Exhibit A UPS Replacement Drawings.pdf

PDF 866 KB Posted

Attached to
Caldwell Building Server Room UPS Replacement
Solicitation number
ITB-12587
Issued by
Leon County, Florida

About this file

The document is a set of electrical engineering drawings for a UPS (Uninterruptible Power Supply) replacement project for the Florida Department of Commerce, located at 107 E Madison St in Tallahassee, FL. The project involves replacing existing UPS systems in the Caldwell Building's basement, specifically targeting UPS-1 and UPS-2 in the electrical and computer rooms. The drawings, prepared by H2 Engineering, detail the demolition and renovation plans for the electrical infrastructure, including a partial power riser diagram, base floor plan, and comprehensive notes on electrical and demolition work.

The project scope includes removing existing UPS equipment, preserving critical circuits, and installing a new UPS system with minimal downtime to the downstream electrical systems. The drawings specify technical details such as electrical panel configurations, conduit routing, and power distribution, with a focus on maintaining system continuity during the renovation. The project appears to be funded by the Florida Department of Commerce and is part of a planned electrical infrastructure upgrade, with the engineering work dated March 14, 2025, and an addendum issued on April 24, 2024. The documentation emphasizes careful coordination with the building owner, adherence to electrical codes, and minimal disruption to the existing operational environment.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

480 4W

125 3 EXISTING

150 3 #2 #1 #6 3 150

0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0

20 20 20 0 0 0 20 20 20 12 12 12

0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0

28 28 28 0 0 0 28 28 28 28 28 28

48 48 48 0 0 0 48 48 48 39 39 39

172 172 172 0 0 0 172 172 172 142 142 142

LIGHTING AND APPLIANCE PANEL: UNNAMED PANEL - EXISTING

AMP RATING NEMA: X TYPE 1 ALUMINUM BUSES DOUBLE LUGS X BOLT-ON BREAKERS

/277 V, 3 PH, TYPE 3R X COPPER BUSES FEED THROUGH LUGS PLUG-ON BREAKERS

kA AIR TYPE 4X X 100% RATED BUS DOUBLE WIDE

SURFACE TYPE 12 SERVICE ENTRANCE RATED TRIPLE WIDE

C

IR

C U

IT

L O

A D

T Y

P E

SERVING

CKT BREAKER

S E

E

-L

IN

E

C O

N D

U

IT

S

IZ

E

P H

A S

E

N E

U T

R A

L S

IZ

E

E G

C S

IZ

E

CONNECTED LOAD

(VA)

CONNECTED LOAD

(VA)

