

OTHER THAN LIFT-OUT CEILINGS, ACCESS PANELS MUST BE PROVIDED.

CONDUIT AND FITTINGS:

ALL INTERIOR CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT).

ALL EXTERIOR CONDUIT SHALL BE RIGID METAL CONDUIT (RMC).

FITTINGS FOR ELECTRICAL METALLIC TUBING SHALL BE STEEL SET SCREW

OR COMPRESSION TYPE. DIE CAST FITTINGS OR CONNECTORS WILL NOT BE

ACCEPTABLE. EMT CONNECTORS TO BE SIMILAR TO T&B "INSULINE" WITH

COMPLETELY INSULATED THROATS. (FIELD APPLIED INSULATED THROATS

ARE NOT ACCEPTABLE).

CONDUITS BUSHINGS SHALL BE METALLIC WITH INSULATED THROATS.

INSULATING GROUNDING TYPE BUSHINGS SHALL BE PROVIDED WHERE

REQUIRED UNDER 'GROUNDING'.

CONDUITS SHOWN ROUTED OVERHEAD MAY NOT BE INSTALLED IN OR

BELOW SLABS OR IN WALLS.

NOT MORE THAN THREE CIRCUITS MAY BE INSTALLED IN ANY ONE CONDUIT

UNLESS OTHERWISE INDICATED.

ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED ON THE

DRAWINGS. EXPOSED CONDUIT WILL BE PERMITTED ONLY AS SHOWN ON THE

DRAWINGS. EXPOSED CONDUIT SHALL BE RUN PARALLEL WITH OR AT RIGHT

ANGLES TO THE BUILDING WALLS. ALL EMPTY CONDUITS SHALL BE PROVIDED

WITH A PLASTIC OR NYLON FISH WIRE.

EXPOSED CONNECTIONS TO MOTORS AND EQUIPMENT FROM OVERHEAD

CONDUITS SHALL CONSIST OF VERTICAL CONDUIT (MINIMUM SIZE 1") FROM

TYPE "LL" OR "LR" UNILET TO FLOOR FLANGE. CONNECTION TO EQUIPMENT

SHALL BE WITH FLEXIBLE METAL CONDUIT FROM TYPE FDT BOXES LOCATED

IN THE VERTICAL CONDUIT.

FLEXIBLE CONDUIT IN ALL AREAS OTHER THAN CEILING PLENUM SUBJECT TO

MOISTURE SHALL BE LIQUID-TIGHT FLEXIBLE CONDUIT. ALL ELECTRICAL

CONNECTIONS TO VIBRATION ISOLATED EQUIPMENT SHALL BE MADE WITH

FLEXIBLE CONDUIT.

GENERAL:

THE INSTALLATION SHALL COMPLY WITH ALL LOCAL LAWS AND

ORDINANCES APPLICABLE TO ELECTRICAL INSTALLATIONS, AND WITH

THE REGULATIONS OF THE NFPA WHERE SUCH REGULATIONS DO NOT

CONFLICT WITH THOSE LAWS. OBTAIN ALL PERMITS REQUIRED.

MANUFACTURERS DRAWINGS AND DATA:

SUBMIT TO THE ENGINEER FOR APPROVAL FIVE (5) COPIES OF THE

COMPLETE LIST OF ALL ELECTRICAL MATERIALS WHICH ARE PROPOSED

TO BE FURNISHED FOR THIS PROJECT. AS A MINIMUM THE

SUBMITTAL SHALL INCLUDE PANELBOARDS, A.I.C. OF BREAKERS

INSTALLED, LIGHT FIXTURES, BALLASTS, AND LAMPS.

STANDARD OF MATERIALS AND WORKMANSHIP:

ALL MATERIALS, EQUIPMENT AND APPARATUS COVERED BY THIS

SPECIFICATION SHALL BE NEW, OF CURRENT MANUFACTURE AND

SHALL BEAR THE SEAL OF APPROVAL OF THE UNDERWRITERS

LABORATORIES. ALL WORK SHALL BE EXECUTED IN A WORKMANLIKE

MANNER AND SHALL PRESENT A NEAT AND MECHANICAL APPEARANCE

WHEN COMPLETED.

