Exhibit A UPS Replacement Drawings.pdf
PDF 866 KB Posted
- Attached to
- Caldwell Building Server Room UPS Replacement
- Solicitation number
- ITB-12587
- Issued by
- Leon County, Florida
About this file
These electrical engineering drawings for the Caldwell Building UPS Replacement project are prepared by H2 Engineering for the Florida Department of Commerce, located at 107 E Madison Street in Tallahassee. The documents detail a comprehensive electrical system modification involving the removal of two existing Uninterruptible Power Supply (UPS) units and the installation of a new UPS system with dual redundant modules and two battery cabinets. The project involves electrical demolition and renovation work in the basement electrical rooms, specifically targeting UPS-1 and UPS-2, with careful sequencing to minimize system downtime and ensure continuity of downstream electrical systems.
The technical specifications call for a high-efficiency UPS with specific requirements, including a Vertiv Liebert EXM model with multiple accessories such as surge protection, communication boards, and remote emergency power off capabilities. The drawings provide detailed electrical riser diagrams, panel schedules, and renovation notes, emphasizing compliance with the Florida Building Code 2023, National Electrical Code 2020, and all relevant jurisdictional regulations. The project includes precise instructions for electrical contractors regarding conduit installation, grounding, circuit breaker specifications, and device mounting, with particular attention to maintaining existing electrical infrastructure while implementing the new UPS system. The contract appears to prioritize minimal operational disruption and precise technical execution.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
480 4W
125 3 EXISTING
150 3 #2 #1 #6 3 150
0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0
20 20 20 0 0 0 20 20 20 12 12 12
0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0
28 28 28 0 0 0 28 28 28 28 28 28
48 48 48 0 0 0 48 48 48 39 39 39
172 172 172 0 0 0 172 172 172 142 142 142
LIGHTING AND APPLIANCE PANEL: UNNAMED PANEL - EXISTING
AMP RATING NEMA: X TYPE 1 ALUMINUM BUSES DOUBLE LUGS X BOLT-ON BREAKERS
/277 V, 3 PH, TYPE 3R X COPPER BUSES FEED THROUGH LUGS PLUG-ON BREAKERS
kA AIR TYPE 4X X 100% RATED BUS DOUBLE WIDE
SURFACE TYPE 12 SERVICE ENTRANCE RATED TRIPLE WIDE
C
IR
C U
IT
L O
A D
T Y
P E
SERVING
CKT BREAKER
S E
E
-L
IN
E
C O
N D
U
IT
S
IZ
E
P H
A S
E
N E
U T
R A
L S
IZ
E
E G
C S
IZ
E
CONNECTED LOAD
(VA)
CONNECTED LOAD
(VA)
E G
C S
IZ
E
P H
A S
E
N E
U T
R A
L S
IZ
E
C O
N D
U
IT
S
IZ
E
S E
E
-L
IN
E
CKT BREAKER
SERVING L
O
A D
T Y
P E
C
IR
C U
IT
T R
IP
S P
E C
IA
L
P O
L E
A B C A B C P O
L E
S P
E C
IA
L
T R
IP