E G

C S

IZ

E

P H

A S

E

N E

U T

R A

L S

IZ

E

C O

N D

U

IT

S

IZ

E

S E

E

-L

IN

E

CKT BREAKER

SERVING L

O

A D

T Y

P E

C

IR

C U

IT

T R

IP

S P

E C

IA

L

P O

L E

A B C A B C P O

L E

S P

E C

IA

L

T R

IP

1 O

EXISTING

27700 SPACE R 2

3 O 27700 SPACE R 4

5 O 27700 SPACE R 6

7 R SPACE SPACE R 8

9 R SPACE SPACE R 10

11 R SPACE SPACE R 12

13 R SPACE SPACE R 14

15 R SPACE SPACE R 16

17 R SPACE SPACE R 18

19 R SPACE SPACE R 20

21 SPACE SPACE 22

23 SPACE SPACE 24

25 SPACE SPACE 26

27 SPACE SPACE 28

29 SPACE SPACE 30

31 SPACE SPACE 32

33 SPACE SPACE 34

35 SPACE SPACE 36

37 SPACE SPACE 38

39 SPACE SPACE 40

41 SPACE SPACE 42

SUB-FEED BREAKER #1 SUB-FEED BREAKER #2

S U

B

R

UPS-1

20000

SPARE

S U

B

R 20000

R 20000

MAIN RATING POLE TRIP 100% RATED SHUNT COMM. COMMENTS

MAIN LUG ONLY

NEW WORK IS SHOWN BOLD. ALL ELSE IS

EXISTING TO REMAIN

LOAD CLASSIFICATION DEMAND

KVA (THIS PANEL) KVA (SUB-PANELS) KVA CONNECTED KVA DEMAND

A B C A B C A B C A B C

M MOTOR 100% CONNECTED (AMPS) 172

K KITCHEN APPLIANCE #: 0 100% CONNECTED (KVA) 143

R RECEPTACLES 10KVA+50%

L LIGHTING 100% DEMAND (AMPS) 142

H HVAC 100% DEMAND (KVA) 118

N N+1 REDUNDANT LOAD 50%

E ELECTRIC VEHICLE CHARGER KVA LIMIT 100%

O OTHER 100%

TOTAL LOAD (KVA)

TOTAL LOAD (AMPS)

UNINTERRUPTIBLE POWER SUPPLY (UPS) SCHEDULE

NAME LOCATION USE

NAMEPLATE RATING

ELECTRICAL

INPUT

NUMBER OF

INPUTS

ELECTRICAL

OUTPUT

MAINT.

BYPASS

KEYED

INTERLOCK

FULL LOAD

RUNTIME

(MINUTES)

CABINETS

BATTERY

EXPANSION

SPACE

OUTPUT

ISOLATION

TRANSFORMER

MANUFACTURER MODEL NUMBER ACCESSORIES

kW kVA

UPS-1 COMM RM B002A LEGALLY REQ'D 48 60 480 V / 3 PH - 4W 1 208 V / 3 PH - 4W INTERNAL YES 60 MULTIPLE 0% YES VERTIV LIEBERT EXM 1, 2, 3, 4,5,6

NOTES: ACCESSORIES:

1 SEE SPECIFICATIONS SECTION 263353 FOR ADDITIONAL EQUIPMENT REQUIREMENTS. 1 SPD

2 MANUFACTURER AND MODEL NUMBER ARE BASIS OF DESIGN. OR EQUALS ARE SUBJECT TO APPROVAL. 2 MODBUS COMMUNICATION BOARD

3 3 ACCESS CONTACT BOARD

4 SHUNT TRIP CONTACTS AND REMOTE EMERGENCY POWER OFF SWITCH

5 REDUNDANCY MODULE WITH ADDITIONAL BATTERY CABINET.

6 MAINTENANCE BY-PASS CABINET.

GENERAL NOTES

1. INSTALL ALL WORK IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2023, THE FLORIDA FIRE PREVENTION CODE, THE NATIONAL ELECTRICAL CODE 2020 EDITION, AND ALL CODES, ORDINANCES, RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION AT THIS SITE. WHERE CONFLICTS

OCCUR BETWEEN CODES AND THE CONSTRUCTION DOCUMENTS, THE MOST RESTRICTIVE

REQUIREMENTS SHALL GOVERN.

2. DRAWINGS ARE DIAGRAMMATIC, INDICATIVE OF WORK TO BE FURNISHED AND INSTALLED UNDER THIS

CONTRACT. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL DIMENSIONS.

3. FIELD VERIFY ALL DIMENSIONS AND ALL CONDITIONS. IF THE CONTRACTOR IS UNABLE TO INTERPRET THE CONTRACT DOCUMENTS, CONTRACTOR IS RESPONSIBLE TO REQUEST CLARIFICATION IN WRITING TO THE ARCHITECT. IF CONTRACTOR PROCEEDS WITH ANY WORK BEFORE OBTAINING CLARIFICATION, CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DEFICIENCIES ASSOCIATED THEREWITH.

4. BEFORE SUBMITTING FOR THE WORK, EACH BIDDER WILL BE RESPONSIBLE TO EXAMINE THE PREMISES AND SATISFY HIMSELF AS TO THE EXISTING CONDITIONS UNDER WHICH CONTRACTOR WILL BE OBLIGED TO OPERATE AND COMPLETE THE WORK UNDER THIS CONTRACT. NO ALLOWANCE WILL SUBSEQUENTLY BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR OMISSION ON

CONTRACTOR'S PART.