STORAGE OF MATERIALS:

THE CONTRACTOR SHALL PROVIDE SUITABLE STORAGE FACILITIES FOR

ALL MATERIAL FURNISHED BY HIM UNDER THIS CONTRACT. ALL ITEMS

TO BE INSTALLED MUST BE FREE OF RUST AND DIRT.

FIREPROOFING:

ALL CONDUIT AND BOXES PASSING THROUGH OR INSTALLED WITHIN

FIRE WALLS AND SMOKE WALLS SHALL BE INSTALLED SO AS TO

MAINTAIN THE INTEGRITY OF THE WALL THROUGH WHICH IT PASSES.

BOXES TO BE INSTALLED WITH 1/8" OF WALL SURFACE.

TESTING:

AT THE COMPLETION OF THE WORK, A THOROUGH TEST SHALL BE

MADE IN THE PRESENCE OF THE ENGINEER OR HIS REPRESENTATIVE,

AND THE ENTIRE SYSTEM SHALL BE SHOWN TO BE IN PERFECT

WORKING CONDITION AS INTENDED BY THESE SPECIFICATIONS.

GUARANTEE:

THE CONTRACTOR SHALL LEAVE THE ENTIRE ELECTRICAL SYSTEM

INSTALLED BY HIM UNDER THIS CONTRACT IN PROPER WORKING

ORDER AND SHALL REPLACE, WITHOUT ADDITIONAL CHARGE, ALL WORK

OR MATERIAL WHICH MAY DEVELOP DEFECTS, ORDINARY WEAR AND

TEAR OR DAMAGE RESULTING FROM IMPROPER HANDLING EXCEPTED,

WITHIN A PERIOD OF ONE YEAR FROM THE DATE OF FINAL TESTING

AND ACCEPTANCE BY THE ENGINEER. BALLASTS SHALL BE INCLUDED

BUT LAMPS SHALL BE EXCLUDED.

CONDUCTORS:

ALL CONDUCTORS SHALL BE COPPER OF NOT LESS THAN

NINETY-EIGHT PERCENT (98%) CONDUCTIVITY, WITH NEC TYPE

THHN/THWN, 600 VOLT INSULATION. CONDUCTORS NO. 12 THROUGH

NO. 10 MAY BE SOLID OR STRANDED AND NO. 8 AND LARGER SHALL

BE STRANDED. NO CONDUCTORS SMALLER THAN NO. 12 SHALL BE

USED EXCEPT AS OTHERWISE NOTED. CONTROL CONDUCTORS SHALL

BE NO. 14. MC CABLE IS NOT PERMITTED.

NEUTRAL WIRES SHALL BE PIGTAILED TO RECEPTACLES SO THAT

RECEPTACLE CAN BE REMOVED FOR REPLACEMENT WITHOUT THE

NEUTRAL CONNECTION TO OTHER RECEPTACLES ON THE CIRCUIT

BEING DISCONNECTED. WHEN STRANDED WIRE IS USED FOR

RECEPTACLE AND LIGHTING CIRCUIT, CONNECTIONS TO THE DEVICES

SHALL BE MADE USING VINYL INSULATED "STAKON" CONNECTOR

TERMINALS.

CABLE AND WIRE SPLICES:

THE MATERIALS SHALL BE COMPATIBLE WITH THE CONDUCTORS,

INSULATIONS AND PROTECTIVE JACKETS OF THE RESPECTIVE CABLES

AND WIRES.

FOR CONDUCTOR SIZED NO. 6 AWG OR LARGER: SPLICES IN

CONDUCTORS SHALL BE MADE WITH INDENTER, CRIMP CONNECTORS

AND COMPRESSION TOOLS OR WITH BOLTED CLAMP TYPE

CONNECTORS TO INSURE A SATISFACTORY MECHANICAL AND

ELECTRICAL JOINT.