1 O
EXISTING
27700 SPACE R 2
3 O 27700 SPACE R 4
5 O 27700 SPACE R 6
7 R SPACE SPACE R 8
9 R SPACE SPACE R 10
11 R SPACE SPACE R 12
13 R SPACE SPACE R 14
15 R SPACE SPACE R 16
17 R SPACE SPACE R 18
19 R SPACE SPACE R 20
21 SPACE SPACE 22
23 SPACE SPACE 24
25 SPACE SPACE 26
27 SPACE SPACE 28
29 SPACE SPACE 30
31 SPACE SPACE 32
33 SPACE SPACE 34
35 SPACE SPACE 36
37 SPACE SPACE 38
39 SPACE SPACE 40
41 SPACE SPACE 42
SUB-FEED BREAKER #1 SUB-FEED BREAKER #2
S U
B
R
UPS-1
20000
SPARE
S U
B
R 20000
R 20000
MAIN RATING POLE TRIP 100% RATED SHUNT COMM. COMMENTS
MAIN LUG ONLY
NEW WORK IS SHOWN BOLD. ALL ELSE IS
EXISTING TO REMAIN
LOAD CLASSIFICATION DEMAND
KVA (THIS PANEL) KVA (SUB-PANELS) KVA CONNECTED KVA DEMAND
A B C A B C A B C A B C
M MOTOR 100% CONNECTED (AMPS) 172
K KITCHEN APPLIANCE #: 0 100% CONNECTED (KVA) 143
R RECEPTACLES 10KVA+50%
L LIGHTING 100% DEMAND (AMPS) 142
H HVAC 100% DEMAND (KVA) 118
N N+1 REDUNDANT LOAD 50%
E ELECTRIC VEHICLE CHARGER KVA LIMIT 100%
O OTHER 100%
TOTAL LOAD (KVA)
TOTAL LOAD (AMPS)
UNINTERRUPTIBLE POWER SUPPLY (UPS) SCHEDULE
NAME LOCATION USE
NAMEPLATE RATING
ELECTRICAL
INPUT
NUMBER OF
INPUTS
ELECTRICAL
OUTPUT
MAINT.
BYPASS
KEYED
INTERLOCK
FULL LOAD
RUNTIME
(MINUTES)
CABINETS
BATTERY
EXPANSION
SPACE
OUTPUT
ISOLATION
TRANSFORMER
MANUFACTURER MODEL NUMBER ACCESSORIES
kW kVA
UPS-1 COMM RM B002A LEGALLY REQ'D 48 60 480 V / 3 PH - 4W 1 208 V / 3 PH - 4W INTERNAL YES 60 MULTIPLE 0% YES VERTIV LIEBERT EXM 1, 2, 3, 4,5,6
NOTES: ACCESSORIES:
1 SEE SPECIFICATIONS SECTION 263353 FOR ADDITIONAL EQUIPMENT REQUIREMENTS. 1 SPD
2 MANUFACTURER AND MODEL NUMBER ARE BASIS OF DESIGN. OR EQUALS ARE SUBJECT TO APPROVAL. 2 MODBUS COMMUNICATION BOARD
3 3 ACCESS CONTACT BOARD
4 SHUNT TRIP CONTACTS AND REMOTE EMERGENCY POWER OFF SWITCH
5 REDUNDANCY MODULE WITH ADDITIONAL BATTERY CABINET.
6 MAINTENANCE BY-PASS CABINET.
GENERAL NOTES
1. INSTALL ALL WORK IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2023, THE FLORIDA FIRE PREVENTION CODE, THE NATIONAL ELECTRICAL CODE 2020 EDITION, AND ALL CODES, ORDINANCES, RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION AT THIS SITE. WHERE CONFLICTS
OCCUR BETWEEN CODES AND THE CONSTRUCTION DOCUMENTS, THE MOST RESTRICTIVE
REQUIREMENTS SHALL GOVERN.
2. DRAWINGS ARE DIAGRAMMATIC, INDICATIVE OF WORK TO BE FURNISHED AND INSTALLED UNDER THIS
CONTRACT. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL DIMENSIONS.
3. FIELD VERIFY ALL DIMENSIONS AND ALL CONDITIONS. IF THE CONTRACTOR IS UNABLE TO INTERPRET THE CONTRACT DOCUMENTS, CONTRACTOR IS RESPONSIBLE TO REQUEST CLARIFICATION IN WRITING TO THE ARCHITECT. IF CONTRACTOR PROCEEDS WITH ANY WORK BEFORE OBTAINING CLARIFICATION, CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DEFICIENCIES ASSOCIATED THEREWITH.