5. THE CONTRACTOR SHALL PAY FOR ALL INSPECTION PERMITS, CERTIFICATES, CONNECTION FEES, SYSTEM DEMAND CHARGES AND LICENSE FEES IN CONNECTION WITH CONTRACTOR'S WORK.

6. ALL WORK SHALL COMPLY WITH APPLICABLE O.S.H.A. AND E.P.A. REGULATIONS AND GUIDELINES.

7. ERECT AND MAINTAIN ALL REASONABLE PRECAUTIONS FOR SAFETY AND HEALTH INCLUDING POSTING

DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS INCLUDING PROMULGATING SAFETY

REGULATIONS. PROVIDE SAFETY PRECAUTIONS AND BARRICADES FOR PEDESTRIANS AT

CONSTRUCTION VEHICLE ACCESS AND EGRESS LOCATIONS.

8. COORDINATE AND SEQUENCE ALL DEMOLITION, CLEANING AND CONSTRUCTION WORK. SUBMIT A

COMPLETELY DETAILED CONSTRUCTION SCHEDULE PRIOR TO PRE-CONSTRUCTION CONFERENCE.

9. THE CONTRACTOR SHALL STRICTLY BE HELD TO THE PROJECT SCHEDULE. CONTRACTOR SHALL PROVIDE SUFFICIENT MANPOWER AND EQUIPMENT TO FULLY MOBILIZE, PROCEED WITH AND COMPLETE

THE WORK.

10. THE CONTRACTOR SHALL BE RESTRICTED TO AREAS SPECIFIED BY THE OWNER FOR ON-SITE STORAGE

OF CONSTRUCTION MATERIALS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION AND

SECURITY OF ALL EQUIPMENT AND MATERIALS.

11. THE CONTRACTOR SHALL MAINTAIN A CLEAN WORK ENVIRONMENT AT ALL TIMES AND SHALL CLEAN CONSTRUCTION SITE OF ALL DEBRIS AT COMPLETION OF THE JOB AND BEFORE FINAL PAYMENT IS MADE.

12. THE CONTRACTOR SHALL FURNISH "AS-BUILT" DRAWINGS TO THE OWNER AT COMPLETION OF

CONSTRUCTION.

13. CONTRACTOR SHALL GUARANTEE THE WORK AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. THIS GUARANTEE SHALL BE IN ADDITION TO THE WARRANTIES PROVIDED BY

MATERIAL SUPPLIERS AND MANUFACTURERS.

14. CONTRACTOR'S USE OF AN APPROVAL STAMP ON DOCUMENTS SUBMITTED AS SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND SIMILAR SUBMITTALS CERTIFIES THAT THE CONTRACTOR HAS COMPLIED WITH THE CONTRACT DOCUMENT REQUIREMENTS RELATED TO "SHOP DRAWINGS, PRODUCT DATA AND

SAMPLES".

15. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR DEVIATIONS FROM REQUIREMENTS

OF THE CONTRACT DOCUMENTS BY THE ARCHITECT/ENGINEER'S APPROVAL OF SHOP DRAWINGS,

PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS UNLESS THE CONTRACTOR HAS SPECIFICALLY INFORMED THE ARCHITECT/ENGINEER IN WRITING OF SUCH DEVIATION AT THE TIME OF SUBMITTAL AND

THE ARCHITECT/ENGINEER HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION. THE

CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR ERRORS OR OMISSIONS IN SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS BY THE ARCHITECT/ENGINEER'S

APPROVAL THEREOF.

16. NOTE ANY SPECIAL REQUIREMENTS INVOLVED IN INSTALLING THE EQUIPMENT IN THE BUILDING.

DISMANTLING AND REASSEMBLING OF ANY EQUIPMENT SHALL BE DONE AS REQUIRED FOR ENTRY INTO

THE BUILDING AND EQUIPMENT ROOMS.