PANELBOARDS: (NEW BREAKERS)

INTERRUPTING RATINGS SHALL MATCH EXISTING PANELS TO MAINTAIN

FULLY RATED STATUS. BRANCH CIRCUIT PROTECTION DEVICES SHALL

BE MOLDED CASE CIRCUIT BREAKERS BOLT-0N TYPE. PANELS SHALL

BE FULLY RATED.

NEW TYPED DIRECTORY CARDS SHALL BE FURNISHED IN EACH PANEL.

WIRING DEVICES:

WALL SWITCHES:

ALL SWITCHES SHALL BE FLUSH ENCLOSED TYPE, SPECIFICATION

GRADE, RATED AT 20 AMPERES, 120/277 VOLTS, ALTERNATING

CURRENT ONLY, AND QUIET OPERATION. COLOR OF ALL DEVICES

SHALL BE IVORY.

MOTOR SWITCHES:

WITH INHERENT THERMAL OVERLOAD PROTECTION SHALL BE SQUARE

D, TYPE F FOR FLUSH OR SURFACE MOUNTING AS REQUIRED BY THE

LOCATION OF THE UNIT. UNITS SHALL BE FURNISHED WITH PILOT

LIGHTS AS INDICATED.

RECEPTACLES:

GROUNDING TYPE DUPLEX RECEPTACLE, RATED 20 AMPERES, 125

VOLTS, 2 WIRE, 3 POLE WITH GROUNDED SHUNT (YOKE PERMANENTLY

GROUNDED TO THIRD CLIP).

OTHER RECEPTACLES LISTED ON THE DRAWINGS SHALL BE

SPECIFICATION GRADE RECEPTACLES. ALL RECEPTACLES SHALL BE

IVORY IN COLOR.

DEVICES PLATES:

ALL PLATES FOR SWITCH, RECEPTACLES AND TELEPHONE OUTLETS

LOCATED IN FINISHED WALLS SHALL BE SMOOTH THERMOPLASTIC.

COLOR TO MATCH DEVICE. ALL PLATES FOR OUTLETS LOCATED ON

UNFINISHED WALL OR ON CONDULET TYPE FITTINGS SHALL BE ZINC

COATED SHEET METAL WITH ROUNDED OR BEVELED EDGES.

ACCEPTABLE MANUFACTURERS: HUBBELL, LEVITON, P&S.

OUTLET BOXES:

SWITCH AND RECEPTACLE OUTLET BOXES SHALL BE FOUR INCH (4")

SQUARE OR FOUR AND ELEVEN SIXTEENTHS INCH (4-11/16") A

MINIMUM OF 1-1/2" DEEP WITH SWITCH RING AS REQUIRE OR GANG

BOXES A MINIMUM OF 2" DEEP WHEN MORE THAN TWO DEVICES

MOUNT UNDER A COMMON COVER.

WALL TELEPHONE OUTLETS SHALL BE FOUR INCH (4") SQUARE BOXES

WITH STANDARD SWITCH COVERS AND TELEPHONE COVER PLATES.

LOCATION OF OUTLETS:

THE APPROXIMATE LOCATIONS OF OUTLETS, ETC. ARE SHOWN ON THE

DRAWINGS. THE EXACT LOCATIONS SHALL BE DETERMINED AT THE

BUILDING. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTE

THE LOCATIONS AND HEIGHTS OF CABINETS, ETC. BEFORE THE

INSTALLATION OF OUTLETS.

SAFETY SWITCHES:

SAFETY SWITCHES SHALL BE "HD" (HEAVY DUTY) UNLESS NOTED

OTHERWISE, FUSED OR NON-FUSIBLE AS INDICATED WITH NUMBER OF

POLES AS SHOWN OR REQUIRED. SAFETY SWITCHES FOR EQUIPMENT

MAY BE NON-FUSED ONLY IF EQUIPMENT IS UL TESTED WITH CIRCUIT

BREAKER PROTECTION. DISCONNECT SWITCHES SHALL BE PROVIDED

FOR ALL MOTORS.

ACCEPTABLE MANUFACTURERS: SQ-D, GE, SIEMENS.

GROUNDING:

IN GENERAL A GROUND WIRE SHALL BE INSTALLED IN EVERY

CONDUIT. THE CONDUIT INSTALLATION ITSELF SHALL SERVE AS AN

ADDITIONAL GROUNDING MEANS.