4. BEFORE SUBMITTING FOR THE WORK, EACH BIDDER WILL BE RESPONSIBLE TO EXAMINE THE PREMISES AND SATISFY HIMSELF AS TO THE EXISTING CONDITIONS UNDER WHICH CONTRACTOR WILL BE OBLIGED TO OPERATE AND COMPLETE THE WORK UNDER THIS CONTRACT. NO ALLOWANCE WILL SUBSEQUENTLY BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR OMISSION ON
CONTRACTOR'S PART.
5. THE CONTRACTOR SHALL PAY FOR ALL INSPECTION PERMITS, CERTIFICATES, CONNECTION FEES, SYSTEM DEMAND CHARGES AND LICENSE FEES IN CONNECTION WITH CONTRACTOR'S WORK.
6. ALL WORK SHALL COMPLY WITH APPLICABLE O.S.H.A. AND E.P.A. REGULATIONS AND GUIDELINES.
7. ERECT AND MAINTAIN ALL REASONABLE PRECAUTIONS FOR SAFETY AND HEALTH INCLUDING POSTING
DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS INCLUDING PROMULGATING SAFETY
REGULATIONS. PROVIDE SAFETY PRECAUTIONS AND BARRICADES FOR PEDESTRIANS AT
CONSTRUCTION VEHICLE ACCESS AND EGRESS LOCATIONS.
8. COORDINATE AND SEQUENCE ALL DEMOLITION, CLEANING AND CONSTRUCTION WORK. SUBMIT A
COMPLETELY DETAILED CONSTRUCTION SCHEDULE PRIOR TO PRE-CONSTRUCTION CONFERENCE.
9. THE CONTRACTOR SHALL STRICTLY BE HELD TO THE PROJECT SCHEDULE. CONTRACTOR SHALL PROVIDE SUFFICIENT MANPOWER AND EQUIPMENT TO FULLY MOBILIZE, PROCEED WITH AND COMPLETE
THE WORK.
10. THE CONTRACTOR SHALL BE RESTRICTED TO AREAS SPECIFIED BY THE OWNER FOR ON-SITE STORAGE
OF CONSTRUCTION MATERIALS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION AND
SECURITY OF ALL EQUIPMENT AND MATERIALS.
11. THE CONTRACTOR SHALL MAINTAIN A CLEAN WORK ENVIRONMENT AT ALL TIMES AND SHALL CLEAN CONSTRUCTION SITE OF ALL DEBRIS AT COMPLETION OF THE JOB AND BEFORE FINAL PAYMENT IS MADE.
12. THE CONTRACTOR SHALL FURNISH "AS-BUILT" DRAWINGS TO THE OWNER AT COMPLETION OF
CONSTRUCTION.
13. CONTRACTOR SHALL GUARANTEE THE WORK AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. THIS GUARANTEE SHALL BE IN ADDITION TO THE WARRANTIES PROVIDED BY
MATERIAL SUPPLIERS AND MANUFACTURERS.
14. CONTRACTOR'S USE OF AN APPROVAL STAMP ON DOCUMENTS SUBMITTED AS SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND SIMILAR SUBMITTALS CERTIFIES THAT THE CONTRACTOR HAS COMPLIED WITH THE CONTRACT DOCUMENT REQUIREMENTS RELATED TO "SHOP DRAWINGS, PRODUCT DATA AND
SAMPLES".
15. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR DEVIATIONS FROM REQUIREMENTS
OF THE CONTRACT DOCUMENTS BY THE ARCHITECT/ENGINEER'S APPROVAL OF SHOP DRAWINGS,
PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS UNLESS THE CONTRACTOR HAS SPECIFICALLY INFORMED THE ARCHITECT/ENGINEER IN WRITING OF SUCH DEVIATION AT THE TIME OF SUBMITTAL AND
THE ARCHITECT/ENGINEER HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION. THE
CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR ERRORS OR OMISSIONS IN SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS BY THE ARCHITECT/ENGINEER'S
APPROVAL THEREOF.