17. ENTRY AND REMOVAL OF EQUIPMENT FROM THE BUILDING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL REPAIR ANY DAMAGED MATERIALS TO THEIR ORIGINAL CONDITION.

SURFACES SHALL BE REPAIRED TO MATCH THE EXISTING ADJACENT UNDAMAGED SURFACES.

18. SUPPORTS AND HANGERS SHALL PRESENT A NEAT, ORDERLY APPEARANCE.

19. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE WALL ASSEMBLIES AND

ACOUSTICAL WALLS.

20. BEAM AND FLOOR PENETRATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. BEAM

SLEEVES AND BEAM REINFORCING APPROVED BY STRUCTURAL ENGINEER SHALL BE FURNISHED AND

INSTALLED BY THIS CONTRACTOR.

21. THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION. THE OWNER WILL MAKE ALL REASONABLE EFFORTS TO ASSIST THE CONTRACTOR IN COMPLETING THE WORK. COORDINATE ALL

WORK WITH THE OWNER'S DESIGNATED REPRESENTATIVE.

22. EXIT WAYS SHALL BE KEPT CLEAR. IF AN EXIT MUST BE TEMPORARILY BLOCKED, PROVIDE THE

REQUIRED BARRICADE AND DIRECTIONAL SIGNS FOR TEMPORARY EXITING AND SAFETY.

23. REMOVE AND REPAIR OR RE-INSTALL EXISTING CEILING ASSEMBLIES AS REQUIRED. REPLACE ANY

ASSEMBLIES DAMAGED OR SOILED DURING CONSTRUCTION.

24. PROVIDE PROPER PROTECTIVE MEASURES TO PROTECT EXISTING FURNITURE, CARPET AND FINISHES DURING THE COURSE OF CONSTRUCTION. TAKE CARE NOT TO DAMAGE EXISTING SURFACES. REPAIR

TO MATCH EXISTING CONDITIONS AS REQUIRED.

25. SEAL ALL HOLES IN WALLS, CEILINGS, FLOORS, ETC. TO MATCH EXISTING ADJACENT SURFACES WHERE

EQUIPMENT, CONDUIT AND/OR PIPING ARE REMOVED.

26. EXISTING EQUIPMENT IS THE PROPERTY OF THE OWNER AND SHALL BE DISPOSED OF AS DIRECTED BY THE OWNER. DISPOSE OF ALL MATERIALS AND EQUIPMENT SHOWN TO BE REMOVED IN ACCORDANCE

WITH LOCAL REGULATIONS.

27. ITEMS REMOVED AND SAVED FOR REUSE SHALL BE PROTECTED FROM DAMAGE DURING

CONSTRUCTION. CONTRACTOR SHALL IDENTIFY ANY DEFECTIVE MATERIALS PRIOR TO DEMOLITION.

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGE TO MATERIALS AT PROJECT COMPLETION NOT

IDENTIFIED PRIOR TO DEMOLITION.

DRAWING INDEX

ELECTRICAL DEMOLITION NOTES

1. UNLESS OTHERWISE NOTED, REMOVE ALL ELECTRICAL MATERIALS AND EQUIPMENT FROM AREAS

INDICATED FOR DEMOLITION.

2. REMOVE ALL ELECTRICAL EQUIPMENT (CONDUIT, POWER & CONTROL WIRING, DISCONNECT SWITCHES, STARTERS,ETC.) RELATED TO EQUIPMENT BEING REMOVED OR REPLACED.

3. REMOVE UNUSED CONDUIT TO THE EXTENT NECESSARY TO ACCOMMODATE NEW WORK AND WHERE CONDUIT IS VISIBLE ABOVE THE FLOOR LINE. EXISTING UNUSED CONDUIT WHICH IS CONCEALED, AND WHICH DOES NOT INTERFERE WITH THE WORK, MAY REMAIN IN PLACE. SEAL ABANDONED LINES THAT

REMAIN IN PLACE BEHIND WALLS OR FLOOR SURFACES. REMOVE EXISTING UNUSED WIRES.