WHERE CONDUITS TERMINATE WITHOUT MECHANICAL CONNECTION (I.E.

LOCKNUTS AND BUSHINGS) TO PANELBOARDS, AND FOR ALL

TERMINATIONS OF CONDUIT WITH #4 OR LARGER; AND FOR ALL SIZES

OF METALLIC CONDUIT (RIGID OR FLEXIBLE) TERMINATING IN

CONCENTRIC KNOCKOUTS, THE FOLLOWING PROCEDURE SHALL BE

FOLLOWED: EACH CONDUIT SHALL BE PROVIDED WITH AN INSULATING

GROUND BUSHING AND EACH BUSHING CONNECTED WITH A BARE

COPPER CONDUCTOR TO THE GROUND BUS IN THE ELECTRICAL

EQUIPMENT. THE GROUND CONDUCTOR SHALL BE IN ACCORDANCE

WITH THE ARTICLE OF GROUNDING OF NEC.

HANGERS AND SUPPORTS:

STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-4, FACTORY-

FABRICATED COMPONENTS FOR FIELD ASSEMBLY. METALLIC COATINGS:

HOT-DIP GALVANIZE AFTER FABRICATION. PAINTED COATINGS:

MANUFACTURER'S STANDARD PAINTING COATING.

RACEWAY AND CABLE SUPPORTS: AS DESCRIBED IN NECA 1 AND NECA

101.

CONDUIT AND CABLE SUPPORT DEVICES: STEEL HANGERS, CLAMPS, AND

ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY

OR CABLE TO BE SUPPORTED.

MOUNTING, ANCHORING AND ATTACHMENT COMPONENTS: POWDER-

ACTUATED FASTENERS, MECHANICAL EXPANSION ANCHORS AND

CONCRETE INSERTS, AS APPLICABLE FOR SURFACE ATTACHMENT.

EXECUTION: COMPLY WITH NECA 1 AND 101 FOR APPLICATION OF

HANGERS AND SUPPORTS. SPACE SUPPORTS AS REQUIRED BY NFPA 70.

TOUCH UP PAINTING AS REQUIRED.

ELECTRICAL SPECIFICATIONS

S = SUPPLY

R = RETURN

DUCT SMOKE DETECTORS

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

N.T.S.

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL

SYMBOLS, LEGEND,

NOTES AND INDEX

E-001

01266083

ELECTRICAL DRAWING INDEX

SHEET DESCRIPTION

E-001 ELECTRICAL SYMBOLS, LEGEND, NOTES AND INDEX

E-101D ELECTRICAL DEMOLITION PLAN - LEVEL 1

E-102D ELECTRICAL DEMOLITION PLAN - LEVEL 2

E-101 ELECTRICAL PLAN - LEVEL 1

E-102 ELECTRICAL PLAN - LEVEL 2

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL ONE-LINE DIAGRAM AND PANEL SCHEDULES

No. Date Description

TELE/COM

MEN

MECHANICAL

ELEV.

EQUIP

LOBBY

HM

NOT IN SCOPE

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

1/8" = 1'-0"

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL

DEMOLITION PLAN -

LEVEL 1

E-101D

01266083

GENERAL NOTES:

LAYOUT IS BASED UPON NON-INVASIVE FIELD INVESTIGATION AND LIMITED EXISTING AS-BUILTS.

CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES BETWEEN THIS

LAYOUT AND FIELD CONDITIONS.

ALL CIRCUITS ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

REWORK EXISTING CONDUIT AND CONDUCTORS WHERE NECESSARY TO

MAINTAIN CONTINUITY OF ELECTRICAL SYSTEMS.

DE-ENERGIZE, DETACH, AND REMOVE ALL ELECTRICAL ITEMS INDICATED BY DASHED LINES UNLESS OTHERWISE NOTED. EXISTING TO REMAIN ITEMS ARE INDICATED BY HALF-TONE LINES UNLESS

OTHERWISE NOTED.

A.

B.

C.