16. NOTE ANY SPECIAL REQUIREMENTS INVOLVED IN INSTALLING THE EQUIPMENT IN THE BUILDING.
DISMANTLING AND REASSEMBLING OF ANY EQUIPMENT SHALL BE DONE AS REQUIRED FOR ENTRY INTO
THE BUILDING AND EQUIPMENT ROOMS.
17. ENTRY AND REMOVAL OF EQUIPMENT FROM THE BUILDING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL REPAIR ANY DAMAGED MATERIALS TO THEIR ORIGINAL CONDITION.
SURFACES SHALL BE REPAIRED TO MATCH THE EXISTING ADJACENT UNDAMAGED SURFACES.
18. SUPPORTS AND HANGERS SHALL PRESENT A NEAT, ORDERLY APPEARANCE.
19. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE WALL ASSEMBLIES AND
ACOUSTICAL WALLS.
20. BEAM AND FLOOR PENETRATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. BEAM
SLEEVES AND BEAM REINFORCING APPROVED BY STRUCTURAL ENGINEER SHALL BE FURNISHED AND
INSTALLED BY THIS CONTRACTOR.
21. THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION. THE OWNER WILL MAKE ALL REASONABLE EFFORTS TO ASSIST THE CONTRACTOR IN COMPLETING THE WORK. COORDINATE ALL
WORK WITH THE OWNER'S DESIGNATED REPRESENTATIVE.
22. EXIT WAYS SHALL BE KEPT CLEAR. IF AN EXIT MUST BE TEMPORARILY BLOCKED, PROVIDE THE
REQUIRED BARRICADE AND DIRECTIONAL SIGNS FOR TEMPORARY EXITING AND SAFETY.
23. REMOVE AND REPAIR OR RE-INSTALL EXISTING CEILING ASSEMBLIES AS REQUIRED. REPLACE ANY
ASSEMBLIES DAMAGED OR SOILED DURING CONSTRUCTION.
24. PROVIDE PROPER PROTECTIVE MEASURES TO PROTECT EXISTING FURNITURE, CARPET AND FINISHES DURING THE COURSE OF CONSTRUCTION. TAKE CARE NOT TO DAMAGE EXISTING SURFACES. REPAIR
TO MATCH EXISTING CONDITIONS AS REQUIRED.
25. SEAL ALL HOLES IN WALLS, CEILINGS, FLOORS, ETC. TO MATCH EXISTING ADJACENT SURFACES WHERE
EQUIPMENT, CONDUIT AND/OR PIPING ARE REMOVED.
26. EXISTING EQUIPMENT IS THE PROPERTY OF THE OWNER AND SHALL BE DISPOSED OF AS DIRECTED BY THE OWNER. DISPOSE OF ALL MATERIALS AND EQUIPMENT SHOWN TO BE REMOVED IN ACCORDANCE
WITH LOCAL REGULATIONS.
27. ITEMS REMOVED AND SAVED FOR REUSE SHALL BE PROTECTED FROM DAMAGE DURING
CONSTRUCTION. CONTRACTOR SHALL IDENTIFY ANY DEFECTIVE MATERIALS PRIOR TO DEMOLITION.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGE TO MATERIALS AT PROJECT COMPLETION NOT
IDENTIFIED PRIOR TO DEMOLITION.
DRAWING INDEX
ELECTRICAL DEMOLITION NOTES
1. UNLESS OTHERWISE NOTED, REMOVE ALL ELECTRICAL MATERIALS AND EQUIPMENT FROM AREAS
INDICATED FOR DEMOLITION.
2. REMOVE ALL ELECTRICAL EQUIPMENT (CONDUIT, POWER & CONTROL WIRING, DISCONNECT SWITCHES, STARTERS,ETC.) RELATED TO EQUIPMENT BEING REMOVED OR REPLACED.