4. WIRING AND CONDUIT TO ELECTRICAL DEVICES BEING REMOVED SHALL BE REMOVED BACK TO NEAREST JUNCTION BOX. ANY DEVICES DOWNSTREAM FROM THESE POINTS SHALL REMAIN OPERABLE.

5. CONTRACTOR SHALL, UPON COMPLETION OF WORK, ENSURE ALL EXISTING CIRCUITS ADJACENT THE

REMODELED AREA(S) ARE IN PROPER WORKING CONDITION.

6. CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS TO ELECTRICAL DEVICES REQUIRED TO

ACCOMMODATE NEW WALLS AND CEILINGS. BECAUSE OF THE NATURE OF THE JOB, UNFORESEEN

INTERFERENCES MAY OCCUR. CLOSE COORDINATION BETWEEN TRADES IS REQUIRED. VERIFY ALL

CONNECTION REQUIREMENTS BEFORE ROUGH-IN.

ELECTRICAL GENERAL NOTES

1. WIRING SHALL BE COPPER, TYPE THHN/THWN-2 IN RACEWAY UNLESS NOTED OTHERWISE. RIGID ELECTRICAL NON-METALLIC SCHEDULE 40 PVC SHALL BE USED IN SLABS AND BELOW GRADE ; RIGID STEEL CONDUIT (RSC) SHALL BE USED WHERE EXPOSED TO PHYSICAL DAMAGE; ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ELSEWHERE WHERE APPROVED BY N.E.C. AND LOCAL CODES. FLEXIBLE METAL CONDUIT (FMC) SHALL BE STEEL AND SHALL BE USED TO CONNECT MOVEABLE EQUIPMENT AND/OR SUBJECT TO VIBRATION; LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LFMC) SHALL BE USED

OUTDOORS OR WHERE SUBJECT TO MOISTURE.

2. CONDUIT SHALL BE STRAPPED IN ACCORDANCE WITH REQUIREMENTS OF N.E.C.

3. CONTRACTOR SHALL BOND AND GROUND SYSTEMS AND EQUIPMENT PER ARTICLE 250 OF N.E.C.

PROVIDE A GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH ARTICLE 250-122 N.E.C. ON ALL

RECEPTACLES AND POWER BRANCH CIRCUITS.

4. THE CONTRACTOR SHALL COORDINATE THE CIRCUIT REQUIREMENTS WITH THE MANUFACTURER OF THE ACTUAL EQUIPMENT FURNISHED UNDER OTHER DIVISIONS OF WORK. THE CIRCUIT BREAKER, WIRE

AND CONDUIT SHALL BE SIZED AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER.

5. CIRCUIT BREAKERS SHALL BE BOLT-IN TYPE.

6. PROVIDE A LAMINATED PLASTIC NAMEPLATE IDENTIFYING EACH NEW PANELBOARD, MOTOR STARTER

AND DISCONNECT SWITCH. LETTERING SHALL BE 1/2" MINIMUM AND SHALL IDENTIFY EQUIPMENT

SERVED, FEEDER ORIGINATION AND CIRCUIT NUMBER. SECURE NAMEPLATE WITH SCREWS TO

EQUIPMENT TO BE IDENTIFIED. PLASTIC TAPE IS NOT APPROVED.

7. EQUIPMENT TO BE FURNISHED UNDER OTHER SECTIONS OF THE SPECIFICATIONS THAT REQUIRE ELECTRICAL CONNECTIONS SHALL BE RECEIVED AND SET WITH ROUGH-IN AND FINAL CONNECTIONS

MADE UNDER THESE SECTIONS.