SHEET NOTES:

DEINSTALL AND REMOVE EXISTING DISCONNECT. RETAIN EXISTING CONDUIT AND CONDUCTORS FOR

NEW UNIT.

1.

1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - LEVEL 1

No. Date Description

TRUE

NORTH

STAIR

STAIR

MECH

FIRST FLOOR

OPEN TO

IN

SI

D E

FA

C

E O

F

ST

U D

30"x48"

REFUGE

AREA OF

FIRST FLOOR

OPEN TO

IN

SI

D E

FA

C

E O

F

ST

U D

30"x48"

REFUGE

AREA OF

NOT IN SCOPE

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

1/8" = 1'-0"

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL

DEMOLITION PLAN -

LEVEL 2

E-102D

01266083

GENERAL NOTES:

LAYOUT IS BASED UPON NON-INVASIVE FIELD INVESTIGATION AND LIMITED EXISTING AS-BUILTS.

CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES BETWEEN THIS

LAYOUT AND FIELD CONDITIONS.

ALL CIRCUITS ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

REWORK EXISTING CONDUIT AND CONDUCTORS WHERE NECESSARY TO

MAINTAIN CONTINUITY OF ELECTRICAL SYSTEMS.

DE-ENERGIZE, DETACH, AND REMOVE ALL ELECTRICAL ITEMS INDICATED BY DASHED LINES UNLESS OTHERWISE NOTED. EXISTING TO REMAIN ITEMS ARE INDICATED BY HALF-TONE LINES UNLESS

OTHERWISE NOTED.

A.

B.

C.

SHEET NOTES:

DEINSTALL AND REMOVE EXISTING DISCONNECT. RETAIN EXISTING CONDUIT AND CONDUCTORS FOR

NEW UNIT.

1.

1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - LEVEL 2

No. Date Description

TELE/COM

MEN

MECHANICAL

ELEV.

EQUIP

LOBBY

HM

HM-20,22,24

CU-1

CU-2

HM-2,4,6

HM-8,10,12

AHU-1

AHU-2S

S

S

S

HDP-14,16,18

HDP-8,10,123

CU-4

NOT IN SCOPE

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

1/8" = 1'-0"

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL PLAN -

LEVEL 1

E-101

01266083

GENERAL NOTES:

NEW ITEMS PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR ARE INDICATED BY BOLD LINES.A.

SHEET NOTES:

PROVIDE 60 AMP (FUSED @ 40A) NEMA 3R DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE

REUSED.

PROVIDE 60 AMP (FUSED @ 50A) NEMA 3R DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE

REUSED.

PROVIDE 100 AMP (FUSED @ 80A) NEMA 1 DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE

REUSED.

EXISTING 120V UV LIGHT CIRCUIT TO BE REUSED.

EXISTING DUCT DETECTORS TO BE REUSED.

1.

2.

3.

4.

5.

1/8" = 1'-0"1 ELECTRICAL PLAN - LEVEL 1

No. Date Description

STAIR

STAIR

MECH

FIRST FLOOR

OPEN TO

IN

SI

D E

FA

C

E O

F

ST

U D

30"x48"

REFUGE

AREA OF

FIRST FLOOR

OPEN TO

IN

SI

D E

FA

C

E O

F

ST

U D

30"x48"

REFUGE

AREA OF

AHU-4

S

S

HDP-31,33,35

NOT IN SCOPE

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

1/8" = 1'-0"

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL PLAN -

LEVEL 2

E-102

01266083

GENERAL NOTES:

NEW ITEMS PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR ARE INDICATED BY BOLD LINES.A.

SHEET NOTES:

PROVIDE 100 AMP (FUSED @ 80A) NEMA 1 DISCONNECT. EXISTING CONDUIT AND CONDUCTORS MAY BE

REUSED.

EXISTING 120V UV LIGHT CIRCUIT TO BE REUSED.

EXISTING DUCT DETECTORS TO BE REUSED.

1.

2.

3.