3. REMOVE UNUSED CONDUIT TO THE EXTENT NECESSARY TO ACCOMMODATE NEW WORK AND WHERE CONDUIT IS VISIBLE ABOVE THE FLOOR LINE. EXISTING UNUSED CONDUIT WHICH IS CONCEALED, AND WHICH DOES NOT INTERFERE WITH THE WORK, MAY REMAIN IN PLACE. SEAL ABANDONED LINES THAT
REMAIN IN PLACE BEHIND WALLS OR FLOOR SURFACES. REMOVE EXISTING UNUSED WIRES.
4. WIRING AND CONDUIT TO ELECTRICAL DEVICES BEING REMOVED SHALL BE REMOVED BACK TO NEAREST JUNCTION BOX. ANY DEVICES DOWNSTREAM FROM THESE POINTS SHALL REMAIN OPERABLE.
5. CONTRACTOR SHALL, UPON COMPLETION OF WORK, ENSURE ALL EXISTING CIRCUITS ADJACENT THE
REMODELED AREA(S) ARE IN PROPER WORKING CONDITION.
6. CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS TO ELECTRICAL DEVICES REQUIRED TO
ACCOMMODATE NEW WALLS AND CEILINGS. BECAUSE OF THE NATURE OF THE JOB, UNFORESEEN
INTERFERENCES MAY OCCUR. CLOSE COORDINATION BETWEEN TRADES IS REQUIRED. VERIFY ALL
CONNECTION REQUIREMENTS BEFORE ROUGH-IN.
ELECTRICAL GENERAL NOTES
1. WIRING SHALL BE COPPER, TYPE THHN/THWN-2 IN RACEWAY UNLESS NOTED OTHERWISE. RIGID ELECTRICAL NON-METALLIC SCHEDULE 40 PVC SHALL BE USED IN SLABS AND BELOW GRADE ; RIGID STEEL CONDUIT (RSC) SHALL BE USED WHERE EXPOSED TO PHYSICAL DAMAGE; ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ELSEWHERE WHERE APPROVED BY N.E.C. AND LOCAL CODES. FLEXIBLE METAL CONDUIT (FMC) SHALL BE STEEL AND SHALL BE USED TO CONNECT MOVEABLE EQUIPMENT AND/OR SUBJECT TO VIBRATION; LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LFMC) SHALL BE USED
OUTDOORS OR WHERE SUBJECT TO MOISTURE.
2. CONDUIT SHALL BE STRAPPED IN ACCORDANCE WITH REQUIREMENTS OF N.E.C.
3. CONTRACTOR SHALL BOND AND GROUND SYSTEMS AND EQUIPMENT PER ARTICLE 250 OF N.E.C.
PROVIDE A GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH ARTICLE 250-122 N.E.C. ON ALL
RECEPTACLES AND POWER BRANCH CIRCUITS.
4. THE CONTRACTOR SHALL COORDINATE THE CIRCUIT REQUIREMENTS WITH THE MANUFACTURER OF THE ACTUAL EQUIPMENT FURNISHED UNDER OTHER DIVISIONS OF WORK. THE CIRCUIT BREAKER, WIRE
AND CONDUIT SHALL BE SIZED AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER.
5. CIRCUIT BREAKERS SHALL BE BOLT-IN TYPE.
6. PROVIDE A LAMINATED PLASTIC NAMEPLATE IDENTIFYING EACH NEW PANELBOARD, MOTOR STARTER
AND DISCONNECT SWITCH. LETTERING SHALL BE 1/2" MINIMUM AND SHALL IDENTIFY EQUIPMENT
SERVED, FEEDER ORIGINATION AND CIRCUIT NUMBER. SECURE NAMEPLATE WITH SCREWS TO
EQUIPMENT TO BE IDENTIFIED. PLASTIC TAPE IS NOT APPROVED.
7. EQUIPMENT TO BE FURNISHED UNDER OTHER SECTIONS OF THE SPECIFICATIONS THAT REQUIRE ELECTRICAL CONNECTIONS SHALL BE RECEIVED AND SET WITH ROUGH-IN AND FINAL CONNECTIONS
MADE UNDER THESE SECTIONS.