8. DEVICE MOUNTING HEIGHTS INDICATED SHALL BE TO DEVICE CENTER LINE.

9. RELOCATE, AS REQUIRED, ANY EXISTING WIRE AND CONDUIT WHICH INTERFERES WITH INSTALLATION

OF THE NEW WORK.

10. EACH FEEDER, UNGROUNDED CONDUCTOR, AND GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY

PHASE OR LINE AND SYSTEM AT ALL TERMINATION, CONNECTION, AND SPLICE POINTS.

ABBREVIATIONS

ACT ABOVE COUNTERTOP

AFC AVAILABLE FAULT CURRENT

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ATS AUTOMATIC TRANSFER SWITCH

BF BELOW RAISE COMPUTER FLOOR

C CONDUIT

CLG DEVICE LOCATED ON CEILING

CNT CONTACTOR

DISC DISCONNECT

DN DOWN

EC ELECTRICAL CONTRACTOR

EM FIXTURE PROVIDED WITH EMERGENCY BATTERY OR ON EMERGENCY CIRCUIT

ER EXISTING ELECTRICAL DEVICE RELOCATED TO NEW POSITION

EX EXISTING ELECTRICAL DEVICE TO REMAIN

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFIB GROUND FAULT INTERRUPTER BREAKER

G GROUND

GRC GALVANIZED RIGID CONDUIT

LCP LIGHTING CONTROL PANEL

NIS NOT IN SCOPE

PGB POWER GROUNDING BAR

PNL ELECTRICAL PANEL

RE REPLACE EXISTING ELECTRICAL DEVICE (AND COVER PLATE) AT THIS LOCATION

REL RELOCATE EXISTING ELECTRICAL DEVICE

TGB TELECOMMUNICATIONS GROUNDING BAR

TP TAMPER PROOF DEVICE

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

WP WEATHERPROOF

EXISTING SWITCH TO BE REMOVED

POWER

DUPLEX RECEPTACLE - 120 VOLT, 20 AMP, 3 POLE GROUNDING TYPE, MOUNT

18" AFF WITH GROUND PRONG UP UNLESS NOTED OTHERWISE.

WIRE IN CONDUIT - CONCEALED IN WALL OR CEILING.

WIRE IN CONDUIT - CONCEALED IN FLOOR OR UNDERGROUND.

CONDUIT - STUB OUT AND CAP

HOMERUN TO PANEL - ARROW INDICATE NUMBER OF CIRCUITS. SHORT SLASH

MARK(S) INDICATE NUMBER OF PHASE CONDUCTORS. LONG SLASH MARK(S)

INDICATE NEUTRAL CONDUCTOR(S). LONG SLASH MARK WITH HOOK INDICATES

GREEN GROUND WIRE; WHERE NOT SHOWN GROUND WIRE IS STILL REQUIRED

IN EACH FEEDER, LIGHTING, RECEPTACLE, AND POWER BRANCH CIRCUIT. NO

SLASH MARKS INDICATE 2 CURRENT CARRYING CONDUCTORS AND GROUND

WIRE. THERE SHALL BE NO SHARED NEUTRALS BETWEEN MULTIPLE CIRCUITS.

ELECTRICAL PANEL - 120/208 VOLT

ELECTRICAL PANEL - 277/480 VOLT

EMERGENCY "STOP" PUSH-BUTTON

POWER GROUNDING BARPGB

* EQUIPMENT SIZES WILL BE INDICATED AS FOLLOWS:

STARTER NEMA SIZE

(NO # SHOWN FOR

DISC SWITCHES)

AMP RATING & POLE QTY.