1/8" = 1'-0"1 ELECTRICAL PLAN - LEVEL 2

No. Date Description

1MOUNTING HEIGHTS

No Scale

No Scale

PANELBOARD NAMEPLATE

TYPICAL 120/208V PANELBOARD

TYPICAL 277/480V PANELBOARD

PANEL "XXXX"

120/208V, 3∅∅, 4W

FED FROM PANEL "XXXX"

VIA T-XXX

FED FROM PANEL "XXXX"

277/480V, 3∅∅, 4W

PANEL "XXX"

1/16" THICK WHITE PLASTIC

WITH COLORED FACE PER

SPECIFICATIONS

PANELBOARD NAME

TYPICAL EQUIPMENT

AHU-X

480V, 3∅∅

FED FROM "NDH1-4"

AHU-X

480V, 3∅∅

FED FROM "NDH1-4"

WHITE PLASTIC WITH COLORED FACE PER

SPECIFICATIONS

ADHESIVE BACKING WHEN

INSTALLED

IN CONDITIONED SPACES

EQUIPMENT VOLTAGE

EQUIPMENT NAME

FASTEN WITH BRASS SCREWS

WHEN LOCATED IN NON-

CONDITIONED OR

EXTERIOR SPACES

No Scale

EQUIPMENT NAMEPLATE

F

EXIT

F

VC

W

CL

80"

48"

90"

48"

AFF

18"

AFF

36"

TELE. OUTLET

42" A.F.F. W/ 36" COUNTER,

39" A.F.F. W/ 30" COUNTER,

48" A.F.F. WITHOUT COUNTER

78" MAX.

TO TOP DEVICE

OR AS NOTED ON PLANS

PANELBOARD

DUPLEX RECEPTACLE

CENTERED OVER DOOR

(WHERE APPLICABLE)

CLOCK OUTLET FIRE SPEAKER & LIGHT

80" AFF FROM BOTTOM OF DEVICE

REMOTE TEST

VOLUME CONTROL

FA PULL

STATION

SWITCH

RECEPTACLE

TELE. OUTLET

FINISHED FLOOR

SPECIAL POWER OUTLET

CL

CL

CL

CL

CL

1MOUNTING HEIGHTS

No Scale

No Scale

PANELBOARD NAMEPLATE

TYPICAL 120/208V PANELBOARD

TYPICAL 277/480V PANELBOARD

PANEL "XXXX"

120/208V, 3∅∅, 4W

FED FROM PANEL "XXXX"

VIA T-XXX

FED FROM PANEL "XXXX"

277/480V, 3∅∅, 4W

PANEL "XXX"

1/16" THICK WHITE PLASTIC

WITH COLORED FACE PER

SPECIFICATIONS

1/4" HIGH LETTERING FOR

PANELBOARD NAME

1/8" HIGH LETTERING FOR

REMAINING TEXT

PANELBOARD NAME

PANELBOARD VOLTAGE

PANELBOARD SOURCE

TYPICAL EQUIPMENT

AHU-X

480V, 3∅∅

FED FROM "NDH1-4"

AHU-X

480V, 3∅∅

FED FROM "NDH1-4"

1/4" HIGH LETTERING FOR

PANELBOARD NAME

1/8" HIGH LETTERING FOR

REMAINING TEXT

FASTEN WITH BRASS SCREWS

WHEN LOCATED IN NON-

CONDITIONED OR

EXTERIOR SPACES

EQUIPMENT SOURCE

(PANEL & CIRCUIT)

No Scale

EQUIPMENT NAMEPLATE

F

F

VC

W

CL

80"

48"

90"

48"

AFF

18"

6" AFC

AFF

36"

TELE. OUTLET

42" A.F.F. W/ 36" COUNTER,

39" A.F.F. W/ 30" COUNTER,

48" A.F.F. WITHOUT COUNTER

78" MAX.