8. DEVICE MOUNTING HEIGHTS INDICATED SHALL BE TO DEVICE CENTER LINE.
9. RELOCATE, AS REQUIRED, ANY EXISTING WIRE AND CONDUIT WHICH INTERFERES WITH INSTALLATION
OF THE NEW WORK.
10. EACH FEEDER, UNGROUNDED CONDUCTOR, AND GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY
PHASE OR LINE AND SYSTEM AT ALL TERMINATION, CONNECTION, AND SPLICE POINTS.
ABBREVIATIONS
ACT ABOVE COUNTERTOP
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ATS AUTOMATIC TRANSFER SWITCH
BF BELOW RAISE COMPUTER FLOOR
C CONDUIT
CLG DEVICE LOCATED ON CEILING
CNT CONTACTOR
DISC DISCONNECT
DN DOWN
EC ELECTRICAL CONTRACTOR
EM FIXTURE PROVIDED WITH EMERGENCY BATTERY OR ON EMERGENCY CIRCUIT
ER EXISTING ELECTRICAL DEVICE RELOCATED TO NEW POSITION
EX EXISTING ELECTRICAL DEVICE TO REMAIN
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFIB GROUND FAULT INTERRUPTER BREAKER
G GROUND
GRC GALVANIZED RIGID CONDUIT
LCP LIGHTING CONTROL PANEL
NIS NOT IN SCOPE
PGB POWER GROUNDING BAR
PNL ELECTRICAL PANEL
RE REPLACE EXISTING ELECTRICAL DEVICE (AND COVER PLATE) AT THIS LOCATION
REL RELOCATE EXISTING ELECTRICAL DEVICE
TGB TELECOMMUNICATIONS GROUNDING BAR
TP TAMPER PROOF DEVICE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
WP WEATHERPROOF
EXISTING SWITCH TO BE REMOVED
POWER
DUPLEX RECEPTACLE - 120 VOLT, 20 AMP, 3 POLE GROUNDING TYPE, MOUNT
18" AFF WITH GROUND PRONG UP UNLESS NOTED OTHERWISE.
WIRE IN CONDUIT - CONCEALED IN WALL OR CEILING.
WIRE IN CONDUIT - CONCEALED IN FLOOR OR UNDERGROUND.
CONDUIT - STUB OUT AND CAP
HOMERUN TO PANEL - ARROW INDICATE NUMBER OF CIRCUITS. SHORT SLASH
MARK(S) INDICATE NUMBER OF PHASE CONDUCTORS. LONG SLASH MARK(S)
INDICATE NEUTRAL CONDUCTOR(S). LONG SLASH MARK WITH HOOK INDICATES
GREEN GROUND WIRE; WHERE NOT SHOWN GROUND WIRE IS STILL REQUIRED
IN EACH FEEDER, LIGHTING, RECEPTACLE, AND POWER BRANCH CIRCUIT. NO
SLASH MARKS INDICATE 2 CURRENT CARRYING CONDUCTORS AND GROUND
WIRE. THERE SHALL BE NO SHARED NEUTRALS BETWEEN MULTIPLE CIRCUITS.
ELECTRICAL PANEL - 120/208 VOLT
ELECTRICAL PANEL - 277/480 VOLT
EMERGENCY "STOP" PUSH-BUTTON
POWER GROUNDING BARPGB
* EQUIPMENT SIZES WILL BE INDICATED AS FOLLOWS:
STARTER NEMA SIZE
(NO # SHOWN FOR
DISC SWITCHES)
AMP RATING & POLE QTY.