NEMA ENCLOSED TYPE

NON-FUSED (AS SHOWN)

1 / 30A / 3P / 3R / NF

25AF

25ACB

FUSED (AS SHOWN)

CIRCIUT BREAKER AMPS (AS SHOWN)

J JUNCTION BOX - 4" SQUARE (UNO)

DISCONNECT SWITCH - SEE DRAWING OR MECHANICAL EQUIPMENT

SCHEDULE FOR SIZE

DEMOLITION

ELECTRICAL DEVICES TO BE REMOVED

RELOCATE EXISTING DEVICE TO POSITION SHOWN

REL

NTS

PARTIAL POWER RISER DIAGRAM

150A150A

PANEL

'CPB'

100A

208/120V

UPS

BASEMENT ELEC RM B010

LOAD CENTER

PANELS

100A

4#3, #8G, 1 1/4"C

4#4/0, #4G, 2 1/2"C

4#2/0,#4G, 2 1/2"C

P1-225A P2-225A P3-225A P4-225A

UNNAMED

PANEL

400A

480/277V 3PH

GENERAL NOTES

1. NEW WORK AND DEVICES ARE SHOWN BOLD. ALL ELSE IS EXISTING TO REMAIN.

BASEMENT RM B002A

ATS#2600A

DISC

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

G

H

B

C

D

E

F

G

H

A

1 2 3 4 5 6 7 8 9 10

DRAWING NO.

SUBMITTAL

PHASE CHECK

REVISIONS

SHEET TITLE

SEAL

DRAWNDATE

Florida Registry #2485

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2ENGINEERING, INC., IS PROHIBITED.

H2E PROJECT No.

114 EAST 5th AVENUE

TALLAHASSEE, FL 32303

PHONE 850.224.7922

www.H2Engineering.com

Anthony D. Wyrick, P.E. #98346

/2

/2

:0

:5

A

M A u to d e s k D o c s /2

-1

F la C o m m e rc e

C a ld w e ll

B ld g U

P S r e p la c e m e n t/

-1

M

E P

C e n tr a l_

F la

.C o m m e rc e

C a ld w e ll

B ld g U

P S r e p la c e m e n t_ R

.r v t

24187

E0.1

GENERAL NOTES &

LEGENDS

CONSTRUCTION DOCUMENTS 2025-03-14 GAG

CALDWELL BLDG, UPS

REPLACEMENT

24-187

107 E MADISON ST,

TALLAHASSEE, FL 32399

FLORIDA DEPARTMENT

OF COMMERCE

ADW

E0.1 GENERAL NOTES & LEGENDS

E1.1 BASE FLOOR PLAN

# Description Date

1 ADDENDUM #1 04/24/24

1 1

Exhibit A

B004

MECH. RM.

B003

LOBBY

B009

ELEC.

RM.

EXIST.

ELEV.

B010

W.TRANSFORMER

RM.

B022

COMPUTER ROOM

B004

MECH. RM.

B003

LOBBY

B009

ELEC.

RM.

EXIST.

ELEV.

B010

W.TRANSFORMER

RM.

B022

COMPUTER ROOM

CPA CP

CPB

LB3

ATS

#2DP3

LBD

150kVA

300kVA

150kVA

ROUTE NEW FEEDER TO

EXISTING POWER CENTER.

REFER TO RISER DIAGRAM

FOR FEEDER INFORMATION.

POWER

CENTER

200A

DISC

600A

DISC

UNNAMED PANEL

UPS-1

RELOCATE EXISTING PANEL.

RECONNECT EXISTING

CIRCUITS PRESERVED

DURING DEMOLITION. EXTEND

#10 WIRE, #10G IN 3/4 CONDUIT

TO MAKE NEW CONNECTION.

CPB

ER

CONNECT TO EXISTING FEEDER

9' - 0"

AVAILABLE WALL SPACE

CPB

CPA CP

ATS

#2

UPS1 UPS2

LB3

DP3

LBD

150kVA

300kVA

POWER

CENTER

DEMOLISH UPS-2 CIRCUIT

BACK TO PANEL. MARK

BREAKER AS SPARE AND

TURN TO THE OFF POSITION.

UNNAMED PANEL

200A

DISC

600A

DISC

DEMOLISH EXISTING UPS-1 AND

UPS-2. PRESERVE EXISTING

UPS-1 CIRCUIT FOR REUSE

DURING RENOVATION.