TO TOP DEVICE

OR AS NOTED ON PLANS

WALL MOUNTED LIGHT FIXTURES

AS NOTED ON PLANS

PANELBOARD

DUPLEX RECEPTACLE

CENTERED OVER DOOR

(WHERE APPLICABLE)

CENTERED BETWEEN

DOOR & CEILING

(COORDINATE WITH

ARCHITECT)

CLOCK OUTLET FIRE SPEAKER & LIGHT

80" AFF FROM BOTTOM OF DEVICE

REMOTE TEST

VOLUME CONTROL

FA PULL

STATION

SWITCH

RECEPTACLE

TELE. OUTLET

FINISHED FLOOR

SPECIAL POWER OUTLET

CL

CL

CL

CL

CL

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

N.T.S.

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL

DETAILS

E-501

01266083

ELEVATOR AHU-2 AHU-1

EXISTING

PANEL

"H1A"

EXISTING

SWITCHBOARD "HDP"

EXISTING

PANEL

"H2A"

EXISTING

PANEL

"L1A"

EXISTING PANEL "LMDP"

EXISTING

PANEL

"C1A" EXISTING

PANEL "C2A"

EXISTING

PANEL

"L2A"

EXISTING

PANEL "HE1"

EXISTING

PANEL "HE2"

EXISTING GENERATOR

EXISTING

PANEL

"LM"

EXISTING

"FACP"

EXISTING

PANEL

"HM"

EXISTING

PANEL "ER2"

UPS

TX-1

J

M

800A, 65,000

277/480V, 3PH, 4W

800AF

800AT

3P3P 100AT

100AF 3P 400AF

300AT

LSIG

ST EPO

FPL

METER

277/480V

LIGHTING PANEL

FIRST FLOOR SECOND FLOOR

LIGHTING PANEL

277/480V

277/480

277/480-120/208V

120/208V

RECEPTACLE

PANEL

225AT

250AF3P

FIRST FLOOR

PANEL

3P

RECEPTACLE

COMPUTER

120/208V

FIRST FLOOR

SECOND FLOOR

120/208V

COMPUTER

RECEPTACLE

3P

PANEL

SECOND FLOOR

3P

PANEL

RECEPTACLE

120/208V

FIRST FLOOR

PANEL

EMERGENCY

277/480V

3P

3P

277/480V

EMERGENCY

PANEL

SECOND FLOOR

ST800AF

800AT

G CONTROL AND

PROTECTION SYSTEM

GENERATOR

ANNUNCIATOR

3P

60AT

100AF3P

SS

SURGE

SUPPRESSOR

100AT

100AF

100AT

100AF250AF

225AT

120/208V

MECHANICAL

EQUIPMENT

3P

PANEL

FIRST FLOOR

SUPPRESSOR

SURGESS

100AT

100AF3P 3P 100AF

100AT

80A/3P 3P 250AF

225AT

277/480V

EQUIPMENT

MECHANICAL

PANEL

FIRST FLOOR

AUTOMATIC

TRANSFER

LSIG

800AT

800AF

3P

100AT

100AF

100AT

100AF

120/208V. 3PH, 4W

600A, 22,000 AIC

600AT

600AF

250AF

225AT

LSIG

60AT

100AF

3P

3P

SPACE SPACE

225KVA

3P

SPARE SPACE SPACE

250AF 250AF

SPARE

3P

SPACE

22,000 AIC20A

1P

2P

SPACE

225AT

250AF 100AF

100AT3P

EPO

LOCATED IN

ELECTRICAL RM.

SECOND FLOOR

PANEL

UPS

120/208V

60AT

100AF

AND

BYPASS

SWITCH

250AF3P

SPARE SPACE

EXISTING GENERATOR FOR

BUILDING

80A/3P 1 1

NEW WORK

AHU-4

80A/3P

2 2 2

"HDP" LOAD CALCULATION

EXISTING LOAD

- REMOVED LOAD

+ ADDED LOAD (INCLUDING "HM")

CALCULATED TOTAL LOAD

292.7 kVA

239.1 kVA

254.4 kVA

308.0 kVA

370.5 AMPS @

277/480V, 3PH, 4W

7370 Cabot Ct, Suite 103 Melbourne, FL 32940

P 321.636.0274 www.tlc-engineers.com

© Copyright 2026 TLC Engineering Solutions, Inc.