NEMA ENCLOSED TYPE
NON-FUSED (AS SHOWN)
1 / 30A / 3P / 3R / NF
25AF
25ACB
FUSED (AS SHOWN)
CIRCIUT BREAKER AMPS (AS SHOWN)
J JUNCTION BOX - 4" SQUARE (UNO)
DISCONNECT SWITCH - SEE DRAWING OR MECHANICAL EQUIPMENT
SCHEDULE FOR SIZE
DEMOLITION
ELECTRICAL DEVICES TO BE REMOVED
RELOCATE EXISTING DEVICE TO POSITION SHOWN
REL
NTS
PARTIAL POWER RISER DIAGRAM
150A150A
PANEL
'CPB'
100A
208/120V
UPS
BASEMENT ELEC RM B010
LOAD CENTER
PANELS
100A
4#3, #8G, 1 1/4"C
4#4/0, #4G, 2 1/2"C
4#2/0,#4G, 2 1/2"C
P1-225A P2-225A P3-225A P4-225A
UNNAMED
PANEL
400A
480/277V 3PH
GENERAL NOTES
1. NEW WORK AND DEVICES ARE SHOWN BOLD. ALL ELSE IS EXISTING TO REMAIN.
BASEMENT RM B002A
ATS#2600A
DISC
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
H
B
C
D
E
F
G
H
A
1 2 3 4 5 6 7 8 9 10
DRAWING NO.
SUBMITTAL
PHASE CHECK
REVISIONS
SHEET TITLE
SEAL
DRAWNDATE
Florida Registry #2485
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2ENGINEERING, INC., IS PROHIBITED.
H2E PROJECT No.
114 EAST 5th AVENUE
TALLAHASSEE, FL 32303
PHONE 850.224.7922
www.H2Engineering.com
Anthony D. Wyrick, P.E. #98346
/2
/2
:0
:5
A
M A u to d e s k D o c s /2
-1
F la C o m m e rc e
C a ld w e ll
B ld g U
P S r e p la c e m e n t/
-1
M
E P
C e n tr a l_
F la
.C o m m e rc e
C a ld w e ll
B ld g U
P S r e p la c e m e n t_ R
.r v t
24187
E0.1
GENERAL NOTES &
LEGENDS
CONSTRUCTION DOCUMENTS 2025-03-14 GAG
CALDWELL BLDG, UPS
REPLACEMENT
24-187
107 E MADISON ST,
TALLAHASSEE, FL 32399
FLORIDA DEPARTMENT
OF COMMERCE
ADW
E0.1 GENERAL NOTES & LEGENDS
E1.1 BASE FLOOR PLAN
# Description Date
1 ADDENDUM #1 04/24/24
1 1
Exhibit A
B004
MECH. RM.
B003
LOBBY
B009
ELEC.
RM.
EXIST.
ELEV.
B010
W.TRANSFORMER
RM.
B022
COMPUTER ROOM
B004
MECH. RM.
B003
LOBBY
B009
ELEC.
RM.
EXIST.
ELEV.
B010
W.TRANSFORMER
RM.
B022
COMPUTER ROOM
CPA CP
CPB
LB3
ATS
#2DP3
LBD
150kVA
300kVA
150kVA
ROUTE NEW FEEDER TO
EXISTING POWER CENTER.
REFER TO RISER DIAGRAM
FOR FEEDER INFORMATION.
POWER
CENTER
200A
DISC
600A
DISC
UNNAMED PANEL
UPS-1
RELOCATE EXISTING PANEL.
RECONNECT EXISTING
CIRCUITS PRESERVED
DURING DEMOLITION. EXTEND
#10 WIRE, #10G IN 3/4 CONDUIT
TO MAKE NEW CONNECTION.
CPB
ER
CONNECT TO EXISTING FEEDER
9' - 0"
AVAILABLE WALL SPACE
CPB
CPA CP
ATS
#2
UPS1 UPS2
LB3
DP3
LBD
150kVA
300kVA
POWER
CENTER
DEMOLISH UPS-2 CIRCUIT
BACK TO PANEL. MARK
BREAKER AS SPARE AND
TURN TO THE OFF POSITION.
UNNAMED PANEL
200A
DISC
600A
DISC
DEMOLISH EXISTING UPS-1 AND
UPS-2. PRESERVE EXISTING
UPS-1 CIRCUIT FOR REUSE
DURING RENOVATION.