CPB REL

TEST EXISTING CIRCUITS TO VERIFY

ABANDONED AND IN-USE CIRCUITS.

CONFIRM ABANDONED CIRCUITS WITH THE

OWNER AND DEMOLISH. DISCONNECT

EXISTING IN-USE CIRCUITS AND PRESERVE

FOR REUSE DURING RENOVATION.

NIS

DEMOLITION GENERAL NOTES

1. ALL DEVICES SHOWN DASHED ARE TO BE DEMOLISHED. ALL OTHER DEVICES ARE EXISTING TO REMAIN.

2. WHERE DEVICE IS SHOWN TO BE REMOVED IN EXISTING WALL TO REMAIN , REMOVE BACK BOX AND FINISH

WALL / FLOOR / CEILING TO MATCH SURROUNDING AREA.

3. DISCONNECT WIRING AT PANEL OR NEAREST DEVICE OR JUNCTION BOX TO REMAIN ON SAME CIRCUIT.

4. WHERE SURFACE RACEWAYS EXISTS TO DEVICE , REMOVE RACEWAY BACK TO POINT BEHIND FINISHED

SURFACE , INCLUDING BACK BOX RECESS IN SURFACE'S PATCH SURFACE.

5. SEQUENCE DEMOLITION OF THE EXISTING UPS TO PROVIDE MINIMAL DOWNTIME TO THE SYSTEM DOWN STREAM OF THE UPS. PROVIDE TEMPORARY BYPASS AS NECESSARY TO ENSURE CONTINUITY OF THE DOWN

STREAM SYSTEM DURING THE UPS DEMOLITION.

RENOVATION GENERAL NOTES

1. ALL DEVICES SHOWN SHADED ARE EXISTING. ALL OTHER DEVICES ARE NEW.

2. COORDINATE WITH OWNER ANY REQUIRED DOWN TIME TO FACILITATE CONNECTION TO THE NEW UPS SYSTEM. PROVIDE LINE ITEM PROVISIONS IN THE BID TO COVER WEEKEND OR AFTERHOURS WORK

REQUIRED TO MAKE THE NEW CONNECTION.

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

G

H

B

C

D

E

F

G

H

A

1 2 3 4 5 6 7 8 9 10

DRAWING NO.

SUBMITTAL

PHASE CHECK

REVISIONS

SHEET TITLE

SEAL

DRAWNDATE

Florida Registry #2485

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2ENGINEERING, INC., IS PROHIBITED.

H2E PROJECT No.

114 EAST 5th AVENUE

TALLAHASSEE, FL 32303

PHONE 850.224.7922

www.H2Engineering.com

Anthony D. Wyrick, P.E. #98346

/2

/2

:0

:5

A

M A u to d e s k D o c s /2

-1

F la C o m m e rc e

C a ld w e ll

B ld g U

P S r e p la c e m e n t/

-1

M

E P

C e n tr a l_

F la

.C o m m e rc e

C a ld w e ll

B ld g U

P S r e p la c e m e n t_ R

.r v t

24187

E1.1

BASE FLOOR PLAN

CONSTRUCTION DOCUMENTS 2025-03-14 GAG

CALDWELL BLDG, UPS

REPLACEMENT

24-187

107 E MADISON ST,

TALLAHASSEE, FL 32399

FLORIDA DEPARTMENT

OF COMMERCE

ADW

PROJECT

NORTH

1/4" = 1'-0"

BASE FLOOR PLAN RENO

PROJECT

NORTH

1/4" = 1'-0"

BASE FLOOR PLAN DEMO

# Description Date

1 ADDENDUM #1 04/24/24BASEMENT KEYPLAN

Sheets
E0.1 - GENERAL NOTES & LEGENDS
E1.1 - BASE FLOOR PLAN
G0.0 - COVER SHEET

File details come from the government source that posted it. Updated .