TLC Project No.:

COA 15

Seal

Drawing No.:

Scale:

Revisions:

Drawing Title:

Approved By:

Issue Date:

Project No.:

Drawn By:

Consultants:

PERMIT SET

N.T.S.

7/

/2

:3 0:

P

M C

:\R ev it

L oc al s\

_C oc oa

C ity

P ol ic e

D ep t H

VA

C R en o_

M

EP

_R

_L uk e.

Ad am sD

5C 5E

.rv t

C O

C O

A C

IT

Y

PO

LI

C E

D

EP

T H

VA

C

R

EN

O

K

IN

G S

T.

C

O C

O A, F L

01266083

07/22/2026

JDH

MMH

ELECTRICAL

ONE-LINE DIAGRAM

AND PANEL

SCHEDULES

E-601

01266083

12" = 1'-0"1 ELECTRICAL ONE-LINE

1: UTILIZE EXISTING BREAKER IN EXISTING PANELBOARD

2: PROVIDE NEW BREAKER IN EXISTING PANELBOARD.

KEYNOTES (KN):

TOTAL DEMAND CURRENT (A): 195

TOTAL DEMAND LOAD (KVA): 162.094

HVAC 126494 VA 100.00% 126494 VA TOTAL CONNECTED LOAD (KVA): 162.094

EQUIPMENT 35600 VA 100.00% 35600 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD PANEL TOTALS

CONNECTED PHASE AMPS (A) 195.059 195.059 195.059

CONNECTED PHASE LOAD (KVA) 54.031 54.031 54.031

41 SPACE -- 1 -- -- 1 -- SPACE 42

39 SPACE -- 1 -- -- 1 -- SPACE 40

37 SPACE -- 1 -- -- 1 -- SPACE 38

35 SPACE -- 1 -- -- 1 -- SPACE 36

33 SPACE -- 1 -- -- 1 -- SPACE 34

31 SPACE -- 1 -- -- 1 -- SPACE 32

29 SPACE -- 1 -- -- 1 -- SPACE 30

27 SPACE -- 1 -- -- 1 -- SPACE 28

25 SPACE -- 1 -- -- 1 -- SPACE 26

23 SPACE -- 1 -- 7.702 24

21 SPACE -- 1 -- 7.702 22

19 SPACE -- 1 -- 7.702

3 40 CU-4

17 1.667 10.200 18 15 1.667 10.200 16

EXIST. LOAD 20 3

1.667 10.200

3 45 EXIST. CU-3

11 17.200 7.702 12 9 17.200 7.702 10

EXIST. AHU-3 70 3

17.200 7.702

3 40 CU-2

5 0.000 9.561 6 3 0.000 9.561 4

SPARE 30 3

0.000 9.561

3 50 CU-1

KN CKT CIRCUIT DESCRIPTION TRIP(A) P A (KVA) B (KVA) C (KVA) P TRIP(A) CIRCUIT DESCRIPTION CKT KN SUPPLY FROM: HDP ENCLOSURE: NEMA 1 MAX. HEIGHT BUSING: NO MAINS TYPE: MLO RATING: 225 A

LOCATION: TELE/COM 114 MOUNTING: SURFACE DIST. / PHASE / WIRES: 480Y/277V / 3 / 4 K.A.I.C. RATING: 65 FEED THRU: NO

NAME: HM EXISTING

SHEET NOTES:

PROVIDE NEW BREAKER IN EXISTING PANELBOARD.

PROVIDE 3#3, 1#8 GND IN EXISTING 1-1/2" C. EXTEND AND REWORK CONDUIT, AS REQUIRED.

1.

2.

E-001 - ELECTRICAL SYMBOLS, LEGEND, NOTES AND INDEX
E-101D - ELECTRICAL DEMOLITION PLAN - LEVEL 1
E-102D - ELECTRICAL DEMOLITION PLAN - LEVEL 2
E-101 - ELECTRICAL PLAN - LEVEL 1
E-102 - ELECTRICAL PLAN - LEVEL 2
E-501 - ELECTRICAL DETAILS
E-601 - ELECTRICAL ONE-LINE DIAGRAM AND PANEL SCHEDULES

File details come from the government source that posted it. Updated .