CPB REL
TEST EXISTING CIRCUITS TO VERIFY
ABANDONED AND IN-USE CIRCUITS.
CONFIRM ABANDONED CIRCUITS WITH THE
OWNER AND DEMOLISH. DISCONNECT
EXISTING IN-USE CIRCUITS AND PRESERVE
FOR REUSE DURING RENOVATION.
NIS
DEMOLITION GENERAL NOTES
1. ALL DEVICES SHOWN DASHED ARE TO BE DEMOLISHED. ALL OTHER DEVICES ARE EXISTING TO REMAIN.
2. WHERE DEVICE IS SHOWN TO BE REMOVED IN EXISTING WALL TO REMAIN , REMOVE BACK BOX AND FINISH
WALL / FLOOR / CEILING TO MATCH SURROUNDING AREA.
3. DISCONNECT WIRING AT PANEL OR NEAREST DEVICE OR JUNCTION BOX TO REMAIN ON SAME CIRCUIT.
4. WHERE SURFACE RACEWAYS EXISTS TO DEVICE , REMOVE RACEWAY BACK TO POINT BEHIND FINISHED
SURFACE , INCLUDING BACK BOX RECESS IN SURFACE'S PATCH SURFACE.
5. SEQUENCE DEMOLITION OF THE EXISTING UPS TO PROVIDE MINIMAL DOWNTIME TO THE SYSTEM DOWN STREAM OF THE UPS. PROVIDE TEMPORARY BYPASS AS NECESSARY TO ENSURE CONTINUITY OF THE DOWN
STREAM SYSTEM DURING THE UPS DEMOLITION.
RENOVATION GENERAL NOTES
1. ALL DEVICES SHOWN SHADED ARE EXISTING. ALL OTHER DEVICES ARE NEW.
2. COORDINATE WITH OWNER ANY REQUIRED DOWN TIME TO FACILITATE CONNECTION TO THE NEW UPS SYSTEM. PROVIDE LINE ITEM PROVISIONS IN THE BID TO COVER WEEKEND OR AFTERHOURS WORK
REQUIRED TO MAKE THE NEW CONNECTION.
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
H
B
C
D
E
F
G
H
A
1 2 3 4 5 6 7 8 9 10
DRAWING NO.
SUBMITTAL
PHASE CHECK
REVISIONS
SHEET TITLE
SEAL
DRAWNDATE
Florida Registry #2485
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2ENGINEERING, INC., IS PROHIBITED.
H2E PROJECT No.
114 EAST 5th AVENUE
TALLAHASSEE, FL 32303
PHONE 850.224.7922
www.H2Engineering.com
Anthony D. Wyrick, P.E. #98346
/2
/2
:0
:5
A
M A u to d e s k D o c s /2
-1
F la C o m m e rc e
C a ld w e ll
B ld g U
P S r e p la c e m e n t/
-1
M
E P
C e n tr a l_
F la
.C o m m e rc e
C a ld w e ll
B ld g U
P S r e p la c e m e n t_ R
.r v t
24187
E1.1
BASE FLOOR PLAN
CONSTRUCTION DOCUMENTS 2025-03-14 GAG
CALDWELL BLDG, UPS
REPLACEMENT
24-187
107 E MADISON ST,
TALLAHASSEE, FL 32399
FLORIDA DEPARTMENT
OF COMMERCE
ADW
PROJECT
NORTH
1/4" = 1'-0"
BASE FLOOR PLAN RENO
PROJECT
NORTH
1/4" = 1'-0"
BASE FLOOR PLAN DEMO
# Description Date
1 ADDENDUM #1 04/24/24BASEMENT KEYPLAN
| Sheets |
| E0.1 - GENERAL NOTES & LEGENDS |
| E1.1 - BASE FLOOR PLAN |
| G0.0 - COVER SHEET |
File details come from the government source that posted it. Updated .